background image

30

HEAT STAGE 2 — The Heat Stage 2 point provides the state
of the Heating 2 output.
Heating Stage 2: Display Units:

Discrete ASCII

Default Value:

Off

Display Range:

Off/On

Network Access: Read Only

HEAT STAGE 3, EXHAUST FAN, OR REVERSING
VALVE — This point displays the commanded state of auxil-
iary output. This output can be configured to control a third
stage of heat, an exhaust fan or a reversing valve on some heat
pump units. 

In the exhaust fan mode with continuous exhaust con-

figured, this point may control a bank of lights or another
indicator that should remain ON whenever the controller is in
the occupied mode.
Heat 3, Exhaust,
Rev Valve:

Display Units:

Discrete ASCII

Default Value:

Off

Display Range:

Off/On

Network Access: Read Only

ENTHALPY — This point displays the current status of an
outdoor air or differential enthalpy input. This point may be
broadcast to other controllers or received from a controller
which supports global broadcast of the ENTH variable.
Enthalpy:

Display Units:

Discrete ASCII

Default Value:

High

Display Range:

High/Low

Network Access: Read/Write

INDOOR AIR QUALITY (IAQ) — The  Air  Quality  point
displays the indoor air quality reading from a CO

2

 sensor

installed in the space. The CO

2

 sensor maintains differential

indoor air quality for demand control ventilation per ASHRAE
Standard 62-1999. The controller can be configured to generate
an alarm when the control is in occupied mode and the CO

2

level exceeds the high or low limit set. 
Indoor Air 
Quality (ppm):

Display Units:

None shown (parts per

 million 

implied)

Default Value:

0

Display Range: 

0 to 5000

Network Access: Read/Write

INDOOR AIR QUALITY SET POINT — This  point  dis-
plays the current Indoor Air Quality set point. The set point is
determined by the configured Indoor Air Quality differential
and the current outdoor air quality value. If an outdoor air
quality value is not received, the controller will assume a
default outdoor level of 400 ppm and calculate the set point
using that value.
Indoor Air Quality
Set Point:

Display Units:

None shown (parts per

 million 

implied)

Default Value:

0

Display Range: 

0 to 5000

Network Access: Read Only

OUTDOOR AIR QUALITY — This point displays the read-
ing from an outdoor air quality sensor. This point supports
global broadcast of outdoor air quality on a network.
Outdoor Air Quality
Set Point:

Display Units:

None shown (parts per

 million 

implied)

Default Value:

0

Display Range: 

0 to 5000

Network Access: Read/Write

FIRE SHUTDOWN — While in sensor control mode, this
point can be used to receive a signal from a smoke detector or
fire panel to shut down the Supply Fan, all heating and cooling
stages, and to close the economizer. 
Fire Shutdown:

Display  Units:

Discrete ASCII

Default Value:

Normal

Display Range:

Normal/Alarm

Network Access: Read/Write

SPT OFFSET — This point displays the value of the Space
Temperature offset calculated from the input of a T56 sensor
slide bar.
SPT Offset:

Display Units:

Delta Degrees F 
(Delta Degrees C)

Default Value:

0.0

Display Range:

–15 to 15

Network Access: Read/Write

COMPRESSOR 1 — This point displays the commanded
state of the compressor 1 output.
Compressor 1:

Display  Units:

Discrete ASCII

Default Value:

Off

Display Range:

Off/On

Network Access: Read Only

COMPRESSOR 2 — This point displays the commanded
state of the compressor 2 output.
Compressor 2:

Display  Units:

Discrete ASCII

Range:

Off/On

Default Value:

Off

Network Access: Read Only

COMPRESSOR 

SAFETY 

— 

When the controller is in

sensor mode, this point can be used to monitor the status of the
compressor trouble output supplied with some equipment.
When the input is detected, the controller will energize all
available stages to satisfy the demand and issue a compressor
trouble alert on the communications network.
Compressor
Safety:

Display  Units:

Discrete ASCII

Display  Range:

Off/On

Default Value:

Off

Network Access: Read Only

Thermostat Control Input Screen — 

The Thermo-

stat Control Input Display is used to display the input status of
equipment requests from the thermostat (TSTAT). See Table 8.

Alarm Service Configuration Screen — 

The Alarm

Service Configuration is used to configure the alarms used on
the PremierLink™ controller. See Table 9.

ALARM  ROUTING  CONTROL  — The  Alarm  Routing
Control indicates which CCN system software or devices will
receive and process alarms sent by the PremierLink controller.
This decision consists of eight digits which can be set to zero or
one. A setting of one indicates alarms should be sent to this
device. A setting of zero disables alarm processing for that
device. Currently the corresponding digits are configured for
the following devices: first digit is for user interface software
(ComfortWORKS

®

, ComfortVIEW™, etc.); second digit is

for Autodial Gateway or Telink; fourth digit is for Alarm Print-
er Interface Module, DataLINK™ module; digits 3 and 5
through 8 are unused.
Alarm Routing
Control:

Range:

00000000 to 1111111  

Default Value:

00000000 

Summary of Contents for PREMIERLINK 33CSPREMLK

Page 1: ...nts Display Screen 28 Thermostat Control Input Screen 30 Alarm Service Configuration Screen 30 Controller Identification Screen 31 Holiday Configuration Screen 31 Occupancy Configuration Screen 32 Set...

Page 2: ...on 33ZCSENCO2 sensor is an indoor wall mounted sensor with an LED light emitting diode display 33ZCT55CO2 sensor is an indoor wall mounted sensor without display The CO2 sensor also includes a space t...

Page 3: ...de 3 Use 4 connector Molex with red white and black wires to connect the communication wires Verify the color codes in Table 2 to ensure the Red wire connects to Terminal 1 Connect the White ground wi...

Page 4: ...U YEL RED ORN PNK PremierLink Connections 40RM Connections 38AKS Terminal Board TB2 W2 R Y1 Y2 W1 G C X WHT WHT IFC C2 C1 40RM 40RMQ 40RMS HEAT ACCESSORY W2 W1 C 4 10 9 8 3 2 1 CCSV CCR CR2 CCR LLSV C...

Page 5: ...T FOR DUAL TRANSFORMER EQUIPTMENT RELAYS WHT BLU YEL RED ORN PNK PremierLink Connections 40RM Connections 38AKS Terminal Board TB3 W2 R Y1 Y2 W1 G C X WHT WHT IFC C2 C1 CCR 40RM 40RMQ 40RMS HEAT ACCES...

Page 6: ...S3 EXH RVS RED RED J8 J1 PWR CUT TO ISOLATE CONTROLLER POWER CUT FOR DUAL TRANSFORMER EQUIPTMENT RELAYS WHT BLU YEL RED ORN PNK PremierLink Connections 38AH Connections ACCESSORY RELAY PACKAGE IFR CR2...

Page 7: ...heat pump units 2 Configure AUXOUT to 3 for reversing valve 3 Configure PremierLink control for 2 stage heat and single stage cool 4 If IAQ is high priority wire HS2 to W1 If not wire HS1 to W1 Fig 2G...

Page 8: ...ay 24 VAC 1A J8 9 HEAT STAGE 2 HS2 DO Relay 24 VAC 1A J8 6 HEAT 3 EXHAUST REVERSING VALVE HS3 EXH RVS DO Relay 24 VAC 1A J8 3 AI Analog Input DI Digital Input DO Digital Output RED RED BRN GRN FAN CMP...

Page 9: ...tal screws field supplied 6 Use 20 gage wire to connect the sensor to the controller The wire is suitable for distances of up to 500 ft Use a three conductor shielded cable for the sensor and set poin...

Page 10: ...uter jacket of the cable Do not pull or draw cable with a force that may harm the physical or electrical properties Avoid splices in any control wiring Perform the following steps to connect the SAT s...

Page 11: ...is recommended For installation where it is not necessary to reach the control it may be mounted higher on the wall or on the ceiling provided the location represents a good sampling of air Wiring the...

Page 12: ...LK SENSOR 2 SENSOR 1 RED RED BLK SENSOR 3 SENSOR 4 BLK BLK RED RED RED BLK BLK SENSOR 8 SENSOR 9 SENSOR 5 RED BLK SENSOR 6 SENSOR 7 BLK RED SPACE TEMPERATURE AVERAGING 4 SENSOR APPLICATION SPACE TEMPE...

Page 13: ...5SPT 33ZCT56SPT 33ZCT58SPT Space Temperature Sensors 33ZCSENSAT Supply Air Temperature Sensor 33ZCSENCO2 Outdoor and 33ZCT55CO2 33ZCT56CO2 Indoor Air Quality Sensors OAT Outdoor Air Temperature Sensor...

Page 14: ...O 2 Sensor 33ZCT55CO2 33ZCT56CO2 NOTE No wire is connected to connector J 5 pin 4 You must relocate a wire from an unused terminal Typically one of the red wires from connector J 4 may be used for thi...

Page 15: ...red wires from J4 connector to prevent 24 vac shorting other components or ground Inputs on J4 are 24 vac Red leads are voltage source Fig 9 PremierLink Controller Sensor Wiring With Programmable or N...

Page 16: ...move red wire from J4 9 to prevent 24 vac shorting out other components or ground Inputs on J4 are 24 vac Red leads are voltage source Fig 10 PremierLink Field Installed Controller Sensor Wiring Discr...

Page 17: ...3 2 1 2 1 H G 24 VAC OR 24 VDC NC ALARM RELAY CONTACTS COM NO 0 10VDC SIG COM J5 3 4 20mA J5 2 Fig 12 Outdoor Air Quality CO2 Sensor 33ZCSENCO2 Typical Wiring Diagram Fig 13 Outdoor Air Quality Sensor...

Page 18: ...control the enthalpy switch receiver option and the outdoor and return air sensor option Either option can be used to indicate when the outdoor air is suitable for free cooling ENTHALPY SWITCH RECEIVE...

Page 19: ...he indoor enthalpy The LOW Enthalpy terminal is energized when the outdoor enthalpy is lower than the indoor enthalpy The relay output is wired to the unit economizer which will open or close dependin...

Page 20: ...enthalpy sensor will not calculate enthalpy OUTDOOR AND RETURN AIR ENTHALPY SEN SORS The differential enthalpy control is supplied as a field installed accessory to be used with the Economizer damp e...

Page 21: ...e and remove 1 2 in of insulation from each conductor 6 Connect the RED wire to spade connector on the sensor Connect the BLK wire to S spade connector on the sensor Use wire nuts or closed end crimp...

Page 22: ...emove power from unit 2 Remove the logic module from the actuator and discard 3 Mount the adapter onto the actuator by gently pushing the adapter onto terminals P1 and P of actuator 4 NOTE Be sure the...

Page 23: ...ierLink Controller is grounded and actuator is grounded on common side then common wire from PremierLink controller J9 2 is not needed Fig 25 PremierLink Controller Wiring Differential Enthalpy Contro...

Page 24: ...erLink controller connect the pink wire on actuator to purple wire on PremierLink J9 1 See Fig 30A For the Belimo Actuator connect the white wire on the ac tuator to J9 1 on the PremierLink controller...

Page 25: ...UATOR 50TJ400812 M9206 GGC 2 ECONOMIZER 12 PIN HARNESS RED 24 VAC 1 2 3 4 5 BRN TRANSFORMER GROUND 6 7 8 9 10 11 12 PNK PL6 4 20mA TO J9 1 ON PREMIERLINK CONTROLLER 12 PIN FEMALE MOLEX CONNECTOR 12 8...

Page 26: ...the power has been restored To enable the feature again the switch must be put back to the 0 position and power must be restored this prevents subsequent resets to factory defaults if the switch is l...

Page 27: ...ator See the base unit controls and troubleshooting guide for more information Pressing any key while in the default display mode will cause the Navigator to enter its manual mode In this mode all sub...

Page 28: ...lt Value 0 0 Display Range 40 0 to 245 0 Network Access Read Write OUTDOOR AIR TEMPERATURE Temperature of the air leaving the unit downstream of any cool or heat sources measured by a 10K thermistor T...

Page 29: ...er timer value to zero will provide the same function The value of the timer is stored in EEPROM to protect it in the event of a power failure This is done periodically every 24 hours The filter timer...

Page 30: ...wn parts per million implied Default Value 0 Display Range 0 to 5000 Network Access Read Write FIRE SHUTDOWN While in sensor control mode this point can be used to receive a signal from a smoke detect...

Page 31: ...ality Low Limit Display Units PPM implied Display Range 0 0 to 5000 0 Default Value 0 0 Indoor Air Quality High Limit Display Units PPM implied Display Range 0 0 to 5000 0 Default Value 1200 0 Table 9...

Page 32: ...mes will take effect on a day configured as a holiday A zero means the schedule period will not apply to that day Day of week Range 0 or 1 Default Values 11111111 for period 1 00000000 for the rest of...

Page 33: ...pecifies the value for Purge Minimum Damper Position for High Outdoor Air temperature conditions IAQ Pre Occupancy Purge Algorithm shall use this value whenever Outdoor Air Temperature is above or at...

Page 34: ...e 3 0 Derivative Gain Range 20 0 to 20 0 Default Value 5 0 Starting Value Units Degrees F Range 40 0 to 120 0 Default Value 75 0 STAGED HEATING The Staged Heating function is used for two position val...

Page 35: ...be sent to the device The sign of the submaster gain limit determines the direction in which the output will be driven in response to a given error The gain is expressed in percent change in output p...

Page 36: ...and the supply air temperature goes below Lockout Temperature set point the compressor will cycle to maintain the supply air set point The minimum on and off times and stage up and down timers will st...

Page 37: ...ing capacity is limited When Demand Limit option is enabled the control will re spond to the Loadshed Controller commands such as Redline Alert Shed Unshed and Redline Cancel Demand Limiting Range Dis...

Page 38: ...sed by bringing in too much outdoor air to maintain IAQ set point When an override condition takes place IAQ control is disabled and Economizer Mini mum Position is set to the user configured value MD...

Page 39: ...rk Access None OVERRIDE DURATION The Override Duration point displays the number of minutes remaining for an occupancy override which is in effect If the override duration value down loaded is in hour...

Page 40: ...TIMED OVERRIDE IN EFFECT The Timed Override In Effect point shows if a timed override is currently in effect Timed Override in Effect Display Range No Yes Default Value No Network Access Read Only STA...

Page 41: ...omizer Submaster Reference Display Units Degrees F Degrees C Display Range 48 to 120 Default Value 120 Network Access Read Only ECONOMIZER SUBMASTER GAIN Displays the cur rent Submaster gain multiplie...

Page 42: ...play Units Degrees F Degrees C Display Range 0 0 to 99 9 Default Value 0 0 Network Access None The Occupancy Status point displays a 1 if occupancy is re ported by the Linkage Thermostat The Occupancy...

Page 43: ......

Page 44: ...inue or change at any time specifications or designs without notice and without incurring obligations PC 111 Catalog No 533 80072 Printed in U S A Form 38 54SI Pg 44 11 02 Replaces 38 52SI Book 1 4 Ta...

Reviews: