1:  Turn off power to the heating and cooling system and to the Infinity

TM

 air 

purifier.

2:  Remove the air purifier door (Fig. 1).  Disconnect the power cord and air 

flow sensor cables from the power supply module (Fig. 2).

3:  Remove the filter and enhancement module from the air purifier cabinet 

(Fig. 3) and place on a flat surface in a well lit area.

ELECTRICAL SHOCK  & HIGH VOLTAGE 

HAZARD

Failure to follow this warning could result in 

personal injury or death.
Before installing or servicing system, always turn 

off main power to system.  There may be more 

than one (1) disconnect switch.

WARNING

REMOVING THE OLD POWER SUPPLY:

CUT HAZARD

Failure to follow this caution may result in personal 

injury.  Sheet metal parts may have sharp edges or 

burrs.  Use care and wear appropriate protective 

clothing and gloves when handling parts.

CAUTION

Fig. 1

Fig. 3

Fig. 4

Fig. 5

Fig. 6

Fig. 7

Fig. 8

TO POWER SUPPLY

TO ENHANCEMENT GRID

4:  Disconnect the green ground wire from the 

enhancement module (Fig. 4).

5:  Cut the two high voltage wires where they 

exit the power supply enclosure (Fig. 5).

6:  Disconnect the ¼” quick disconnect terminal (with the cut wire) 

from the ionization array and discard (Fig. 6) - this may require 

the use of needle-nose pliers.

7:  Cut the splice away from the media enhancement grid wire (Fig. 7).  

Cut the media enhancement grid wire next to the wire splice under 

the heat shrink tubing (Fig. 8).

Fig. 2