Installation Instructions

24ACB, 24ACC

Single---Stage Comfort

t

Series Air Conditioners

with Puron

r

Refrigerant

1---1/2 To 5 Nominal Tons (Sizes 18 to 60)

SAFETY CONSIDERATIONS

Improper installation, adjustment, alteration, service, maintenance,
or use can cause explosion, fire, electrical shock, or other

conditions which may cause death, personal injury, or property
damage. Consult a qualified installer, service agency, or your

distributor or branch for information or assistance. The qualified

installer or agency must use factory--authorized kits or accessories
when modifying this product. Refer to the individual instructions

packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses, protective clothing,

and work gloves. Use quenching cloth for brazing operations.
Have fire extinguisher available. Read these instructions

thoroughly and follow all warnings or cautions included in

literature and attached to the unit. Consult local building codes
and current editions of the National Electrical Code ( NEC ) NFPA

70. In Canada, refer to current editions of the Canadian electrical
code CSA 22.1.

Recognize safety information. This is the safety--alert symbol

When you see this symbol on the unit and in instructions or
manuals, be alert to the potential for personal injury. Understand

these signal words; DANGER, WARNING, and CAUTION. These

words are used with the safety--alert symbol. DANGER identifies
the most serious hazards which

will

result in severe personal injury

or death. WARNING signifies hazards which

could

result in

personal injury or death. CAUTION is used to identify unsafe

practices which

would

result in minor personal injury or product

and property damage. NOTE is used to highlight suggestions
which

will

result in enhanced installation, reliability, or operation.

!

WARNING

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal

injury or death.
Before installing, modifying, or servicing system, main

electrical disconnect switch must be in the OFF position.

There may be more than 1 disconnect switch. Lock out and

tag switch with a suitable warning label.

INSTALLATION INSTRUCTIONS

NOTE

: In some cases noise in the living area has been traced to

gas pulsations from improper installation of equipment.

1. Locate unit away from windows, patios, decks, etc. where

unit operation sound may disturb customer.

2. Ensure that vapor and liquid tube diameters are appropriate

for unit capacity.

3. Run refrigerant tubes as directly as possible by avoiding un-

necessary turns and bends.

4. Leave some slack between structure and unit to absorb vi-

bration.

5. When passing refrigerant tubes through the wall, seal open-

ing with RTV or other pliable silicon--based caulk. (See Fig.
1.)

6. Avoid direct tubing contact with water pipes, duct work,

floor joists, wall studs, floors, and walls.

7. Do not suspend refrigerant tubing from joists and studs with

a rigid wire or strap which comes in direct contact with
tubing.(See Fig. 1.)

8. Ensure that tubing insulation is pliable and completely sur-

rounds vapor tube.

9. When necessary, use hanger straps which are 1 in. (25.4

mm) wide and conform to shape of tubing insulation. (See
Fig. 1.)

10. Isolate hanger straps from insulation by using metal sleeves

bent to conform to shape of insulation.

INSULATION

VAPOR TUBE

LIQUID TUBE

OUTDOOR WALL INDOOR WALL

LIQUID TUBE

VAPOR TUBE

INSULATION

CAULK

Avoid contact between tubing and structure

NOTE:

THROUGH THE WALL

HANGER STRAP

(AROUND VAPOR

TUBE ONLY)

JOIST

1” (25.4 mm) MIN.

SUSPENSION

A94026

Fig. 1 -- Piping Installation

The outdoor unit contains system refrigerant charge for operation

with AHRI rated indoor unit when connected by 15 ft. (4.57 m) of
field--supplied or factory accessory tubing. For proper unit

operation, check refrigerant charge using charging information
located on control box cover and/or in the Check Charge section of

this instruction.

IMPORTANT

: Maximum liquid--line size is 3/8--in. OD for all

residential applications including long line.

IMPORTANT

: Always install the factory--supplied liquid--line

filter drier. If replacing the filter drier, refer to Product Data Digest
for appropriate part number. Obtain replacement filter driers from
your distributor or branch.

Summary of Contents for Single-Stage Comfort 24ACB

Page 1: ...must be in the OFF position There may be more than 1 disconnect switch Lock out and tag switch with a suitable warning label INSTALLATION INSTRUCTIONS NOTE In some cases noise in the living area has been traced to gas pulsations from improper installation of equipment 1 Locate unit away from windows patios decks etc where unit operation sound may disturb customer 2 Ensure that vapor and liquid tub...

Page 2: ...ieve pressure and recover all refrigerant before system repair or final unit disposal Use all service ports and open all flow control devices including solenoid valves Federal regulations require that you do not vent refrigerant to the atmosphere Recover during system repair or final unit disposal CAUTION UNIT DAMAGE HAZARD Failure to follow this caution may result in equipment damage or improper ...

Page 3: ...of filter drier in liquid line is required 2 Filter drier must be wrapped in a heat sinking material such as a wet cloth while brazing Refer to Fig 3 and install filter drier as follows 1 Braze 5 in liquid tube to the indoor coil 2 Wrap filter drier with damp cloth 3 Braze filter drier to above 5 in 127 mm liquid tube Flow arrow must point towards indoor coil 4 Connect and braze liquid refrigerant...

Page 4: ...perature is higher than indicated or reclaim refrigerant if temperature is lower Allow a tolerance of 3_F 1 7_C Units with Indoor Piston Units installed with indoor pistons require charging by the superheat method The following procedure is valid when indoor airflow is within 21 percent of its rated CFM 1 Operate unit a minimum of 15 minutes before checking charge 2 Measure suction pressure by att...

Page 5: ...6 47 114 46 112 44 110 43 108 42 106 41 439 118 48 116 47 114 46 112 44 110 43 108 42 450 120 49 118 48 116 47 114 46 112 44 110 43 462 122 50 120 49 118 48 116 47 114 46 112 44 474 124 51 122 50 120 49 118 48 116 47 114 46 Table 3 Superheat Charging AC Only OUTDOOR TEMP _F EVAPORATOR ENTERING AIR TEMPERATURE _F WB 50 52 54 56 58 60 62 64 67 68 70 72 74 76 55 9 12 14 17 20 23 26 29 32 35 37 40 42 ...

Page 6: ... 59 10 45 47 49 51 53 55 57 59 61 12 47 49 51 53 55 57 59 61 63 14 49 51 53 55 57 59 61 63 65 16 51 53 55 57 59 61 63 65 67 18 53 55 57 59 61 63 65 67 69 20 55 57 59 61 63 65 67 69 71 22 57 59 61 63 65 67 69 71 73 24 59 61 63 65 67 69 71 73 75 26 61 63 65 67 69 71 73 75 77 28 63 65 67 69 71 73 75 77 79 30 65 67 69 71 73 75 77 79 81 32 67 69 71 73 75 77 79 81 83 34 69 71 73 75 77 79 81 83 85 36 71 ...

Page 7: ...rical wire or metal conduit when installed in accordance with existing electrical codes Connect Ground and Power Wires Connect ground wire to ground connection in control box for safety Connect power wiring to contactor as shown in Fig 6 DISCONNECT PER N E C AND OR LOCAL CODES CONTACTOR GROUND LUG FIELD GROUND WIRING FIELD POWER WIRING A91056 Fig 6 Line Connections Connect Control Wiring Route 24 ...

Page 8: ...eset Adjust charge by adding or removing 0 6 oz ft of 3 8 liquid line above or below 15ft 4 57 m respectively For standard refrigerant line lengths 80 ft 24 38 m or less allow system to operate in cooling mode at least 15 minutes If conditions are favorable check system charge by subcooling method If any adjustment is necessary adjust charge slowly and allow system to operate for 15 minutes to sta...

Page 9: ...700 psig service pressure rating S Leak detectors should be designed to detect HFC refrigerant S Puron refrigerant as with other HFCs is only compatible with POE oils S Vacuum pumps will not remove moisture from oil S Do not use liquid line filter driers with rated working pressures less than 600 psig S Do not leave Puron suction line filter driers in line longer than 72 hours S Do not install a s...

Page 10: ...rris St S Indianapolis IN 46231 Printed in U S A Edition Date 07 10 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No 24ACB C 3SI Replaces 24ACB C 2SI 24ACB 24ACC ...

Reviews: