4
PHYSICAL DATA -- UNIT 50VT
UNIT SIZE
50VT024
50VT030
50VT036
50VT042
50VT048
50VT060
NOMINAL CAPACITY (ton)
2
2.5
3
3.5
4
5
OPERATING WEIGHT
}
(lb)
(kg)
306
139
316
143
371
168
412
187
432
196
462
210
COMPRESSOR QUANTITY
1
TYPE
SCROLL COMPRESSOR
REFRIGERANT
R---410A
Refrigerant (R---410A) Quantity (lb)
Quantity (kg)
9.5
4.3
10.5
4.8
9.0
4.1
14.0
6.4
17.0
7.7
16.0
7.3
METERING DEVICE ID
TXV
ORIFICE OD in. (Qty)
mm
0.032 (2)
.81
0.038 (2)
.97
0.040 (2)
1.02
0.038 (Left OD Coil)
0.040 (Right OD Coil)
.97/102
0.040 (2)
1.02
0.049 (2)
1.24
OUTDOOR COIL
Rows... Fins/in.
face area (sq. ft.)
2...21
13.6
2...21
15.4
2...21
13.6
2...21
19.4
2...21
19.4
2...21
23.3
OUTDOOR FAN
Nominal Airflow (CFM)
Diameter Motor HP (RPM)
2500
22
1/8 (825)
2600
22
1/8 (825)
3000
22
1/4 (1100)
3500
22
1/8 (825)
3500
22
1/4 (1100)
3800
22
1/3 (1100)
INDOOR COIL
Rows... Fins/in.
face area (sq. ft.)
3...17
3.7
3...17
3.7
3...17
4.7
3...17
4.7
3...17
5.7
4...17
5.7
INDOOR BLOWER
Nominal Cooling Airflow (CFM)
Size (in.)
(mm)
Motor (HP)
800
10x10
254x254
1/2
1000
10x10
254x254
1/2
1200
11x10
279x254
3/4
1400
11x10
279x254
3/4
1600
11x10
279x254
1.0
1750
11x10
279x254
1.0
HIGH---PRESSURE SWITCH (psig)
Cutout
Reset (Auto)
650
±
15
420
±
25
LOSS---OF---CHARGE/LOW---PRESSURE
SWITCH
(Liquid Line) (psig)
Cutout
Reset (Auto)
20
±
5
45
±
10
20
±
5
45
±
10
RETURN---AIR FILTERS*
{
throwaway (in.)
(mm)
20x20x1
508x508x25
20x24x1
508x610x25
24x30x1
610x762x25
24x36x1
610x914x25
*Required filter sizes shown are based on the larger of the ARI (Air conditioning and Refrigeration Institute) rated cooling airflow or the heating airflow velocity of
300 ft/minute for throwaway type or 450 ft/minute for high---capacity type. Air filter pressure drop for non---standard filters must not exceed 0.08 IN. W.C.
{
If using accessory filter rack refer to the filter rack installation instructions for correct filter size and quantity.
}
For 460 volt units, add 14 lb (6.4 kg) to the weight.
A--WEIGHTED SOUND POWER LEVEL (dBA)
MODEL 50VT
STANDARD
RATING
(dBA)
TYPICAL OCTAVE BAND SPECTRUM (dBA) (without tone adjustment)
125
250
500
1000
2000
4000
8000
024--- --- ---301
74
67.0
65.5
68.5
68.0
63.5
59.5
53.5
030--- --- ---301/501
72
61.5
62.5
66.0
66.0
63.0
57.5
50.5
036--- --- ---301/501/601
78
62.0
69.0
72.5
73.0
70.5
67.5
62.0
042--- --- ---301/501/601
75
62.5
62.5
68.5
70.0
67.0
62.0
58.5
048--- --- ---301/501/601
78
70.5
69.5
71.0
72.5
69.5
66.0
59.5
060--- --- ---301/501/601
79
69.0
69.0
71.5
74.0
72.0
67.5
59.5
NOTE: Tested in accordance with ARI Standard 270---95 (not listed in ARI).