Carrier INFINITY 24ANA Installation Instructions Manual Download Page 13

13

24ANA7 MODELS, COMPRESSOR THERMAL CUTOUT

The control senses the compressor voltage at VR and VS. When

starting or running, a phase difference of the voltages on the
inputs will indicate the thermal protector is closed. If the phase

difference is 5 degrees or less for 10 seconds, the internal
protector is open. The control de--energizes the appropriate

compressor contactor for 15 minutes, but continues to operate the

outdoor fan. The control Status LED will flash the appropriate
code shown in table 5. After 15 minutes, with a call for low or

high stage cooling, the appropriate compressor contactor is
energized. If the thermal protector has not re--set, the outdoor fan

is turned off. If the call for cooling or heating continues, the

control will energize the compressor contactor every 15 minutes.
If the thermal protector closes, (at the next 15 minute interval

check), the unit will resume operation.
If the thermal cutout trips for three consecutive cycles, then unit

operation is locked out for 4 hours and the appropriate fault code
is displayed.

24ANA1 MODELS, COMPRESSOR THERMAL CUTOUT

If the control senses the compressor voltage after start--up, and is

then absent for 10 consecutive seconds while cooling demand

exists, the thermal protector is open. The control de--energizes
the compressor contactor for 15 minutes, but continues to operate

the outdoor fan.

The control Status LED will flash the

appropriate code shown in table 5. After 15 minutes, with a call

for low or high stage cooling, the compressor contactor is

energized. If the thermal protector has not re--set, the outdoor fan
is turned off. If the call for cooling continues, the control will

energize the compressor contactor every 15 minutes. If the
thermal protector closes, (at the next 15 minute interval check),

the unit will resume operation.
If the thermal cutout trips for three consecutive cycles, then unit

operation is locked out for 4 hours and the appropriate fault code

is displayed.

LOW OR HIGH CONTACTOR OPEN (24ANA7 MODELS)
/ NO 230V AT COMPRESSOR (24ANA1 MODELS)

If the compressor voltage is not sensed when the compressor
should be starting, the appropriate contactor may be stuck open or

there is a wiring error. The control will flash the appropriate fault

code. Check the contactor and control box wiring.

24ANA7 MODELS ONLY, COMPRESSOR START
DETECTION

In low stage, if the specified start voltage at VR terminal is not

achieved, the start relay is de--energized after 1 second and the
control will flash the appropriate fault code.
In high stage, if the specified start voltage at VS terminal is not
achieved, the start relay is de--energized after 1 second and the

control will flash the appropriate fault code.
If the specified start voltage is not achieved for 3 consecutive low

stage starts, low stage operation is locked out for 30 minutes. If

the specified start voltage is not achieved for 3 consecutive high
stage starts, high stage operation is locked out for 30 minutes.

The control will flash the appropriate fault code.

TROUBLESHOOTING 24ANA7 UNITS FOR PROPER
SWITCHING BETWEEN LOW & HIGH STAGES

Check the suction and liquid pressures at the service valves.

Suction pressure should be reduced by 5--10% when switching

from low to high capacity. There should be a 10--20% increase in
liquid pressure when switching from low to high capacity.

Compressor current should increase 100--250% when switching
from low to high stage.

TROUBLESHOOTING 24ANA1 UNITS FOR PROPER
SWITCHING BETWEEN LOW & HIGH STAGES

Check the suction pressures at the service valves.

Suction

pressure should be reduced by 3--10% when switching from low

to high capacity.

NOTE

: The liquid pressures are very similar between low and

high stage operation, so liquid pressure should not be used for
troubleshooting.
Compressor current should increase 20--45% when switching

from low to high stage.

The compressor solenoid when

energized in high stage, should measure 24vac.

MAJOR COMPONENTS
2--STAGE CONTROL

The two--stage control board controls the following functions:
-- Low-- and high--stage compressor contactor operation
-- Outdoor fan motor operation
-- Low ambient cooling
-- Crankcase heater operation
-- Compressor external protection
-- Pressure switch monitoring
-- Time delays
-- On 24ANA7 models, start relay and capacitor

FIELD CONNECTIONS

On 24ANA7 models with non--communicating (non--Infinity)
system, the two--stage control receives 24vac low--voltage control

system inputs through the R, C, Y1, and Y2 connections located
at the bottom of the control board (see Fig. 10)
All 24ANA1 models are part of a complete Infinity

communicating system and use only the ABCD connections on
the circuit board.

TWO STAGE COMPRESSOR

The two stage compressor contains motor windings that provide

2--pole (3500 RPM) operation. Refer to Table 3 for correct
winding resistance.

COMPRESSOR INTERNAL RELIEF

The compressor is protected by an internal pressure relief (IPR)

which relieves discharge gas into compressor shell when
differential between suction and discharge pressures exceeds 500

-- 550 psi on 24ANA7 models and 550 -- 625 psi on 24ANA1

models.. The compressor is also protected by an internal overload
attached to motor windings.

COMPRESSOR CONTROL CONTACTORS

The contactor(s) have a 24 volt coil. The electronic control board

controls the operation of the appropriate contactors.

24AN

A

Summary of Contents for INFINITY 24ANA

Page 1: ... series will also be identified TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS 2 INSTALLATION RECOMMENDATIONS 2 INSTALLATION 3 11 Step 1 Check Equipment Jobsite 3 Step 2 Install on Solid Pad 3 Step 3 Clearance Requirements 3 Step 4 Operating Ambient 3 Step 5 Install TXV 3 4 Step 6 Make Piping Connections 5 8 Step 7 Make Electrical Connections 8 9 Step 8 Compressor Crankcase Heater 9 Step 9 Install A...

Page 2: ...D SAFETY HAZARD Failure to follow this warning could result in personal injury or equipment damage Puron refrigerant systems operate at higher pressures than standard R 22 systems Do not use R 22 service equipment or components on Puron equipment INSTALLATION RECOMMENDATIONS NOTE In some cases noise in the living area has been traced to gas pulsations from improper installation of equipment 1 Loca...

Page 3: ...ng rooftop applications Roof mounted units exposed to winds above 5 mph may require wind baffles Consult the Application Guideline and Service Manual Residential Split System Air Conditioners and Heat Pumps Using Puron Refrigerant for wind baffle construction UNIT BASE PAN DIMENSIONS TIEDOWN KNOCKOUT LOCATIONS A B C 36 1 2 x 40 11 5 8 6 13 16 28 3 4 29 1 2 X 33 10 1 16 5 5 8 23 3 4 A05177 Fig 3 Cl...

Page 4: ...pe See Fig 4 for correct positioning of sensing bulb 9 Proceed with remainder of unit installation 2 O CLOCK 10 O CLOCK SENSING BULB STRAP SUCTION TUBE 8 O CLOCK 4 O CLOCK IN OD SMALLER LARGER THAN 7 8 IN OD 7 8 A81032 Fig 4 Position of Sensing Bulb REPLACING TXV ON R 22 INDOOR COIL 1 Pump system down to 2 psig and recover refrigerant 2 Remove coil access panel and fitting panel from front of cabi...

Page 5: ...e or improper operation To prevent damage to unit or service valves observe the following S Use a brazing shield S Wrap service valves with wet cloth or use a heat sink material Outdoor units may be connected to indoor section using accessory tubing package or field supplied refrigerant grade tubing of correct size and condition For tubing requirements beyond 80 ft substantial capacity and perform...

Page 6: ...d with Infinity Control Low Ambient not allowed with non communicating Thermostat No No Winter Start Control Standard with Infinity Control Low Ambient not allowed with Non Communicating Thermostat No No Accumulator No No No Compressor Start Assist Capacitor and Relay Standard on 24ANA7 models Not required on 24ANA1 models since compressor always starts un loaded Standard on 24ANA7 models Not requ...

Page 7: ...refrigerant grade tubing Service valves are closed from factory and ready for brazing After wrapping service valve with a wet cloth braze sweat connections using industry accepted methods and materials Consult local code requirements Refrigerant tubing and indoor coil are now ready for leak testing This check should include all field and factory joints EVACUATE REFRIGERANT TUBING AND INDOOR COIL C...

Page 8: ...t with compressor terminal box cover removed Be sure field wiring complies with local and national fire safety and electrical codes and voltage to system is within limits shown on unit rating plate Contact local power company for correction of improper voltage See unit rating plate for recommended circuit protection device NOTE Operation of unit on improper line voltage constitutes abuse and could...

Page 9: ...he positions of SW1 5 AIRFLOW SELECTION FOR FK4 FV4 FAN COILS FOR 24ANA7 MODELS ONLY USING NON COMMUNICAT ING NON INFINITY THERMOSTATS The FK4 and FV4 provide high and low stage blower operation to match the capacities of compressor at high and low stage To select recommended airflow refer to the FK4 and FV4 Installation Instructions The FK4 and FV4 utilize an Easy Select control board that allows...

Page 10: ...mber Status Light An amber colored STATUS light is used to display the operation mode and fault codes as specified in the troubleshooting section See Table 5 for codes and definitions NOTE Only one code will be displayed on the outdoor unit control board the most recent with the highest priority UTILITY INTERFACE With Infinity Control The utility curtailment relay should be wired between R and Y2 ...

Page 11: ...d low ambient operation The Infinity Control provides an automatic evaporator coil freeze protection algorithm that eliminates the need for an evaporator freeze thermostat Low ambient cooling must be enabled in the User Interface set up Fan may not begin to cycle until about 40_F OAT Fan will cycle based on coil and outdoor air temperature Infinity controlled low ambient mode operates as follows S...

Page 12: ...trol senses the opening of a high or low pressure switch it will respond as follows 1 De energize the appropriate compressor contactor 2 Keep the outdoor fan operating for 15 minutes 3 Display the appropriate fault code See Table 5 4 After a 15 minute delay if there is still a call for cooling and the LPS or HPS is reset the appropriate compressor contactor is energized 5 If LPS or HPS has not clo...

Page 13: ...art voltage at VS terminal is not achieved the start relay is de energized after 1 second and the control will flash the appropriate fault code If the specified start voltage is not achieved for 3 consecutive low stage starts low stage operation is locked out for 30 minutes If the specified start voltage is not achieved for 3 consecutive high stage starts high stage operation is locked out for 30 ...

Page 14: ... If the outdoor air sensor indicates 10_F warmer thanthe coil sensor or the outdoor air sensor indicates 20_F cooler than the coil sensor the sensors are out of range If the sensors are out of range the control will flash the appropriate fault code as shown in Table 5 The thermistor comparison is not performed during low ambient cooling or defrost operation FAILED THERMISTOR DEFAULT OPERATION Fact...

Page 15: ...2 74 1 98 1 55 0 74 Run R C 0 80 0 75 0 48 0 36 Winding 24ANA1024 24ANA1036 24ANA1048 24ANA1060 Start S C 1 40 1 29 1 52 0 60 Run R C 1 32 0 89 0 64 0 49 Table 4 Required Liquid Line Temperature F LIQUID PRESSURE AT SER VICE VALVE PSIG REQUIRED SUBCOOLING TEMPERATURE F 8 10 12 14 16 18 189 58 56 54 52 50 48 195 60 58 56 54 52 50 202 62 60 58 56 54 52 208 64 62 60 58 56 54 215 66 64 62 60 58 56 222...

Page 16: ...or not reading or out of range Ohm out sensor and check wiring Thermistors out of range 56 Improper relationship between coil sensor and outdoor air sensor Ohm out sensors and check wiring Low Stage Ther mal Cutout 71 No voltage phase difference is detected on 24ANA7 models or compres sor voltage sensed then disappears on 24ANA1 models while cooling or heating demand exists Possible causes are int...

Page 17: ...TY RISE HL38MG026 AIRFLOW SELECTOR R1 H AFS A02005 Fig 13 Infinity Wiring with 2 Stage Puron refrigerant Air Conditioner Applies to 24ANA7 Models Only WIRING DIAGRAM NOTES 1 WIRING MUST CONFORM TO NEC OR LOCAL CODES 2 UNDERLINED LETTER ON THERMOSTAT TERMINAL INDICATES USAGE FOR EXAMPLE O W2 MEANS O IS ENERGIZED IN COOLING MODE 3 REFER TO INDOOR UNIT INSTALLATION INSTRUCTIONS FOR ANY ADDITIONAL FEA...

Page 18: ...h rated working pressures less than 600 psig S Do not leave Puron suction line filter driers in line longer than 72 hours S Do not install a suction line filter drier in liquid line S POE oils absorb moisture rapidly Do not expose oil to atmosphere S POE oils may cause damage to certain plastics and roofing materials S Wrap all filter driers and service valves with wet cloth when brazing S A facto...

Reviews: