2

keeps the conditioned air from being affected by the outdoor
ambient temperature and provides improved indoor air quality.

(Conforms to American Society of Heating, Refrigeration and Air
Conditioning Engineers No. 62P.) The sloped drain pan minimizes

standing water in the drain. An external drain is provided.

Short--Cycling protection

for the compressor is incorporated into

our defrost control board ensuring a five minute delay (+/--2

minutes) before restarting compressor after shutdown for any
reason.

TABLE OF CONTENTS

FEATURES/BENEFITS

1--2

. . . . . . . . . . . . . . . . . . . . . . . . . . . . .

MODEL NUMBER NOMENCLATURE

2

. . . . . . . . . . . . . . . . .

ARI CAPACITIES

3

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

PHYSICAL DATA

4

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

OPTIONS AND ACCESSORIES

5

. . . . . . . . . . . . . . . . . . . . . . .

BASE UNIT DIMENSIONS

8--9

. . . . . . . . . . . . . . . . . . . . . . . . .

ACCESSORY DIMENSIONS

10

. . . . . . . . . . . . . . . . . . . . . . . . .

SELECTION PROCEDURE

11

. . . . . . . . . . . . . . . . . . . . . . . . . .

PERFORMANCE DATA

12--19

. . . . . . . . . . . . . . . . . . . . . . . . . .

TYPICAL PIPING AND WIRING

20

. . . . . . . . . . . . . . . . . . . . .

APPLICATION DATA

21

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

ELECTRICAL DATA

23--24

. . . . . . . . . . . . . . . . . . . . . . . . . . . .

TYPICAL WIRING SCHEMATICS

25--27

. . . . . . . . . . . . . . . . .

CONTROLS

28

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

GUIDE SPECIFICATIONS

29--30

. . . . . . . . . . . . . . . . . . . . . . . .

MODEL NUMBER NOMENCLATURE

50VT

--- ---

--- --- ---

1

Type of Unit

50VT --- Single Packaged

Heat Pump Unit

Nominal Cooling Capacity

024 --- 2.0 Tons

030 --- 2.5 Tons

036 --- 3.0 Tons

042 --- 3.5 Tons

048 --- 4.0 Tons

060 --- 5.0 Tons

024

N/A

Electrical Supply

3 --- 208/230--- 1--- 60

5 --- 208/230--- 3--- 60

6 --- 460--- 3--- 60

3

0

Series

Packaging

Options

AD --- Louvered Grille

BT --- AL evap, vinyl condenser

CC --- AL evap, CU condenser

CU --- CU evap & condenser

TP --- Base unit with tin plated indoor coil hairpins

TV --- TP with vinyl coating on outdoor coil

TC --- TP with AL indoor coil & CU/CU outdoor coil

See Price Page for full list of factory options.

Only used if ordering an option

LEGEND

AL --- Aluminum

CU --- Copper

N/A --- Not applicable

---

N/A

REGISTERED

ISO 9001:2000

As an Energy Star® Partner, Carrier 
Corporation has determined that this
product meets the ENERGY STAR® 
guidelines for energy efficiency.

50V

T

Summary of Contents for Performance 50VT

Page 1: ...static Expansion Valve A hard shutoff balance port TXV maintains a constant superheat at the evaporator exit cooling cycle resulting in higher overall system efficiency Refrigerant system is designed...

Page 2: ...AND WIRING 20 APPLICATION DATA 21 ELECTRICAL DATA 23 24 TYPICAL WIRING SCHEMATICS 25 27 CONTROLS 28 GUIDE SPECIFICATIONS 29 30 MODEL NUMBER NOMENCLATURE 50VT 1 Type of Unit 50VT Single Packaged Heat P...

Page 3: ...8 0 048 301 501 601 45500 3 3 23800 2 3 8 0 060 301 501 601 60000 3 5 33600 2 3 8 0 LEGEND dB Sound Levels decibels db Dry Bulb SEER Seasonal Energy Efficiency Ratio wb Wet Bulb COP Coefficient of Per...

Page 4: ...TCH psig Cutout Reset Auto 650 15 420 25 LOSS OF CHARGE LOW PRESSURE SWITCH Liquid Line psig Cutout Reset Auto 20 5 45 10 20 5 45 10 RETURN AIR FILTERS throwaway in mm 20x20x1 508x508x25 20x24x1 508x6...

Page 5: ...al heat in the unit when required Each package has a heater module that slides into the controls compartment Heater sizes range from 5 0 to 20 0 kW The electric heater design allows the use of a singl...

Page 6: ...0 HZ CPHEATER055A00 5 0 X X X X X CPHEATER056A00 10 0 X X X CPHEATER068A00 10 0 X X CPHEATER058A00 15 0 X X X X X CPHEATER059A01 20 0 X X X 460 THREE PHASE 60 HZ CPHEATER060A00 5 0 X X X X CPHEATER061...

Page 7: ...ISCHARGE REPLACEMENT PANEL HOLE FOR ECONOMIZER WIRING HARDNESS DOOR LATCH ANGLE HINGED FILTER ACCESS DOOR INSTALL FILTER ACCESS DOOR STICKER ALUMINUM FILTER RAINHOOD 11 13 32 17 13 32 16 1 4 EV APORAT...

Page 8: ...8 UNIT DIMENSIONS 50VT024 030 A08074 50VT...

Page 9: ...060 74 34 59 27 89 40 148 67 98 45 153 70 82 37 66 30 108 49 170 77 82 37 66 30 99 45 165 75 86 39 69 31 104 47 173 78 86 39 69 31 113 51 178 81 92 42 74 34 111 50 185 84 92 42 74 34 120 54 190 86 74...

Page 10: ...d retainer bracket must also be used A BTyp Supply opening B x C Long Support D 445 16 Return opening B X C Insulate d deck pan Short Support CTyp C00076 UNIT SIZE CATALOG NUMBER A IN MM B IN MM C IN...

Page 11: ...will provide a total capacity of 36 000 Btuh and a SHC of 27 400 Btuh Calculate SHC correction if required using Note 4 under Cooling Capacities tables 3 Select heating capacity of unit to provide de...

Page 12: ...18 58 1 93 21 38 17 30 2 16 19 34 15 99 2 40 17 19 14 61 2 66 72 29 85 16 75 1 55 27 72 15 64 1 73 25 55 14 52 1 94 23 35 13 40 2 16 22 34 12 76 2 13 18 67 11 09 2 66 At 75_F 23 9 _C entering dry bulb...

Page 13: ...5 27 32 22 64 2 69 25 06 21 88 2 95 22 58 20 93 3 22 72 36 33 19 07 2 03 34 30 18 58 2 24 32 12 18 01 2 46 29 81 17 37 2 70 27 30 16 63 2 96 24 52 15 74 3 23 At 75_F 23 9 _C entering dry bulb Tennesse...

Page 14: ...26 97 3 31 28 73 24 84 3 61 24 84 22 67 3 93 72 49 01 26 47 2 54 44 48 24 63 2 78 40 03 22 80 3 05 35 68 20 98 3 33 31 39 19 16 3 63 27 12 17 31 3 95 At 75_F 23 9 _C entering dry bulb Tennessee Valley...

Page 15: ...89 3 83 38 06 30 44 3 80 32 50 27 49 4 64 72 50 59 27 89 2 87 47 95 26 72 3 18 45 17 25 51 3 51 42 14 24 18 3 88 41 29 23 80 3 86 35 01 21 00 4 69 At 75_F 23 9 _C entering dry bulb Tennessee Valley A...

Page 16: ...40 4 33 37 39 32 12 4 80 32 61 29 67 5 31 72 60 91 32 02 3 17 55 86 30 17 3 53 50 80 28 29 3 92 45 76 26 38 4 36 40 65 24 40 4 83 35 38 22 30 5 34 At 75_F 23 9 _C entering dry bulb Tennessee Valley A...

Page 17: ...64 5 73 47 60 44 16 6 42 40 92 42 14 7 17 72 79 84 37 74 4 09 72 79 36 91 4 60 65 73 35 91 5 16 58 70 34 70 5 79 51 53 33 23 6 48 44 15 31 39 7 22 At 75_F 23 9 _C entering dry bulb Tennessee Valley A...

Page 18: ...capacity Btuh 1 10 x cfm t ldb t edb Wet bulb temperature corresponding to enthalpy air leaving evaporator coil h lwb t lwb total capacity Btuh 4 5 x cfm h lwb h ewb Where h ewb Enthalpy of air enter...

Page 19: ...F 26 6_C edb temperature of air entering evapo rator coil Below 805 F 26 6_C edb subtract corr factor x cfm from SHC Above 805 F 26 6_C edb add corr factor x cfm to SHC Correction Factor 1 10 x 1 BF...

Page 20: ...1449 1411 1362 1313 1278 1231 1188 High Black CFM 1705 1643 1607 1568 1518 1483 1448 1404 1360 50VT04230 50 60 Low Blue CFM 1295 1234 1182 1126 1075 1016 955 898 857 Med Low Pink CFM 1345 1282 1235 1...

Page 21: ...re duct covers Maximum cooling airflow To minimize the possibility of condensate blow off from the evaporator airflow through the units should not exceed 450 cfm per ton Minimum cooling airflow Minimu...

Page 22: ...LANCE POINT WORKSHEET 0 10 20 30 40 50 60 70 20 10 0 10 20 30 40 50 60 70 OUTDOOR TEMPERATURE F 0 0 2 9 5 9 8 8 11 7 14 6 17 6 20 5 024 0 030 0 036 0 042 0 048 0 060 0 BASED ON INDOOR ENT AIR AT 70 F...

Page 23: ...11 3 15 54 2 62 5 110 2 120 6 125 125 15 20 72 2 83 3 132 8 146 7 150 150 5 4 7 2 25 9 30 74 9 79 9 80 80 50VT 030 501 208 230 3 60 187 253 10 3 58 0 0 9 4 1 17 8 17 8 25 25 3 8 5 10 4 12 30 9 32 9 3...

Page 24: ...size from NEC 3 Unbalanced 3 Phase Supply Voltage Never operate a motor where a phase imbalance in supply volt age is greater than 2 Use the following formula to determine the percentage of voltage i...

Page 25: ...25 TYPICAL WIRING SCHEMATIC 208 230 1 60 A08024 50VT...

Page 26: ...26 TYPICAL WIRING SCHEMATIC 208 230 3 60 A08025 50VT...

Page 27: ...27 TYPICAL WIRING SCHEMATIC 460 3 60 A08026 50VT...

Page 28: ...stage thermostat If optional electric heat package is used a relay is energized bringing on first bank of supplemental electric heat When thermostat is satisfied contacts open deenergizing contactor a...

Page 29: ...l be made from steel and shall be double inlet type with forward curved blades with corrosion resistant finish Fan wheel shall be dynamically balanced 3 Outdoor fan shall be direct drive propeller typ...

Page 30: ...mbient temperature 8 Filter Rack Kit Shall provide filter mounting for downflow applications 9 Square To Round Duct Transitions 024 048 Shall have the ability to convert the supply and return open ing...

Reviews: