– 3 –

3

Selection of installation place

WARNING

Install the air conditioner securely in a location where the base can sustain the weight adequately.

If the strength is not enough, the unit may fall down resulting in injury.

Install the air conditioner at a height 8’ (2.4 m) or more from the floor.

If you insert your hands or others directly into the unit while the air conditioner operates, it is dangerous because you 
may contact with revolving fan or active electricity.

CAUTION

Do not install in a location where flammable gas may leaks are possible.

If the gas leak and accumulate around the unit, it may ignite and cause a fire.

Upon approval of the customer, install the air conditioner in a place that satisfies the following 

conditions.

• Place where the unit can be installed horizontally.
• Place where a sufficient servicing space can be ensured for safety maintenance and check.
• Place where drained water will not cause any problem.

Avoid installing in the following places.

• Place exposed to air with high salt content (seaside area), or place exposed to large quantities of sulfide gas (hot 

spring). 
(Should the unit be used in these places, special protective measures are needed.)

• A restaurant kitchen where a lot of oil is used or place near machines in a factory (Oil adhering to the heat 

exchanger and resin part (turbo fan) in the indoor unit may reduce the performance, generate mist or dew drop, 
or deform or damage resin parts.)

• Places where iron or other metal dust is present. If iron or other metal dust adheres to or collects on the interior 

of the air conditioner, it may spontaneously combust and start a fire.

• Place where organic solvent is used nearby.
• Place close to a machine generating high frequency.
• Place where the discharged air blows directly into the window of the neighbor house. (Outdoor unit)
• Place where noise of the outdoor unit is easily transmitted.

(When the outdoor unit is installed on the boundary with the neighbor, pay due attention to the level of noise.)

• Place with poor ventilation. (Before air duct work, check whether value of fan speed, static pressure and duct 

resistance are correct.)

• Do not use the air conditioner for special purposes such as preserving food, precision instruments, or art objects, 

or where breeding animals or growing plants are kept. (This may degrade the quality of preserved materials.)

• Place where any of high-frequency appliances (including inverter devices, private power generators, medical 

equipment, and communication equipment) and inverter-type fluorescent light is installed. 
(A malfunction of the air conditioner, abnormal control, or problems due to noise to such appliances/equipment 
may occur.)

• When the wireless remote control is used in a room equipped with an inverter-type fluorescent light or at a place 

exposed to direct sunlight, signals from the remote control may not be received correctly.

• Place where organic solvent is used.
• Place near a door or window exposed to humid outside air (Dew drop may form.).
• Place where special spray is used frequently.

Installation space

Secure the specified space in the figure for installation and servicing.

unit: in (mm)

Selection of installation place

Continual operation of the indoor unit under high-humidity conditions as described below, dew may condense and 
water may drop.
Especially, high-humidity atmosphere (dew point temperature: 73.4 °F (23 °C) or more) may generate dew inside 
the ceiling.
1. Unit is installed inside the ceiling with slated roof.
2. Unit is installed at a location using inside of the ceiling as fresh air take-in path.
3. Kitchen

Advice

• Set a service check opening panel at right side of the unit (size: 17.7" × 17.7" (450 × 450 mm) or more) for piping, 

maintenance, and servicing.

• If installing a unit at such place, put insulating material (glass wool, etc.) additionally on all the positions of the 

indoor unit which come to contact with high-humidity atmosphere.

REQUIREMENT

When the humidity inside the ceiling seems to be higher than 80%, attach a heat insulator to the side (top) 
surface of the indoor unit. (Use a heat insulator that is 0.4" (10 mm) or more thick.)

Model MMU-

A in (mm)

AP007 to AP030 Type

10.7” (271) or more

AP036, AP042 Type

13.1” (334) or more

A

Obstacle

39.4” (1000) or more

39.4”

 (

1000) 

or

 m

ore

0.6

” (15)

 

or mo

re

7.9” (200)

7.9”

 (

200)

Check port

17.7” x 17.7”

(450 x 450)

Check port

17.7” x 17.7”

(450 x 450)

Check port must be located on the Fresh 

air intake box side, if it is installed.

5-EN

6-EN

+00EH99876001-3.book  Page 3  Wednesday, May 27, 2015  10:08 AM

Summary of Contents for MMU-AP0072H2UL

Page 1: ...UL MMU AP0182H2UL MMU AP0212H2UL MMU AP0242H2UL MMU AP0302H2UL MMU AP0362H2UL MMU AP0422H2UL AIR CONDITIONER MULTI TYPE Installation Manual For commercial use Pour usage commercial Installation Manual 1 English Manuel d installation 19 Français 00EH99876001 3 book Page 1 Wednesday May 27 2015 10 08 AM ...

Page 2: ...y For the installation of these products follow the Installation Manuals supplied with them The wireless type remote control is designed to be installed by attaching a wireless remote control kit sold separately to the standard panel The wireless remote control kit consists of a wireless remote control and adjust corner caps with a signal receiving unit Part name Qty Shape Usage Installation Manua...

Page 3: ...is mixed in the refrigerant the gas pressure in the refrigeration cycle becomes abnormally high and it resultingly causes pipe burst and injuries on persons Perform installation work properly according to the Installation Manual Inappropriate installation may result in water leakage electric shock or fire When the air conditioner is installed in a small room provide appropriate measures to ensure ...

Page 4: ...e the air conditioner for special purposes such as preserving food precision instruments or art objects or where breeding animals or growing plants are kept This may degrade the quality of preserved materials Place where any of high frequency appliances including inverter devices private power generators medical equipment and communication equipment and inverter type fluorescent light is installed...

Page 5: ...ng can be raised Refer to 8 Applicable controls in this manual for the setting procedure Discharge direction As shown in the figure below air discharge directions can be selected according to the shape of the room and the location of the indoor unit installation Model MMU Possible installed ceiling height AP007 to AP030 Type Up to 12 6 3 8 m AP036 AP042 Type Up to 15 1 4 6 m Model MMU AP007 AP009 ...

Page 6: ... of the indoor unit installation and orientation After the location of the indoor unit installation has been determined open the ceiling and install hanging bolts The dimensions of the ceiling opening and hanging bolt pitches are given in the outline drawing and the attached installation pattern When a ceiling already exists lay the drain pipe refrigerant pipe control wires and remote control wire...

Page 7: ...use water leakage Hanging bolt Level Hanging bracket Washer Accessory To prevent the bolt from falling off for safety be sure to set it just under the hanging bracket as shown in the figure Eccentric washer Accessory Nut 3 8 M10 Hanging bolt 3 8 M10 Nut 3 8 M10 Procure hanging bolts and nuts locally Install with the marking UP facing up Indoor unit Level vial levelness 0 2 5 mm or less Hanging bol...

Page 8: ...ocally procured to the hard socket of the attached supplied flexible hose Connect a drain pipe locally procured to the connected hard socket REQUIREMENT Connect hard vinyl chloride pipes securely using an adhesive for vinyl chloride to avoid water leakage It takes some time until the adhesive is dried and hardened refer to the manual of the adhesive Do not apply stress to the joint with the drain ...

Page 9: ... 2 Flare nut and flare works are also different from those of the conventional refrigerant Take out the flare nut attached to the main unit of the air conditioner and use it REQUIREMENT When the refrigerant pipe is long provide support brackets at intervals of 8 2 9 10 2 5 3 m to clamp the refrigerant pipe Otherwise abnormal sound may be generated CAUTION IMPORTANT 4 POINTS FOR PIPING WORK 1 Remov...

Page 10: ... be faced upward ceiling side Banding band Locally procured 7 Electrical connection WARNING 1 Use predefined wire and connect them certainly Keep the connecting terminal free from external force Improper wire connection or clamping may result in exothermic fire or malfunction 2 Connect ground wire grounding work Incomplete grounding cause an electric shock Do not connect ground wires to gas pipes ...

Page 11: ... control wiring remote control inter unit wiring Wire size AWG20 Total wire length of remote control wiring and remote control inter unit wiring L L1 L2 Ln In case of wired type only Up to 1640 5 500 m In case of wireless type included Up to 1312 4 400 m Total wire length of remote control inter unit wiring L1 L2 Ln Up to 656 2 200 m L1 L L2 Ln Indoor unit Remote control inter unit wiring Indoor u...

Page 12: ...ck Conduit connection hole Piping Knockout Bushing of control and remote control wires Lock nut Conduit pipe Conduit plate Remote control terminal block Cord clamp Side D Space 0 33 8 5 mm Side C Space 0 16 4 mm Insert the wire to Side C Ground screw Ground screw for shielded wire control wire Power supply wires and ground wire 1 Strip the wire ends Power supply wire 0 4 10 mm Ground wire 0 8 20 m...

Page 13: ...nit runs and the louvers start swinging The indoor unit can be confirmed for which to change settings 1 6 1 3 2 5 4 Display content varies with the indoor unit model Procedure 3 Specify CODE No with temp setup buttons Procedure 4 Select SET DATA with timer time buttons Procedure 5 Push button When the display changes from flashing to lit the setup is completed To change settings of another indoor ...

Page 14: ...ion is selected ceiling contamination is less reduced SET DATA Filter sign lighting time 0000 None 0001 150 H 0002 2500 H Factory default 0003 5000 H 0004 10000 H SET DATA Detection temp shift value 0000 No shift 0001 1 8 F 1 C 0002 3 6 F 2 C Factory default 0003 5 4 F 3 C 0004 7 2 F 4 C 0005 9 0 F 5 C 0006 10 8 F 6 C SET DATA Louver direction setting 0000 Smudge reducing position Air direction to...

Page 15: ...er indoor unit Non polarity For address setup refer to the Installation Manual attached to the outdoor unit UNIT No 1 1 UNIT No 1 2 UNIT No 1 3 UNIT No 1 4 1 0001 2 0002 3 0003 5 0005 4 0004 SET DATA 0001 0005 SET DATA SET DATA 0000 0001 Remote control sensor Not used factory default Used 0000 SET DATA 9 Test run Before test run Before turning on the circuit breaker carry out the following procedu...

Page 16: ...test run After confirming a signal receiving sound beep immediately set the temperature to 64 F 18 C with the temp setup buttons After confirming a signal receiving sound beep immediately set the temperature to 86 F 30 C with the temp setup buttons 3 4 5 6 2 7 2 2 Always select HIGH fan speed 10Troubleshooting Confirmation and check When an error occurred in the air conditioner the check code and ...

Page 17: ...I F E16 E16 00 Capacity over 01 No of connected units Capacity over No of connected indoor units I F E18 Communication error between indoor units Indoor E19 E19 00 Header is nothing 02 Two or more header units Outdoor header units quantity error I F E20 E20 01 Outdoor of other line connected 02 Indoor of other line connected Other line connected during automatic address I F E23 E23 Sending error i...

Page 18: ...red remote control display Outdoor 7 segment display Sensor block display of receiving unit Auxiliary code Operation Timer Ready Flash A3 IPDU Fan IPDU 1 2 3 01 02 03 04 05 06 07 08 09 0A 0B 0C 0D 0E 0F IPDU error Error detected by TCC LINK central control device TCC LINK TOSHIBA Carrier Communication Link P18 P18 ALT Discharge temp TD3 error I F P19 P19 Detected outdoor unit number ALT 4 way valv...

Page 19: ...EH99876001 3 00EH99876001 3 book Page 39 Wednesday May 27 2015 10 08 AM ...

Reviews: