Carrier INFINITY 24ANA Installation Instructions Manual Download Page 16

16

STATUS CODES

Table 5 shows the status codes flashed by the amber status light.

Most system problems can be diagnosed by reading the status
code as flashed by the amber status light on the control board.
The codes are flashed by a series of short and long flashes of the
status light. The short flashes indicate the first digit in the status

code, followed by long flashes indicating the second digit of the

error code. The short flash is 0.25 seconds ON and the long flash
is 1.0 second ON. Time between flashes is 0.25 seconds. Time

between short flash and first long flash is 1.0 second. Time
between code repeating is 2.5 seconds with LED OFF.
Count the number of short and long flashes to determine the
appropriate flash code. Table 5 gives possible causes and actions

related to each error.

EXAMPLE

:

3 short flashes followed by 2 long flashes indicates a 32 code.

Table 5 shows this to be low pressure switch open.

Table 5—TROUBLESHOOTING

OPERATION

FAULT

AMBER

LED

FLASH

CODE

POSSIBLE CAUSE AND ACTION

Standby – no call for unit operation

None

On solid, no

flash

Normal operation

Emergency Mode --- Model 24ANA1

only

Standard Thermo-

stat Control

(24ANA1 only)

Rapid, con-

tinuous flash-

ing

Unit being controlled by standard thermostat inputs instead of Infinity Con-

trol. Only high stage operation is available. This operating mode should be

used in emergency situations only.

Low Stage Cool/Heat Operation

None

1, pause

Normal operation

High Stage Cool/Heat Operation

None

2, pause

Normal operation

System Commu-

nications Failure

16

Communication with user interface lost. Check wiring to User Interface,

indoor and outdoor units

Invalid Model Plug

25

Control does not detect a model plug or detects an invalid model plug. Unit

will not operate without correct model plug.

High Pressure

Switch Open

31

High---pressure switch trip. Check refrigerant charge, outdoor fan operation

and coils for airflow restrictions.

Low Pressure

Switch Open

32

Low pressure switch trip. Check refrigerant charge and indoor air flow

Control Fault

45

Outdoor unit control board has failed. Control board needs to be replaced.

Brown Out (230 v)

46

Line voltage < 187v for at least 4 seconds. Compressor and fan operation

not allowed until voltage>190v. Verify line voltage.

No 230v at Unit

47

There is no 230v at the contactor when indoor unit is powered and cooling/

heating demand exists. Verify the disconnect is closed and 230v wiring is

connected to the unit.

Outdoor Air Temp

Sensor Fault

53

Outdoor air sensor not reading or out of range. Ohm out sensor and check

wiring.

Outdoor Coil Sen-

sor Fault

55

Coil sensor not reading or out of range. Ohm out sensor and check wiring.

Thermistors out of

range

56

Improper relationship between coil sensor and outdoor air sensor. Ohm out

sensors and check wiring.

Low Stage Ther-

mal Cutout

71

No voltage phase difference is detected (on 24ANA7 models) or compres-

sor voltage sensed, then disappears (on 24ANA1 models) while cooling or

heating demand exists. Possible causes are internal compressor overload

trip or start relay not releasing (if installed).

High Stage Ther-

mal Cutout

72

No voltage phase difference is detected (on 24ANA7 models) or compressor

voltage sensed, then disappears (on 24ANA1 models) while cooling or heat-

ing demand exists. Possible causes are internal compressor overload trip or

start relay not releasing (if installed).

Contactor Shorted

73

Compressor voltage sensed when no demand for compressor operation

exists. Contactor may be stuck closed or there is a wiring error.

No 230V at Com-

pressor

(24ANA1 Only)

74

Compressor voltage not sensed when compressor should be starting. Con-

tactor may be stuck open or there is a wiring error.

Low Stage Did Not

Start

(24ANA7 Only)

75

Specified start voltage at VR terminal was not achieved in low stage. Start

relay was de---energized after 1 second.

Low Stage Did Not

Start 3 times

(24ANA7Only)

76

For 3 consecutive low stage starts, the specified start voltage at VR terminal

was not achieved & start relay was de---energized. Low stage locked out for

30 minutes.

High Stage Did Not

Start

(24ANA7 Only)

77

Specified start voltage at VS terminal was not achieved in high stage. Start

relay was de---energized after 1 second.

High Stage Did Not

Start 3 times

(24ANA7 Only)

78

For 3 consecutive high stage starts, the specified start voltage at VS terminal

was not achieved & start relay was de---energized. High stage locked out for

30 minutes.

Low Stage Ther-

mal Lockout

81

Thermal cutout occurs in three consecutive low/ high stage cycles. Low

stage locked out for 4 hours or until 24v power recycled.

High Stage Ther-

mal Lockout

82

Thermal cutout occurs in three consecutive high/low stage cycles. High

stage locked out for 4 hours or until 24v power recycled.

Low Pressure

Lockout

83

Low pressure switch trip has occurred during 3 consecutive cycles. Unit

operation locked out for 4 hours or until 24v power recycled.

High Pressure

Lockout

84

High pressure switch trip has occurred during 3 consecutive cycles. Unit

operation locked out for 4 hours or until 24v power recycled.

Low Contactor

Open

(24ANA7 Only)

85

Compressor voltage not sensed when compressor should be starting. Low

stage contactor may be stuck open or there is a wiring error.

High Contactor

Open

(24ANA7 Only)

87

Compressor voltage not sensed when compressor should be starting. High

stage contactor may be stuck open or there is a wiring error.

24AN

A

Summary of Contents for INFINITY 24ANA

Page 1: ... series will also be identified TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS 2 INSTALLATION RECOMMENDATIONS 2 INSTALLATION 3 11 Step 1 Check Equipment Jobsite 3 Step 2 Install on Solid Pad 3 Step 3 Clearance Requirements 3 Step 4 Operating Ambient 3 Step 5 Install TXV 3 4 Step 6 Make Piping Connections 5 8 Step 7 Make Electrical Connections 8 9 Step 8 Compressor Crankcase Heater 9 Step 9 Install A...

Page 2: ...D SAFETY HAZARD Failure to follow this warning could result in personal injury or equipment damage Puron refrigerant systems operate at higher pressures than standard R 22 systems Do not use R 22 service equipment or components on Puron equipment INSTALLATION RECOMMENDATIONS NOTE In some cases noise in the living area has been traced to gas pulsations from improper installation of equipment 1 Loca...

Page 3: ...ng rooftop applications Roof mounted units exposed to winds above 5 mph may require wind baffles Consult the Application Guideline and Service Manual Residential Split System Air Conditioners and Heat Pumps Using Puron Refrigerant for wind baffle construction UNIT BASE PAN DIMENSIONS TIEDOWN KNOCKOUT LOCATIONS A B C 36 1 2 x 40 11 5 8 6 13 16 28 3 4 29 1 2 X 33 10 1 16 5 5 8 23 3 4 A05177 Fig 3 Cl...

Page 4: ...pe See Fig 4 for correct positioning of sensing bulb 9 Proceed with remainder of unit installation 2 O CLOCK 10 O CLOCK SENSING BULB STRAP SUCTION TUBE 8 O CLOCK 4 O CLOCK IN OD SMALLER LARGER THAN 7 8 IN OD 7 8 A81032 Fig 4 Position of Sensing Bulb REPLACING TXV ON R 22 INDOOR COIL 1 Pump system down to 2 psig and recover refrigerant 2 Remove coil access panel and fitting panel from front of cabi...

Page 5: ...e or improper operation To prevent damage to unit or service valves observe the following S Use a brazing shield S Wrap service valves with wet cloth or use a heat sink material Outdoor units may be connected to indoor section using accessory tubing package or field supplied refrigerant grade tubing of correct size and condition For tubing requirements beyond 80 ft substantial capacity and perform...

Page 6: ...d with Infinity Control Low Ambient not allowed with non communicating Thermostat No No Winter Start Control Standard with Infinity Control Low Ambient not allowed with Non Communicating Thermostat No No Accumulator No No No Compressor Start Assist Capacitor and Relay Standard on 24ANA7 models Not required on 24ANA1 models since compressor always starts un loaded Standard on 24ANA7 models Not requ...

Page 7: ...refrigerant grade tubing Service valves are closed from factory and ready for brazing After wrapping service valve with a wet cloth braze sweat connections using industry accepted methods and materials Consult local code requirements Refrigerant tubing and indoor coil are now ready for leak testing This check should include all field and factory joints EVACUATE REFRIGERANT TUBING AND INDOOR COIL C...

Page 8: ...t with compressor terminal box cover removed Be sure field wiring complies with local and national fire safety and electrical codes and voltage to system is within limits shown on unit rating plate Contact local power company for correction of improper voltage See unit rating plate for recommended circuit protection device NOTE Operation of unit on improper line voltage constitutes abuse and could...

Page 9: ...he positions of SW1 5 AIRFLOW SELECTION FOR FK4 FV4 FAN COILS FOR 24ANA7 MODELS ONLY USING NON COMMUNICAT ING NON INFINITY THERMOSTATS The FK4 and FV4 provide high and low stage blower operation to match the capacities of compressor at high and low stage To select recommended airflow refer to the FK4 and FV4 Installation Instructions The FK4 and FV4 utilize an Easy Select control board that allows...

Page 10: ...mber Status Light An amber colored STATUS light is used to display the operation mode and fault codes as specified in the troubleshooting section See Table 5 for codes and definitions NOTE Only one code will be displayed on the outdoor unit control board the most recent with the highest priority UTILITY INTERFACE With Infinity Control The utility curtailment relay should be wired between R and Y2 ...

Page 11: ...d low ambient operation The Infinity Control provides an automatic evaporator coil freeze protection algorithm that eliminates the need for an evaporator freeze thermostat Low ambient cooling must be enabled in the User Interface set up Fan may not begin to cycle until about 40_F OAT Fan will cycle based on coil and outdoor air temperature Infinity controlled low ambient mode operates as follows S...

Page 12: ...trol senses the opening of a high or low pressure switch it will respond as follows 1 De energize the appropriate compressor contactor 2 Keep the outdoor fan operating for 15 minutes 3 Display the appropriate fault code See Table 5 4 After a 15 minute delay if there is still a call for cooling and the LPS or HPS is reset the appropriate compressor contactor is energized 5 If LPS or HPS has not clo...

Page 13: ...art voltage at VS terminal is not achieved the start relay is de energized after 1 second and the control will flash the appropriate fault code If the specified start voltage is not achieved for 3 consecutive low stage starts low stage operation is locked out for 30 minutes If the specified start voltage is not achieved for 3 consecutive high stage starts high stage operation is locked out for 30 ...

Page 14: ... If the outdoor air sensor indicates 10_F warmer thanthe coil sensor or the outdoor air sensor indicates 20_F cooler than the coil sensor the sensors are out of range If the sensors are out of range the control will flash the appropriate fault code as shown in Table 5 The thermistor comparison is not performed during low ambient cooling or defrost operation FAILED THERMISTOR DEFAULT OPERATION Fact...

Page 15: ...2 74 1 98 1 55 0 74 Run R C 0 80 0 75 0 48 0 36 Winding 24ANA1024 24ANA1036 24ANA1048 24ANA1060 Start S C 1 40 1 29 1 52 0 60 Run R C 1 32 0 89 0 64 0 49 Table 4 Required Liquid Line Temperature F LIQUID PRESSURE AT SER VICE VALVE PSIG REQUIRED SUBCOOLING TEMPERATURE F 8 10 12 14 16 18 189 58 56 54 52 50 48 195 60 58 56 54 52 50 202 62 60 58 56 54 52 208 64 62 60 58 56 54 215 66 64 62 60 58 56 222...

Page 16: ...or not reading or out of range Ohm out sensor and check wiring Thermistors out of range 56 Improper relationship between coil sensor and outdoor air sensor Ohm out sensors and check wiring Low Stage Ther mal Cutout 71 No voltage phase difference is detected on 24ANA7 models or compres sor voltage sensed then disappears on 24ANA1 models while cooling or heating demand exists Possible causes are int...

Page 17: ...TY RISE HL38MG026 AIRFLOW SELECTOR R1 H AFS A02005 Fig 13 Infinity Wiring with 2 Stage Puron refrigerant Air Conditioner Applies to 24ANA7 Models Only WIRING DIAGRAM NOTES 1 WIRING MUST CONFORM TO NEC OR LOCAL CODES 2 UNDERLINED LETTER ON THERMOSTAT TERMINAL INDICATES USAGE FOR EXAMPLE O W2 MEANS O IS ENERGIZED IN COOLING MODE 3 REFER TO INDOOR UNIT INSTALLATION INSTRUCTIONS FOR ANY ADDITIONAL FEA...

Page 18: ...h rated working pressures less than 600 psig S Do not leave Puron suction line filter driers in line longer than 72 hours S Do not install a suction line filter drier in liquid line S POE oils absorb moisture rapidly Do not expose oil to atmosphere S POE oils may cause damage to certain plastics and roofing materials S Wrap all filter driers and service valves with wet cloth when brazing S A facto...

Reviews: