Carrier MMU-AP0072H2UL Installation Manual Download Page 10

– 9 –

Tightening connection

CAUTION

• Do not apply excessive torque. Otherwise, the nut 

may crack depending on the conditions.

Tightening torque of flare pipe connections

Pressure of R410A is higher than that of R22.
(Approx. 1.6 times) Use a torque wrench, tighten the 
flare pipe connecting sections which connect the 
indoor and outdoor units of the specified tightening 
torque.
Incorrect connections may cause not only a gas leak, 
but also a trouble of the refrigeration cycle.
Align the centers of the connecting pipes and tighten 
the flare nut as far as possible with your fingers. Then 
tighten the nut with a spanner and torque wrench as 
shown in the figure.

REQUIREMENT

Tightening with an excessive torque may crack the nut 
depending on installation conditions.
Tighten the nut within the specified tightening torque.

Piping with outdoor unit

• Shape of valve differs according to the outdoor unit.

For details of installation, refer to the Installation 
Manual of the outdoor unit.

Leak check test, evacuation 
and other procedure

For leak check test, evacuation, addition of refrigerant, 
and gas leak check, refer to the Installation Manual 
attached to the outdoor unit.

REQUIREMENT

Do not supply power to the indoor unit until the leak 
check test and evacuation are completed. (If the indoor 
unit is powered on, the pulse motor valve is fully closed, 
which extends the time for vacuuming.)

Open the valve fully

Open the valve of the outdoor unit fully.
For details, refer to the Installation Manual attached to 
the outdoor unit.

Heat insulation process

Apply heat insulation for the pipes separately at liquid 
side and gas side.
For the heat insulation to the pipes at gas side, use the 
material with heat-resisting temperature 248 °F (120 
°C) or higher.
Apply the attached heat insulation to the pipe 
connecting section of the indoor unit securely without 
gap.

REQUIREMENT

• Apply the heat insulation to the pipe connecting 

section of the indoor unit securely up to the root 
without exposure of the pipe. (The pipe exposed to the 
outside may causes water leak.)

• Wrap heat insulator with its slits facing up (ceiling 

side).

Unit: ft•lbs (N•m)

Outer dia. of copper pipe

Tightening torque

1/4" (6.4 mm)

10 - 13 (14 - 18)

3/8" (9.5 mm)

24 - 31 (33 - 42)

1/2" (12.7 mm)

37 - 46 (50 - 62)

5/8" (15.9 mm)

46 - 57 (63 - 77)

Work using double spanner

Indoor unit

Union

Heat insulation 

pipe 

(Accessory)

Flare nut

Heat insulator 

of the pipe

Wrap the pipe with the attached heat insulator 

without any gap between the indoor unit.

The seam must be faced upward 

(ceiling side).

Banding band 

(Locally 

procured)

7

Electrical connection

WARNING

1.

Use predefined wire and connect them certainly. 
Keep the connecting terminal free from external 
force.

Improper wire connection or clamping may result in 
exothermic, fire or malfunction.

2.

Connect ground wire. (grounding work)

Incomplete grounding cause an electric shock.
Do not connect ground wires to gas pipes, water 
pipes, lightning rods or ground wires for telephone 
wires.

3.

Install appliance in accordance with national 
wiring regulations.

Capacity shortage of circuit breaker or incomplete 
installation may cause an electric shock or a fire.

CAUTION

• Consult local building codes, NEC (National Electrical 

Code) or CEC (Canadian Electrical Code) for special 
requirements.

• If incorrect/incomplete wiring is carried out, it will 

cause an electrical fire or smoke.

• Install circuit breaker is not tripped by shock waves.

If circuit breaker is not installed, an electric shock may 
be caused.

• Use the cord clamps attached to the product.
• Do not damage or scratch the conductive core and 

inner insulator of power and control wires when 
peeling them.

• Use the power cord and control wire of specified 

thickness, type, and protective devices required.

• Do not connect 208/230 V power to the terminal 

blocks (U1, U2, A, B etc.) for control wiring.
(Otherwise, the system will fail.)

• Perform the electric wiring so that it does not come to 

contact with the high-temperature part of the pipe.
The coating may melt resulting in an accident.

• Do not turn on the circuit breaker of the indoor unit 

until vacuuming of the refrigerant pipes completes.

REQUIREMENT

• For power supply wiring, strictly conform to the Local 

Regulation in each country.

• Run the refrigerant piping line and control wiring line in 

the same line.

Power supply wire and 
control wires specifications

Power supply wire and interconnecting wires are 
procured locally.
For the power supply specifications, follow to the table 
below. If capacity is little, it is dangerous because 
overheat or seizure may be caused.

Indoor unit power supply

• For the power supply of the indoor unit, prepare the 

exclusive power supply separated from that of the 
outdoor unit.

Power supply

Control wiring, Central control wiring

• 2-core with non-polarity wires are used for the 

control wiring between indoor unit and outdoor unit 
and Central control wiring.

• To prevent noise trouble, use 2-core shielded wire.
• The length of the communication line means the total 

length of the control wire length between indoor and 
outdoor units added with the central control wire 
length.

Power supply

208/230-1-60

17-EN

18-EN

+00EH99876001-3.book  Page 9  Wednesday, May 27, 2015  10:08 AM

Summary of Contents for MMU-AP0072H2UL

Page 1: ...UL MMU AP0182H2UL MMU AP0212H2UL MMU AP0242H2UL MMU AP0302H2UL MMU AP0362H2UL MMU AP0422H2UL AIR CONDITIONER MULTI TYPE Installation Manual For commercial use Pour usage commercial Installation Manual 1 English Manuel d installation 19 Français 00EH99876001 3 book Page 1 Wednesday May 27 2015 10 08 AM ...

Page 2: ...y For the installation of these products follow the Installation Manuals supplied with them The wireless type remote control is designed to be installed by attaching a wireless remote control kit sold separately to the standard panel The wireless remote control kit consists of a wireless remote control and adjust corner caps with a signal receiving unit Part name Qty Shape Usage Installation Manua...

Page 3: ...is mixed in the refrigerant the gas pressure in the refrigeration cycle becomes abnormally high and it resultingly causes pipe burst and injuries on persons Perform installation work properly according to the Installation Manual Inappropriate installation may result in water leakage electric shock or fire When the air conditioner is installed in a small room provide appropriate measures to ensure ...

Page 4: ...e the air conditioner for special purposes such as preserving food precision instruments or art objects or where breeding animals or growing plants are kept This may degrade the quality of preserved materials Place where any of high frequency appliances including inverter devices private power generators medical equipment and communication equipment and inverter type fluorescent light is installed...

Page 5: ...ng can be raised Refer to 8 Applicable controls in this manual for the setting procedure Discharge direction As shown in the figure below air discharge directions can be selected according to the shape of the room and the location of the indoor unit installation Model MMU Possible installed ceiling height AP007 to AP030 Type Up to 12 6 3 8 m AP036 AP042 Type Up to 15 1 4 6 m Model MMU AP007 AP009 ...

Page 6: ... of the indoor unit installation and orientation After the location of the indoor unit installation has been determined open the ceiling and install hanging bolts The dimensions of the ceiling opening and hanging bolt pitches are given in the outline drawing and the attached installation pattern When a ceiling already exists lay the drain pipe refrigerant pipe control wires and remote control wire...

Page 7: ...use water leakage Hanging bolt Level Hanging bracket Washer Accessory To prevent the bolt from falling off for safety be sure to set it just under the hanging bracket as shown in the figure Eccentric washer Accessory Nut 3 8 M10 Hanging bolt 3 8 M10 Nut 3 8 M10 Procure hanging bolts and nuts locally Install with the marking UP facing up Indoor unit Level vial levelness 0 2 5 mm or less Hanging bol...

Page 8: ...ocally procured to the hard socket of the attached supplied flexible hose Connect a drain pipe locally procured to the connected hard socket REQUIREMENT Connect hard vinyl chloride pipes securely using an adhesive for vinyl chloride to avoid water leakage It takes some time until the adhesive is dried and hardened refer to the manual of the adhesive Do not apply stress to the joint with the drain ...

Page 9: ... 2 Flare nut and flare works are also different from those of the conventional refrigerant Take out the flare nut attached to the main unit of the air conditioner and use it REQUIREMENT When the refrigerant pipe is long provide support brackets at intervals of 8 2 9 10 2 5 3 m to clamp the refrigerant pipe Otherwise abnormal sound may be generated CAUTION IMPORTANT 4 POINTS FOR PIPING WORK 1 Remov...

Page 10: ... be faced upward ceiling side Banding band Locally procured 7 Electrical connection WARNING 1 Use predefined wire and connect them certainly Keep the connecting terminal free from external force Improper wire connection or clamping may result in exothermic fire or malfunction 2 Connect ground wire grounding work Incomplete grounding cause an electric shock Do not connect ground wires to gas pipes ...

Page 11: ... control wiring remote control inter unit wiring Wire size AWG20 Total wire length of remote control wiring and remote control inter unit wiring L L1 L2 Ln In case of wired type only Up to 1640 5 500 m In case of wireless type included Up to 1312 4 400 m Total wire length of remote control inter unit wiring L1 L2 Ln Up to 656 2 200 m L1 L L2 Ln Indoor unit Remote control inter unit wiring Indoor u...

Page 12: ...ck Conduit connection hole Piping Knockout Bushing of control and remote control wires Lock nut Conduit pipe Conduit plate Remote control terminal block Cord clamp Side D Space 0 33 8 5 mm Side C Space 0 16 4 mm Insert the wire to Side C Ground screw Ground screw for shielded wire control wire Power supply wires and ground wire 1 Strip the wire ends Power supply wire 0 4 10 mm Ground wire 0 8 20 m...

Page 13: ...nit runs and the louvers start swinging The indoor unit can be confirmed for which to change settings 1 6 1 3 2 5 4 Display content varies with the indoor unit model Procedure 3 Specify CODE No with temp setup buttons Procedure 4 Select SET DATA with timer time buttons Procedure 5 Push button When the display changes from flashing to lit the setup is completed To change settings of another indoor ...

Page 14: ...ion is selected ceiling contamination is less reduced SET DATA Filter sign lighting time 0000 None 0001 150 H 0002 2500 H Factory default 0003 5000 H 0004 10000 H SET DATA Detection temp shift value 0000 No shift 0001 1 8 F 1 C 0002 3 6 F 2 C Factory default 0003 5 4 F 3 C 0004 7 2 F 4 C 0005 9 0 F 5 C 0006 10 8 F 6 C SET DATA Louver direction setting 0000 Smudge reducing position Air direction to...

Page 15: ...er indoor unit Non polarity For address setup refer to the Installation Manual attached to the outdoor unit UNIT No 1 1 UNIT No 1 2 UNIT No 1 3 UNIT No 1 4 1 0001 2 0002 3 0003 5 0005 4 0004 SET DATA 0001 0005 SET DATA SET DATA 0000 0001 Remote control sensor Not used factory default Used 0000 SET DATA 9 Test run Before test run Before turning on the circuit breaker carry out the following procedu...

Page 16: ...test run After confirming a signal receiving sound beep immediately set the temperature to 64 F 18 C with the temp setup buttons After confirming a signal receiving sound beep immediately set the temperature to 86 F 30 C with the temp setup buttons 3 4 5 6 2 7 2 2 Always select HIGH fan speed 10Troubleshooting Confirmation and check When an error occurred in the air conditioner the check code and ...

Page 17: ...I F E16 E16 00 Capacity over 01 No of connected units Capacity over No of connected indoor units I F E18 Communication error between indoor units Indoor E19 E19 00 Header is nothing 02 Two or more header units Outdoor header units quantity error I F E20 E20 01 Outdoor of other line connected 02 Indoor of other line connected Other line connected during automatic address I F E23 E23 Sending error i...

Page 18: ...red remote control display Outdoor 7 segment display Sensor block display of receiving unit Auxiliary code Operation Timer Ready Flash A3 IPDU Fan IPDU 1 2 3 01 02 03 04 05 06 07 08 09 0A 0B 0C 0D 0E 0F IPDU error Error detected by TCC LINK central control device TCC LINK TOSHIBA Carrier Communication Link P18 P18 ALT Discharge temp TD3 error I F P19 P19 Detected outdoor unit number ALT 4 way valv...

Page 19: ...EH99876001 3 00EH99876001 3 book Page 39 Wednesday May 27 2015 10 08 AM ...

Reviews: