background image

AIR FOR COMBUSTION AND VENTILATION

Installation of this furnace in an area where it will receive
contaminated combustion air must be avoided. Such contami-
nation would include the following: ammonia, chlorine,
hydrogen sulfide, halogenated hydrocarbons, carbon tetra-
chloride, cleaning solvents, hydrochloric acid, water soften-
ing chemicals, and similar chemicals. Failure to follow this
warning will lead to premature rusting of heat exchanger and
possible premature furnace failure and/or vent failure which
could result in fire hazard and/or bodily harm.

Do not block combustion-air openings in the furnace. Any
blockage will result in improper combustion which may result
in a fire hazard and/or cause bodily harm.

Step 1—General

This furnace should be installed in a location in which facilities for
ventilation permit satisfactory combustion of oil, proper venting,
and maintenance of ambient temperature at safe limits under
normal conditions of use. The location should not interfere with
proper circulation of air within the confined space. (See NFPA-31,
Section 1.5.)

In addition to air needed for combustion, process air shall be
provided as required for: cooling of equipment or material,
controlling dew point, heating, drying, oxidation or dilution, safety
exhaust, and odor control.

In addition to air needed for combustion, air shall be supplied for
ventilation, including all air required for comfort and proper
working conditions for personnel.

The barometric draft regulator (included with furnace) shall be
installed in same room or enclosure as furnace in such a manner as
to prevent any difference in pressure between regulator and
combustion-air supply.

Air requirements for operation of exhaust fans, kitchen ventilation
systems, clothes dryers, and fireplaces shall be considered in
determining the adequacy of a space to provide combustion-air
requirements.

The lack of a proper amount of combustion air can lead to serious
furnace operational problems. Some of these problems are:

1. Excessive oil burner after-drip, and oil fumes.

2. Sooting.

3. Melted oil burner couplings and/or ignitor/relay control.

4. Air band or air shutter settings more open than normal.

5. Lockouts on start-up.

The requirements for combustion and ventilation air depend upon
whether furnace is located in a CONFINED or UNCONFINED
space.

Step 2—Unconfined Space

An unconfined space must have at least 50 cu ft for each 1000
Btuh of total input for all the appliances (such as furnaces, clothes
dryers, water heaters, etc.) in the space.

In unconfined spaces in buildings of conventional frame, brick, or
stone construction, infiltration MAY be adequate to provide air for
combustion, ventilation, and dilution of flue gases. This determi-
nation must be made on an individual installation basis and must
take into consideration the overall volume of unconfined space, the
number of windows and ventilation openings, the number of doors
to the outside, internal doors which can close off unconfined space,

and overall tightness of building construction. Consideration must
also be given to the amount of storage items (furniture, boxes, etc.)
within the unconfined space which take away from the air volume.

Many new buildings and homes (and older ones that have been
weatherized) MUST BE considered as being of tight construction,
therefore, infiltration will not be sufficient to supply necessary air
for combustion and ventilation.

A building can be considered as being of tight construction when:

1. Walls and ceilings exposed to outside atmosphere have a

continuous water vapor retarder with a rating of 1 perm or less
with openings gasketed or sealed, and/or

2. Weatherstripping has been added on operable windows and

doors, and/or

3. Caulking or sealants are applied to areas such as joints around

window and door frames; between sole plates and floors;
between wall-ceiling joints; between wall panels; at penetra-
tions for plumbing, electrical, and fuel lines; and at other
openings.

If combustion and ventilation air must be supplied to an uncon-
fined space from outside, an opening with a FREE AREA of not
less than 1 sq in. per 1000 Btuh of total input of all appliances
within unconfined space (but not less than 100 sq in.) must be
provided. This opening must be located such that it can not be
blocked at any time.

Step 3—Confined Space

A confined space has a volume of less than 50 cu ft per 1000 Btuh
of the total input rating for all appliances installed in that space.

When furnace is installed in a closet or enclosure, 2 ventilation
openings, with OPEN AREA as dimensioned in example below
are required for combustion air. The openings should be located
about 6 in. from top and bottom of enclosure at front of furnace.

NOTE:

In calculating free area, consideration shall be given to

blocking effect of louvers, grilles, or screens protecting openings.
Screens used shall not be smaller than 1/4 in. mesh and shall be
readily accessible for cleaning. If free area through a louver or
grille is known, it shall be used in calculating size and free area
specified. If free area is not known, it may be assumed that wood
louvers have 20 percent free area and metal louvers and grilles
have 60 percent free area. Louvers shall be fixed in open position
or interlocked with furnace so they open automatically at furnace
start-up and remain open during furnace operation.

The size of the openings depends upon whether the air comes from
outside of the structure or an unconfined space inside the structure.

For Example:

Minimum Floor Area for Unconfined Space

58CMA FURNACE

INPUT BTUH

MINIMUM SQ FT WITH

7-1/2 FT CEILING

70,000

467

91,000

607

105,000

700

119,000

793

140,000

933

154,000

1026

For Example:

58CMA FURNACE

INPUT BTUH

LENGTH

(IN.)

HEIGHT

(IN.)

70,000/105,000

16

8

119,000/154,000

20

10

4

Summary of Contents for OIL FURNACE 58CMA

Page 1: ...ck 10 For Year Round Air Conditioning 10 Heating 10 Cooling 10 Constant Blower Switch 10 MAINTENANCE 11 12 General 11 Oil Burner 11 Heat Exchanger and Flue Pipe 11 Blower Removal 12 SAFETY CONSIDERATI...

Page 2: ...nd are available from either The National Fire Protection Agency Batterymarch Park Quincy MA 02269 or The Canadian Stan dards Association 178 Rexdale Blvd Rexdale Ontario M9W 1R3 Recognize safety info...

Page 3: ...oved subbase is used Also since flue pipe is in a down flow position Downflow Conversion Vent Guard Kit MUST be used Also read page 9 When installed in a horizontal position furnace may be suspended b...

Page 4: ...e into consideration the overall volume of unconfined space the number of windows and ventilation openings the number of doors to the outside internal doors which can close off unconfined space and ov...

Page 5: ...uctwork should be attached to either side bottom or side and bottom of furnace See Fig 2 for dimensions of these openings NOTE The back should not be cut out for return air The following recommendatio...

Page 6: ...ange is fixed to burner air tube and no adjustment is required for insertion length OIL CONNECTIONS Complete instructions for installing fuel oil piping can be found in oil burner Installation Instruc...

Page 7: ...H U M 4 5 6 N 7 2 S E A C C O N T C O O L H E A T CAPACITOR WHITE RED BLUE BLACK R99G001 ST9103 CONSTANT LOW SPEED SWITCH CIRCULATING FAN BLACK WHITE UNUSED LO ML MH HI C LEADS 1 2 3 3 H U M 4 5 6 N...

Page 8: ...4 5 6 N 7 2 S E A C C O N T C O O L H E A T CAPACITOR WHITE RED BLUE BLACK R99G001 ST9103 CONSTANT LOW SPEED SWITCH CIRCULATING FAN BLACK WHITE UNUSED LO ML MH HI C LEADS 1 2 3 3 H U M 4 5 6 N 7 2 S E...

Page 9: ...d set above room temperature If all of the above items have been performed set main electrical switch to ON position and burner should start When burner starts proceed to Combustion Check section Step...

Page 10: ...ed on rating plate Failure to follow this warning could lead to severe furnace damage Adjust fan speed ACCORDING TO OIL INPUT SELECTED so that temperature rise is within rise range specified on rating...

Page 11: ...FOR AN EXTENDED PERIOD OF TIME Step 2 Oil Burner For optimum performance oil burner nozzle should be replaced once a year Contact your service technician if you are unsure of this procedure The proce...

Page 12: ...luding Unit Familiarization Maintenance Installation Overview Operating Sequence A large selection of product theory and skills programs is available using popular video based formats and materials Al...

Reviews: