Carrier OIL FURNACE 58CMA Install And Operation Instructions Download Page 5

ALL AIR FROM INSIDE THE STRUCTURE

For a confined space, where air is taken from an interior space, 2
permanent openings of equal area are required. One opening must
be within 12 in. of ceiling and the other within 12 in. of floor. Each
opening must have a free area of at least 1 sq in. per 1000 Btuh of
total input rating but not less than 100 sq in.

ALL AIR FROM OUTSIDE OF STRUCTURE

If outside air is supplied to a confined space, then the 2 openings
must be equal and located as above.

1. If combustion air is taken through a permanent opening

directly communicating with the outdoors, the opening shall
have a minimum free area of 1 sq in. per 4000 Btuh of total
input rating for all equipment in the enclosure.

2. If combustion air is taken from outdoors through vertical

ducts, the openings and ducts MUST have at least 1 sq in. of
free area per 4000 Btuh of the total input for all equipment
within the confined space.

3. If combustion air is taken from outdoors through horizontal

ducts, the openings and ducts MUST have at least 1 sq in. of
free area per 2000 Btuh of the total input for all equipment
within the confined space.

When ducts are used to supply air, they must be of the same cross
sectional area as free area of openings to which they connect.

The minimum dimension of rectangular air ducts must not be less
than 3 in.

DUCTWORK RECOMMENDATIONS

When supply ducts carry air circulated by furnace to areas
outside spaces containing furnace, return air MUST also be
handled by a duct sealed to furnace casing and terminating
outside space containing furnace. Incorrect ductwork termi-
nation and sealing will create a hazardous condition which
could lead to bodily harm.

Return-air grilles and warm air registers MUST NOT be
obstructed.

The proper sizing of warm air ducts is necessary to ensure
satisfactory furnace operation. Ductwork should be in accordance
with the latest editions of NFPA-90A (Installation of Air Condi-
tioning and Ventilating Systems) and NFPA-90B (Warm Air
Heating and Air Conditioning Systems) or Canadian equivalent.

The supply ductwork should be attached to flanged front opening
provided at discharge end of furnace. The return-air ductwork
should be attached to either side, bottom, or side and bottom of
furnace. See Fig. 2 for dimensions of these openings.

NOTE:

The back should not be cut out for return air.

The following recommendations should be followed when install-
ing ductwork:

1. Install locking-type dampers in all branches of individual

ducts to balance out system. Dampers should be adjusted to
impose proper static at outlet of furnace.

2. A flexible duct connector of noncombustible material should

be installed at unit on both supply- and return-air systems. In
applications where extremely quiet operation is necessary, the
first 10 ft (if possible) of supply and return ducts should be
internally lined with acoustical material.

3. In cases where return-air grille is located close to fan inlet,

there should be at least one 90° air turn between fan inlet and
grille. Further reduction in sound level can be accomplished
by installing acoustical air turning vanes or lining duct as
described in item 2 above.

4. When a single air grille is used, duct between grille and

furnace must be the same size as return opening in furnace.

VENTING

Venting of furnace should be to the outside and in accordance with
local codes or requirements of local utility.

OIL-FIRED APPLIANCES SHALL BE CONNECTED TO
FLUES HAVING SUFFICIENT DRAFT AT ALL TIMES TO
ENSURE SAFE AND PROPER OPERATION OF APPLIANCE.

For additional venting information, refer to ANSI/NFPA 211
Chimney, Fireplaces, Vents, and Solid Fuel Burning Appliances
and/or CSA B139 Installation Code.

This furnace is certified for use with Type "L" vent (maximum flue
gas temperature 575°F).

Step 1—Vent System Inspection

Before furnace is installed, it is highly recommended that any
existing vent system be completely inspected.

For Example:

Combustion Air From Unconfined Space

58CMA FURNACE

INPUT BTUH

FREE AREA PER

OPENING

(SQ IN.)

70,000

100

91,000

100

105,000

105

119,000

119

140,000

140

154,000

154

For Example:

Combustion Air From Outdoors Through

Vertical Ducts

58CMA FURNACE

INPUT BTUH

FREE AREA PER

OPENING

(SQ IN.)

ROUND PIPE

(IN. DIA)

70,000

17.5

5

91,000

22.8

6

105,000

26.3

6

119,000

29.8

6

140,000

35.0

6

154,000

38.5

6

For Example:

Combustion Air From Outdoors Through

Horizontal Ducts

58CMA FURNACE

INPUT BTUH

FREE AREA PER OPENING

(SQ IN.)

ROUND PIPE

(IN. DIA)

70,000

35.0

7

91,000

45.5

8

105,000

52.5

9

119,000

59.5

9

140,000

70.0

10

154,000

77.0

10

5

Summary of Contents for OIL FURNACE 58CMA

Page 1: ...ck 10 For Year Round Air Conditioning 10 Heating 10 Cooling 10 Constant Blower Switch 10 MAINTENANCE 11 12 General 11 Oil Burner 11 Heat Exchanger and Flue Pipe 11 Blower Removal 12 SAFETY CONSIDERATI...

Page 2: ...nd are available from either The National Fire Protection Agency Batterymarch Park Quincy MA 02269 or The Canadian Stan dards Association 178 Rexdale Blvd Rexdale Ontario M9W 1R3 Recognize safety info...

Page 3: ...oved subbase is used Also since flue pipe is in a down flow position Downflow Conversion Vent Guard Kit MUST be used Also read page 9 When installed in a horizontal position furnace may be suspended b...

Page 4: ...e into consideration the overall volume of unconfined space the number of windows and ventilation openings the number of doors to the outside internal doors which can close off unconfined space and ov...

Page 5: ...uctwork should be attached to either side bottom or side and bottom of furnace See Fig 2 for dimensions of these openings NOTE The back should not be cut out for return air The following recommendatio...

Page 6: ...ange is fixed to burner air tube and no adjustment is required for insertion length OIL CONNECTIONS Complete instructions for installing fuel oil piping can be found in oil burner Installation Instruc...

Page 7: ...H U M 4 5 6 N 7 2 S E A C C O N T C O O L H E A T CAPACITOR WHITE RED BLUE BLACK R99G001 ST9103 CONSTANT LOW SPEED SWITCH CIRCULATING FAN BLACK WHITE UNUSED LO ML MH HI C LEADS 1 2 3 3 H U M 4 5 6 N...

Page 8: ...4 5 6 N 7 2 S E A C C O N T C O O L H E A T CAPACITOR WHITE RED BLUE BLACK R99G001 ST9103 CONSTANT LOW SPEED SWITCH CIRCULATING FAN BLACK WHITE UNUSED LO ML MH HI C LEADS 1 2 3 3 H U M 4 5 6 N 7 2 S E...

Page 9: ...d set above room temperature If all of the above items have been performed set main electrical switch to ON position and burner should start When burner starts proceed to Combustion Check section Step...

Page 10: ...ed on rating plate Failure to follow this warning could lead to severe furnace damage Adjust fan speed ACCORDING TO OIL INPUT SELECTED so that temperature rise is within rise range specified on rating...

Page 11: ...FOR AN EXTENDED PERIOD OF TIME Step 2 Oil Burner For optimum performance oil burner nozzle should be replaced once a year Contact your service technician if you are unsure of this procedure The proce...

Page 12: ...luding Unit Familiarization Maintenance Installation Overview Operating Sequence A large selection of product theory and skills programs is available using popular video based formats and materials Al...

Reviews: