background image

8

19. Replace burner box cover.
20. Turn on gas and electrical supplies to furnace.
21. Check for gas leaks.
22. Replace main furnace door.

D. CLEANING HEAT EXCHANGERS

The following items should be performed by a qualified service
technician.

Primary Heat Exchangers

If the heat exchangers get an accumulation of light dirt or dust on

the inside, they may be cleaned by the following procedure:

NOTE

: If the heat exchangers get a heavy accumulation of soot

and carbon, both the primary and secondary heat exchangers
should be replaced rather than trying to clean them thoroughly
due to their intricate design. A build--up of soot and carbon
indicates that a problem exists which needs to be corrected, such
as improper adjustment of manifold pressure, insufficient or poor
quality combustion air, improper vent termination, incorrect size
or damaged manifold orifice(s), improper gas, or a restricted heat
exchanger (primary or secondary). Action must be taken to
correct the problem.

1. Turn off gas and electrical supplies to furnace.
2. Remove main furnace door.

UNIT DAMAGE HAZARD

Failure to follow this caution may result in furnace

component damage.
Label all wires prior to disconnection when servicing

controls. Wiring errors can cause improper and hazardous

operation.

CAUTION

!

3. Disconnect wires or connectors to flame rollout switch,

gas valve, igniter, and flame sensor.

4. Disconnect combustion--air intake pipe from intake

housing.

5. Remove the pressure switch tube from intake housing.
6. Remove screws attaching intake housing to burner box,

and rotate intake housing away from burner box for
removal.

7. Using backup wrench, disconnect gas supply pipe from

furnace gas control valve.

8. Disconnect pressure tubing from gas valve.
9. Remove two screws attaching top filler panel and rotate

upwards to gain access to screws attaching burner box to

cell panel.

10. Remove screws attaching burner box to cell panel. (See

Fig. 6.)

NOTE

: Burner box, cover, manifold, gas valve, and burner

assembly should be removed as one assembly.

11. Clean heat exchanger openings with a vacuum and a soft

brush. (See Fig. 8.) NOTE: After cleaning, inspect the heat
exchangers to ensure they are free of all foreign objects

that may restrict flow of combustion products.

12. Reverse items 4 through 10 for reassembly.

NOTE

: Be sure burner box gasket is installed between burner

box and cell panel. (See Fig. 6.) If gasket is damaged, replace it.

NOTE

: Inspect combustion--air intake housing. If foamed gasket

was removed, check for any damage. If gasket is damaged in any
way, it must be repaired. To repair, remove damaged gasket
section, apply sealant releasing agent such as PAM cooking spray
or equivalent (must not contain corn nor canola oil, halogenated
hydrocarbons nor aromatic content, to prevent inadequate seal

from occurring) to burner box and apply a small bead of G.E.
RTV 162, G.E. RTV 6702, or Dow--Corning RTV 738 sealant to
edge of combustion--air intake housing. (See Fig. 9.)

UNIT MAY NOT OPERATE

Failure to follow this caution may result in improper unit

operation.
Failure to attach ground wire to an adequate casing ground

may cause the furnace control to lock out. The ground wire

from the gas valve MUST be attached to the burner box

attachment screw.

CAUTION

!

13. Refer to furnace wiring diagram and reconnect wires to

flame rollout switch, gas valve, igniter, and flame sensor.

14. Reconnect pressure switch tubes to gas valve and intake

housing. Refer to tube routing label on main furnace door
for proper tube location. (See Fig. 10.) Be sure tubes are
not kinked.

15. Turn on gas and electrical supplies to furnace.
16. Check furnace operation through 2 complete heat

operating cycles. Look through sight glass in burner
enclosure to check burners. Burner flames should be clear

blue, almost transparent. (See Fig. 11.)

17. Check for gas leaks.

FIRE OR EXPLOSION HAZARD

Failure to follow this warning could result in personal

injury, death, or property damage.
Never test for gas leaks with an open flame. Use a

commercially available soap solution made specifically for

the detection of leaks to check all connections.

!

WARNING

18. Replace main furnace door.

E. Secondary Heat Exchangers

NOTE

: The condensing side (inside) of the secondary heat

exchangers CANNOT be serviced or inspected. A small number
of bottom outlet openings can be inspected by removing the
inducer assembly. See Flushing Collector Box and Drainage
System section for details on removing inducer assembly.

F. FLUSHING COLLECTOR BOX AND DRAINAGE

SYSTEM

1. Turn off gas and electrical supplies to furnace.
2. Remove main furnace door.
3. Disconnect inducer motor and pressure switch wires or

connectors.

4. Disconnect pressure switch tubes.
5. Disconnect vent pipe from inducer housing outlet by

loosening coupling clamp on inducer outlet.

6. Disconnect drain tube from inducer housing. (See Fig.

10.)

NOTE

: Ensure the drain tube disconnected from the inducer

housing is higher than the collector box opening or water will
flow out of tube.

7. Remove inducer housing assembly by removing 4 bolts

attaching assembly to cell panel.

58MV

C

Summary of Contents for IDEALCOMFORT 58MVC

Page 1: ...ED ISO 9001 2000 SAFETY CONSIDERATIONS Recognize safety information This is the safety alert symbol When you see this symbol on the unit and in instructions or manuals be alert to the potential for personal injury Understand the signal words DANGER WARNING CAUTION and NOTE These words are used with the safety alert symbol DANGER identifies the most serious hazards which will result in severe perso...

Page 2: ...ARGING YOUR BODY S ELECTROSTATIC CHARGE TO GROUND 2 Firmly touch a clean unpainted metal surface of the furnace chassis which is close to the control Tools held in a person s hand during grounding will be satisfactorily discharged 3 After touching the chassis you may proceed to service the control or connecting wires as long as you do nothing that recharges your body with static electricity for ex...

Page 3: ...washable filter clean filter by spraying cold tap water through filter in opposite direction of airflow Rinse filter and let dry Oiling or coating of the filter is not recommended 5 If equipped with factory specified disposable media filter replace only with a factory specified media filter of the same size FILTER RETAINER WASHABLE FILTER IN FURNACE WASHABLE FILTER OR DISPOSABLE MEDIA FILTER IN FI...

Page 4: ...clips on blower wheel vanes Do not bend wheel or blades as balance will be affected 8 If greasy residue is present on blower wheel remove wheel from the blower housing and wash it with an appropriate degreaser To remove wheel a Mark blower wheel location on shaft before disassembly to ensure proper reassembly b Loosen setscrew holding blower wheel on motor shaft NOTE Mark blower mounting arms and ...

Page 5: ...ube from gas valve regulator fitting 7 Unplug igniter from harness 8 Remove igniter leads from slot in manifold grommet 9 Remove screws that secure manifold to burner box See Fig 6 NOTE Do not remove burner box from cell panel 10 Remove manifold orifices and gas valve as 1 assembly 11 Remove screws attaching burner assembly in burner box NOTE Use care when removing and reinstalling burners not to ...

Page 6: ...T BE PLACED IN THIS SLOT A05074 Fig 7 Igniter Wire Placement PRIMARY HX INLET OPENINGS A96305 Fig 8 Cleaning Inlet Openings of Primary Heat Exchangers PAM RTV A93087 Fig 9 Combustion air Intake Housing Gasket Repair 58MVC ...

Page 7: ...lure to follow this warning could result in personal injury death or property damage Gas valve switch MUST be facing forward or tilted slightly WARNING FIRE OR EXPLOSION HAZARD Failure to follow this warning could result in personal injury or death or property damage Never test for gas leaks with an open flame Use a commercially available soap solution made specifically for the detection of leaks ...

Page 8: ...ion air intake housing If foamed gasket was removed check for any damage If gasket is damaged in any way it must be repaired To repair remove damaged gasket section apply sealant releasing agent such as PAM cooking spray or equivalent must not contain corn nor canola oil halogenated hydrocarbons nor aromatic content to prevent inadequate seal from occurring to burner box and apply a small bead of ...

Page 9: ...ccur If leaks are found correct the problem 15 Check for gas leaks 16 Replace main furnace door RTV PAM A93081 Fig 12 Gasket on Collector Box FIRE AND EXPLOSION HAZARD Failure to follow this warning could result in personal injury death or property damage Never test for gas leaks with an open flame Use a commercially available soap solution made specifically for the detection of leaks to check all...

Page 10: ...ensor The 24 v circuit contains an automotive type 3 amp fuse located on the furnace control See Fig 16 Any direct shorts of the 24 v wiring during installation service or maintenance will cause this fuse to blow If fuse replacement is required use ONLY a fuse of identical size The furnace control LED will flash status code 24 when fuse needs to be replaced With power to the unit disconnected chec...

Page 11: ...e condensate enters open drain See Fig 19 UNIT DAMAGE HAZARD Failure of plastic components may occur Do not use ethylene glycol Prestone II antifreeze coolant or equivalent automotive type CAUTION 6 Replace drain connection cap and clamp to inducer housing 7 Replace main furnace door 8 Propylene glycol need not be removed before restarting furnace WIRING DIAGRAMS See Fig 15 16 and 21 for the Delux...

Page 12: ...e through 1 heat cycle to check for proper operation and check LED status j If furnace is operating properly and LEDs indicateproper operation replace main furnace door 3 The control can also assist in troubleshooting by performing a Component Test The Component Test will functionally operate all furnace components except the gas valve NOTE The component test feature will not operate if the furnac...

Page 13: ... LED LIGHTS SW1 SETUP SWITCHES AND BLOWER OFF DELAY MODEL PLUG CONNECTOR AIR CONDITIONING A C AIRFLOW SETUP SWITCHES USER INTERFACE OR ADVANCED PRODUCT MONITOR CONNECTOR CONTINUOUS FAN CF AIRFLOW SETUP SWITCHES OAT CONNECTOR HUMIDIFIER TERMINAL 24 VAC 0 5 AMP MAX ACRDJ AIR CONDITIONING RELAY DISABLE JUMPER FLASH UPGRADE CONNECTOR FACTORY ONLY SW4 SETUP SWITCHES BOARD SERIAL NUMBER EXAMPLE V12 HK42...

Page 14: ...F MINIMUM INSTALLED AMBIENT OR FREEZE PROTECTION REQUIRED A93058 Fig 17 Freeze Protection A99118 Fig 18 Inducer Housing Drain Tube A99119 Fig 19 Funnel in Drain Tube and Antifreeze Running Through Trap 58MVC ...

Page 15: ...15 A07564 Fig 20 Service Label 58MVC ...

Page 16: ...16 A06677 Fig 21 Wiring Diagram 58MVC ...

Page 17: ...switch SW1 1 in the ON position and jumpering R W W1 and Y Y2 simultaneously setup switch SW1 1 in the OFF position Was there a previous status code other than 11 Go to section below for the status code Does the control respond to W W1 W2 Y1 Y Y2 and G 24V thermostat signals Run system through a low heat medium heat high heat or cooling cycle to check operation Status codes are erased after 72 hou...

Page 18: ...l is lost during the blower on delay period blower will come on for the selected blower off delay Check the following items first before proceeding to the next step Gas valve turned off Manual shut off valve Green Yellow wire MUST be connected to furnace sheet metal Flame sensor must not be grounded To determine whether the problem is in the gas valve igniter or flame sensor the system can be oper...

Page 19: ...en wire or bad terminal on either the RED or GREEN wire between the furnace control and the blower motor YES Is there 5 VDC at PL13 2 YELLOW and PL13 4 GREEN Is there 5 VDC at PL3 3 YELLOW and PL3 2 GREEN NO NO You have an open wire or bad terminal on the YELLOW wire between the furnace control and the blower motor YES YES The voltage just measured should be very stable and should not fluctuate mo...

Page 20: ...panion book Classroom ServiceTraining plus hands on the products in our labs can mean increased confidence that really pays dividends in faster troubleshooting fewer callbacks Course descriptions and schedules are in our catalog CALL FOR FREE CATALOG 1 800 644 5544 Packaged Service Training Classroom Service Training Copyright 2007 Carrier Corp S 7310 W Morris St S Indianapolis IN 46231 Manufactur...

Reviews: