Carrier MMU-AP0072H2UL Installation Manual Download Page 16

– 15 –

Wireless remote control

Procedure 

1

Turn on the power of the air conditioner.
When power is turned on for the first time after 
installation, it takes approx. 5 minutes until the remote 
control becomes available. In the case of subsequent 
power-on, it takes approx. 1 minute until the remote 
control becomes available. Execute a test run after the 
predetermined time has passed.

Procedure 

2

Push “ON/OFF” button on the remote control, select 
[COOL] or [HEAT] with “MODE” button, and then select 
[HIGH] with “FAN” button.

Procedure 

3

Procedure 

4

Procedure 

5

Procedure 

6

Repeat procedures 

4

 

 

5

 

 

4

 

 

5

.

Indicators “Operation” (green), “Timer” (green), and 
“Ready” (orange) in the wireless receiver section flash 
in approx. 10 seconds, and the air conditioner starts 
operation. If any of these indicators does not flash, 
repeat procedures 

2

 to 

5

.

Procedure 

7

Upon completion of the test run, push “ON/OFF” button 
to stop operation.

<Overview of test run operations using the 

wireless remote control>

Cooling test run: 

ON/OFF 

 64 °F (18 °C) 

 66 °F (19 °C) 

 64 °F (18 

°C) 

 66 °F (19 °C) 

 64 °F (18 °C)

 →

 66 °F (19 °C) 

 64 °F (18 °C) 

 (test run) 

 ON/OFF

Heating test run: 

ON/OFF 

 86 °F (30 °C) 

 84 °F (29 °C) 

 86 °F (30 

°C) 

 84 °F (29 °C) 

 86 °F (30 °C) 

 84 °F (29 °C) 

 86 °F (30 °C) 

 (test run) 

 ON/OFF

Cooling test run

Heating test run

Set the temperature to 

64 °F 

(18 °C)

 with the temp. setup 

buttons.

Set the temperature to 

86 °F 

(30 °C)

 with the temp. setup 

buttons.

Cooling test run

Heating test run

After confirming a signal 

receiving sound “beep” 

immediately set the 

temperature to 

66 °F (19 °C)

 

with the temp. setup buttons.

After confirming a signal 

receiving sound “beep” 

immediately set the 

temperature to 

84 °F (29 °C)

 

with the temp. setup buttons.

Cooling test run

Heating test run

After confirming a signal 

receiving sound “beep” 

immediately set the 

temperature to 

64 °F (18 °C)

 

with the temp. setup buttons.

After confirming a signal 

receiving sound “beep” 

immediately set the 

temperature to 

86 °F (30 °C)

 

with the temp. setup buttons.

3, 4, 

5, 6

2,7

2

2

Always select 

[HIGH] fan 

speed.

10

Troubleshooting

Confirmation and check

When an error occurred in the air conditioner, the 
check code and the indoor UNIT No. appear on the 
display part of the remote control.
The check code is only displayed during the operation.
If the display disappears, operate the air conditioner 
according to the following “Confirmation of error log” for 
confirmation.

Confirmation of error log

When an error occurred on the air conditioner, the error 
log can be confirmed with the following procedure. 
(The error log is stored in memory up to 4 errors.)
The log can be confirmed from both operating status 
and stop status.

Procedure 

1

Push 

 and 

 buttons simultaneously for 4 seconds 

or more, the following display appears.
If [Service check] 

 is displayed, the mode enters in 

the error log mode.
• [

01

: Order of error log] is displayed in CODE No. 

window.

• [Check code] is displayed in CHECK window.
• [Indoor unit address in which an error occurred] is 

displayed in Unit No.

Procedure 

2

Push 

 button. The error log stored in memory is 

displayed in order.

The numbers in CODE No. indicate CODE No. [

01

(latest) 

 [

04

] (oldest).

REQUIREMENT

Do not push 

 button because all the error log of the 

indoor unit will be deleted.

Procedure 

3

Push 

 button to return to the usual display after 

confirmation.

1. Check the errors according to the above procedure.
2. Ask an authorized dealer or qualified service 

(maintenance) professional to repair or maintain the 
air conditioner.

Check code

Indoor UNIT No. in 

which an error occurred

3

2

1

29-EN

30-EN

+00EH99876001-3.book  Page 15  Wednesday, May 27, 2015  10:08 AM

Summary of Contents for MMU-AP0072H2UL

Page 1: ...UL MMU AP0182H2UL MMU AP0212H2UL MMU AP0242H2UL MMU AP0302H2UL MMU AP0362H2UL MMU AP0422H2UL AIR CONDITIONER MULTI TYPE Installation Manual For commercial use Pour usage commercial Installation Manual 1 English Manuel d installation 19 Français 00EH99876001 3 book Page 1 Wednesday May 27 2015 10 08 AM ...

Page 2: ...y For the installation of these products follow the Installation Manuals supplied with them The wireless type remote control is designed to be installed by attaching a wireless remote control kit sold separately to the standard panel The wireless remote control kit consists of a wireless remote control and adjust corner caps with a signal receiving unit Part name Qty Shape Usage Installation Manua...

Page 3: ...is mixed in the refrigerant the gas pressure in the refrigeration cycle becomes abnormally high and it resultingly causes pipe burst and injuries on persons Perform installation work properly according to the Installation Manual Inappropriate installation may result in water leakage electric shock or fire When the air conditioner is installed in a small room provide appropriate measures to ensure ...

Page 4: ...e the air conditioner for special purposes such as preserving food precision instruments or art objects or where breeding animals or growing plants are kept This may degrade the quality of preserved materials Place where any of high frequency appliances including inverter devices private power generators medical equipment and communication equipment and inverter type fluorescent light is installed...

Page 5: ...ng can be raised Refer to 8 Applicable controls in this manual for the setting procedure Discharge direction As shown in the figure below air discharge directions can be selected according to the shape of the room and the location of the indoor unit installation Model MMU Possible installed ceiling height AP007 to AP030 Type Up to 12 6 3 8 m AP036 AP042 Type Up to 15 1 4 6 m Model MMU AP007 AP009 ...

Page 6: ... of the indoor unit installation and orientation After the location of the indoor unit installation has been determined open the ceiling and install hanging bolts The dimensions of the ceiling opening and hanging bolt pitches are given in the outline drawing and the attached installation pattern When a ceiling already exists lay the drain pipe refrigerant pipe control wires and remote control wire...

Page 7: ...use water leakage Hanging bolt Level Hanging bracket Washer Accessory To prevent the bolt from falling off for safety be sure to set it just under the hanging bracket as shown in the figure Eccentric washer Accessory Nut 3 8 M10 Hanging bolt 3 8 M10 Nut 3 8 M10 Procure hanging bolts and nuts locally Install with the marking UP facing up Indoor unit Level vial levelness 0 2 5 mm or less Hanging bol...

Page 8: ...ocally procured to the hard socket of the attached supplied flexible hose Connect a drain pipe locally procured to the connected hard socket REQUIREMENT Connect hard vinyl chloride pipes securely using an adhesive for vinyl chloride to avoid water leakage It takes some time until the adhesive is dried and hardened refer to the manual of the adhesive Do not apply stress to the joint with the drain ...

Page 9: ... 2 Flare nut and flare works are also different from those of the conventional refrigerant Take out the flare nut attached to the main unit of the air conditioner and use it REQUIREMENT When the refrigerant pipe is long provide support brackets at intervals of 8 2 9 10 2 5 3 m to clamp the refrigerant pipe Otherwise abnormal sound may be generated CAUTION IMPORTANT 4 POINTS FOR PIPING WORK 1 Remov...

Page 10: ... be faced upward ceiling side Banding band Locally procured 7 Electrical connection WARNING 1 Use predefined wire and connect them certainly Keep the connecting terminal free from external force Improper wire connection or clamping may result in exothermic fire or malfunction 2 Connect ground wire grounding work Incomplete grounding cause an electric shock Do not connect ground wires to gas pipes ...

Page 11: ... control wiring remote control inter unit wiring Wire size AWG20 Total wire length of remote control wiring and remote control inter unit wiring L L1 L2 Ln In case of wired type only Up to 1640 5 500 m In case of wireless type included Up to 1312 4 400 m Total wire length of remote control inter unit wiring L1 L2 Ln Up to 656 2 200 m L1 L L2 Ln Indoor unit Remote control inter unit wiring Indoor u...

Page 12: ...ck Conduit connection hole Piping Knockout Bushing of control and remote control wires Lock nut Conduit pipe Conduit plate Remote control terminal block Cord clamp Side D Space 0 33 8 5 mm Side C Space 0 16 4 mm Insert the wire to Side C Ground screw Ground screw for shielded wire control wire Power supply wires and ground wire 1 Strip the wire ends Power supply wire 0 4 10 mm Ground wire 0 8 20 m...

Page 13: ...nit runs and the louvers start swinging The indoor unit can be confirmed for which to change settings 1 6 1 3 2 5 4 Display content varies with the indoor unit model Procedure 3 Specify CODE No with temp setup buttons Procedure 4 Select SET DATA with timer time buttons Procedure 5 Push button When the display changes from flashing to lit the setup is completed To change settings of another indoor ...

Page 14: ...ion is selected ceiling contamination is less reduced SET DATA Filter sign lighting time 0000 None 0001 150 H 0002 2500 H Factory default 0003 5000 H 0004 10000 H SET DATA Detection temp shift value 0000 No shift 0001 1 8 F 1 C 0002 3 6 F 2 C Factory default 0003 5 4 F 3 C 0004 7 2 F 4 C 0005 9 0 F 5 C 0006 10 8 F 6 C SET DATA Louver direction setting 0000 Smudge reducing position Air direction to...

Page 15: ...er indoor unit Non polarity For address setup refer to the Installation Manual attached to the outdoor unit UNIT No 1 1 UNIT No 1 2 UNIT No 1 3 UNIT No 1 4 1 0001 2 0002 3 0003 5 0005 4 0004 SET DATA 0001 0005 SET DATA SET DATA 0000 0001 Remote control sensor Not used factory default Used 0000 SET DATA 9 Test run Before test run Before turning on the circuit breaker carry out the following procedu...

Page 16: ...test run After confirming a signal receiving sound beep immediately set the temperature to 64 F 18 C with the temp setup buttons After confirming a signal receiving sound beep immediately set the temperature to 86 F 30 C with the temp setup buttons 3 4 5 6 2 7 2 2 Always select HIGH fan speed 10Troubleshooting Confirmation and check When an error occurred in the air conditioner the check code and ...

Page 17: ...I F E16 E16 00 Capacity over 01 No of connected units Capacity over No of connected indoor units I F E18 Communication error between indoor units Indoor E19 E19 00 Header is nothing 02 Two or more header units Outdoor header units quantity error I F E20 E20 01 Outdoor of other line connected 02 Indoor of other line connected Other line connected during automatic address I F E23 E23 Sending error i...

Page 18: ...red remote control display Outdoor 7 segment display Sensor block display of receiving unit Auxiliary code Operation Timer Ready Flash A3 IPDU Fan IPDU 1 2 3 01 02 03 04 05 06 07 08 09 0A 0B 0C 0D 0E 0F IPDU error Error detected by TCC LINK central control device TCC LINK TOSHIBA Carrier Communication Link P18 P18 ALT Discharge temp TD3 error I F P19 P19 Detected outdoor unit number ALT 4 way valv...

Page 19: ...EH99876001 3 00EH99876001 3 book Page 39 Wednesday May 27 2015 10 08 AM ...

Reviews: