background image

For any chimney or vent, this should include the following:

1. Inspection for any deterioration in chimney or vent. If dete-

rioration is discovered, chimney must be repaired or vent must
be replaced.

2. Inspection to ascertain that vent system is clear and free of

obstructions. Any blockage must be cleared before installing
furnace.

3. Cleaning chimney or vent if previously used for venting a

solid fuel burning appliance or fireplace.

4. Confirming that all unused chimney or vent connections are

properly sealed.

5. Verification that chimney is properly lined and sized per the

applicable codes. (Refer to list of codes in Safety Consider-
ations section.)

Step 2—Masonry Chimneys

This furnace can be vented into an existing masonry chimney. This
furnace must not be vented into a chimney servicing a solid fuel
burning appliance. Before venting furnace into a chimney, the
chimney MUST be checked for deterioration and repaired if
necessary. The chimney must be properly lined and sized per local
or national codes.

If furnace is vented into a common chimney, the chimney must be
of sufficient area to accommodate the total flue products of all
appliances vented into chimney.

The following requirements are provided for a safe venting
system:

1. Be sure chimney flue is clear of any dirt or debris.

2. Be sure chimney is not servicing an open fireplace.

3. Never reduce pipe size below outlet size of furnace. (See Fig.

2.)

4. All pipes should be supported using proper clamps and/or

straps. These supports should be at least every 4 ft.

5. All horizontal runs of pipe should have at least 1/4 in. per ft of

upward slope.

6. All pipe runs should be as short as possible with as few turns

as possible.

7. Seams should be tightly joined and checked for leaks.

8. The flue pipe must not extend into chimney but be flush with

inside wall.

9. The chimney must extend 3 ft above highest point where it

passes through the roof of a building and at least 2 ft higher
than any portion of a building within a horizontal distance of
10 ft. It shall also be extended at least 5 ft above highest
connected equipment flue collar.

10. Check local codes for any variance.

Step 3—Factory-Built Chimneys

Listed factory-built chimneys may be used. Refer to chimney
manufacturer’s instructions for proper installation.

OIL BURNER

This furnace is supplied with a high-pressure atomizing retention
head-type burner (for use with grade 1 or 2 fuel oil). The mounting
flange is fixed to burner air tube and no adjustment is required for
insertion length.

OIL CONNECTIONS

Complete instructions for installing fuel oil piping can be found in
oil burner Installation Instructions included with furnace.

Oil line entry holes are provided in side panels. Two holes are
provided in each location so that a 2-pipe system may be used if
desired.

An oil filter should be used with all oil burners and should be
installed as close to burner as possible.

BAROMETRIC DRAFT CONTROL

The barometric draft control shipped with furnace MUST be used
with furnace to ensure proper operation. Instructions for installing
control are packed with control.

ELECTRICAL CONNECTIONS

The unit cabinet must have an uninterrupted or unbroken
electrical ground to minimize personal injury if an electrical
fault should occur. A green ground screw is provided in
control box for this connection.

Step 1—115-v Wiring

Before proceeding with electrical connections, make certain that
voltage, frequency, and phase correspond to that specified on unit
rating plate. Also, check to be sure that service provided by utility
is sufficient to handle load imposed by this equipment. Refer to
rating plate or Table 2 for equipment electrical specifications.

Make all electrical connections in accordance with National
Electrical Code (NEC) ANSI/NFPA 70-1996 and any local codes
or ordinances that might apply. For Canadian installations, all
electrical connections must be made in accordance with Canadian
Electrical Code CSA C22.1 or subauthorities having jurisdiction.

Do not connect aluminum wire between disconnect switch
and furnace. Use only copper wire.

The control system depends on correct polarity of power supply.
Connect HOT wire (H) and NEUTRAL wire (N) as shown in Fig.
3 or Fig. 4.

A separate line voltage supply MUST be used with a fused
disconnect switch or circuit breaker between main power panel
and unit. (See Fig. 3 or Fig. 4.)

Metallic conduit (where required/used) may terminate at side panel
of unit. It is not necessary to extend conduit inside unit from side
panel to control box.

When replacing any original furnace wiring, use only 105°C No.
14 AWG copper wire.

Table 2—Electrical Data

UNIT

SIZE

VOLTS—
HERTZ—

PHASE

OPERATING

VOLTAGE RANGE

MAX

UNIT

AMPS

MIN

WIRE

GAGE

MAX WIRE

LENGTH (FT)†

MAX FUSE OR

CKT BKR AMPS‡

Maximum*

Minimum*

105-12

115—60—1

132

104

12.2

14

26

15

120-20

115—60—1

132

104

15.7

14

26

20

* Permissible limits of voltage range at which unit will operate satisfactorily.
† Length shown is as measured 1 way along wire path between unit and service panel for maximum 2% voltage drop.
‡ Time-delay fuse is recommended.

6

Summary of Contents for OIL FURNACE 58CMA

Page 1: ...ck 10 For Year Round Air Conditioning 10 Heating 10 Cooling 10 Constant Blower Switch 10 MAINTENANCE 11 12 General 11 Oil Burner 11 Heat Exchanger and Flue Pipe 11 Blower Removal 12 SAFETY CONSIDERATI...

Page 2: ...nd are available from either The National Fire Protection Agency Batterymarch Park Quincy MA 02269 or The Canadian Stan dards Association 178 Rexdale Blvd Rexdale Ontario M9W 1R3 Recognize safety info...

Page 3: ...oved subbase is used Also since flue pipe is in a down flow position Downflow Conversion Vent Guard Kit MUST be used Also read page 9 When installed in a horizontal position furnace may be suspended b...

Page 4: ...e into consideration the overall volume of unconfined space the number of windows and ventilation openings the number of doors to the outside internal doors which can close off unconfined space and ov...

Page 5: ...uctwork should be attached to either side bottom or side and bottom of furnace See Fig 2 for dimensions of these openings NOTE The back should not be cut out for return air The following recommendatio...

Page 6: ...ange is fixed to burner air tube and no adjustment is required for insertion length OIL CONNECTIONS Complete instructions for installing fuel oil piping can be found in oil burner Installation Instruc...

Page 7: ...H U M 4 5 6 N 7 2 S E A C C O N T C O O L H E A T CAPACITOR WHITE RED BLUE BLACK R99G001 ST9103 CONSTANT LOW SPEED SWITCH CIRCULATING FAN BLACK WHITE UNUSED LO ML MH HI C LEADS 1 2 3 3 H U M 4 5 6 N...

Page 8: ...4 5 6 N 7 2 S E A C C O N T C O O L H E A T CAPACITOR WHITE RED BLUE BLACK R99G001 ST9103 CONSTANT LOW SPEED SWITCH CIRCULATING FAN BLACK WHITE UNUSED LO ML MH HI C LEADS 1 2 3 3 H U M 4 5 6 N 7 2 S E...

Page 9: ...d set above room temperature If all of the above items have been performed set main electrical switch to ON position and burner should start When burner starts proceed to Combustion Check section Step...

Page 10: ...ed on rating plate Failure to follow this warning could lead to severe furnace damage Adjust fan speed ACCORDING TO OIL INPUT SELECTED so that temperature rise is within rise range specified on rating...

Page 11: ...FOR AN EXTENDED PERIOD OF TIME Step 2 Oil Burner For optimum performance oil burner nozzle should be replaced once a year Contact your service technician if you are unsure of this procedure The proce...

Page 12: ...luding Unit Familiarization Maintenance Installation Overview Operating Sequence A large selection of product theory and skills programs is available using popular video based formats and materials Al...

Reviews: