10

UNIT DAMAGE HAZARD

Failure to follow this caution may result in premature

failure of the igniter.
The igniter is fragile. DO NOT allow it to hit burner box

parts while removing or replacing it.

CAUTION

!

e. If replacement is required, replace igniter on igniter

bracket and then install assembly into burner box to avoid

damage to the igniter.

6. To replace igniter and bracket assembly, reverse items 5a

through 5d.

7. Reconnect igniter wire connection and insert the igniter

wires in the slot in the manifold grommet, dressing the

igniter wires to ensure there is no tension on the igniter
itself. (See Fig.7.)

ELECTRICAL OPERATION HAZARD

Failure to follow this warning could result in personal

injury or death.
Igniter wires must be securely placed in slot in manifold

grommet or else they could become pinched or severed and

electrically shorted.

!

WARNING

2-5/32

˝

A04181

Fig. 14 -- Igniter

8. Reinstall burner box cover.
9. Turn on gas and electrical supplies to furnace.

10. Verify igniter operation by initiating control board

self--test feature or by cycling thermostat.

11. Replace main furnace door.

H. ELECTRICAL CONTROLS AND WIRING

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal

injury or death.
There may be more than 1 electrical supply to the unit.

Check accessories and cooling unit for additional electrical

supplies.

!

WARNING

The electrical ground and polarity for 115--v wiring must be
maintained properly. Refer to Fig. 15 for field wiring information

and to Fig. 21 for unit wiring information.

NOTE

: If the polarity is not correct or furnace is not properly

grounded, the STATUS LED on the furnace control will flash
rapidly and prevent the furnace from operating. The control
system also requires an earth ground for proper operation of the
furnace control and flame sensor.
The 24--v circuit contains an automotive--type, 3--amp fuse
located on the furnace control. (See Fig. 16.) Any direct shorts of
the 24--v wiring during installation, service, or maintenance will
cause this fuse to blow. If fuse replacement is required, use ONLY
a fuse of identical size. The furnace control LED will flash status
code 24 when fuse needs to be replaced.
With power to the unit disconnected, check all electrical
connections for tightness. Tighten all screws on electrical
connections. If any smoky or burned connections are found,
disassemble the connection, clean all parts, strip wire, and
reassemble properly and securely.
Reconnect electrical supply to unit and observe unit through 1
complete operating cycle and check for proper operation.

I. CHECKING HEAT TAPE OPERATION

(IF APPLICABLE)

In applications where the ambient temperature around the furnace

is 32

_

F or lower, freeze protection measures are required. If this

application is where heat tape has been applied, check to ensure it
will operate when low temperatures are present.

NOTE

: Heat tape, when used, should be wrapped around the

condensate drain trap and drain line. There is no need to use heat
tape within the furnace casing. Most heat tapes are temperature
activated, and it is not practical to verify the actual heating of the
tape. Check the following:

1. Check for signs of physical damage to heat tape such as

nicks, cuts, abrasions, gnawing by animals, etc.

2. Check for discolored heat tape insulation. If any damage

or discolored insulation is evident, replace heat tape.

3. Check that heat tape power supply circuit is on.

UNIT AND PROPERTY DAMAGE HAZARD

Failure to follow this caution may result in furnace

component failures or water property damage.
If this furnace is to be operated in an unconditioned space

where the ambient temperatures may be 32

_

F (0

_

C) or

lower, freeze protection measures must be taken. See

CONDENSATE DRAIN PROTECTION section of

Installation, Start--up, and Operating Instructions. (See Fig.

17.)

CAUTION

!

58MV

C

Summary of Contents for IDEALCOMFORT 58MVC

Page 1: ...ED ISO 9001 2000 SAFETY CONSIDERATIONS Recognize safety information This is the safety alert symbol When you see this symbol on the unit and in instructions or manuals be alert to the potential for personal injury Understand the signal words DANGER WARNING CAUTION and NOTE These words are used with the safety alert symbol DANGER identifies the most serious hazards which will result in severe perso...

Page 2: ...ARGING YOUR BODY S ELECTROSTATIC CHARGE TO GROUND 2 Firmly touch a clean unpainted metal surface of the furnace chassis which is close to the control Tools held in a person s hand during grounding will be satisfactorily discharged 3 After touching the chassis you may proceed to service the control or connecting wires as long as you do nothing that recharges your body with static electricity for ex...

Page 3: ...washable filter clean filter by spraying cold tap water through filter in opposite direction of airflow Rinse filter and let dry Oiling or coating of the filter is not recommended 5 If equipped with factory specified disposable media filter replace only with a factory specified media filter of the same size FILTER RETAINER WASHABLE FILTER IN FURNACE WASHABLE FILTER OR DISPOSABLE MEDIA FILTER IN FI...

Page 4: ...clips on blower wheel vanes Do not bend wheel or blades as balance will be affected 8 If greasy residue is present on blower wheel remove wheel from the blower housing and wash it with an appropriate degreaser To remove wheel a Mark blower wheel location on shaft before disassembly to ensure proper reassembly b Loosen setscrew holding blower wheel on motor shaft NOTE Mark blower mounting arms and ...

Page 5: ...ube from gas valve regulator fitting 7 Unplug igniter from harness 8 Remove igniter leads from slot in manifold grommet 9 Remove screws that secure manifold to burner box See Fig 6 NOTE Do not remove burner box from cell panel 10 Remove manifold orifices and gas valve as 1 assembly 11 Remove screws attaching burner assembly in burner box NOTE Use care when removing and reinstalling burners not to ...

Page 6: ...T BE PLACED IN THIS SLOT A05074 Fig 7 Igniter Wire Placement PRIMARY HX INLET OPENINGS A96305 Fig 8 Cleaning Inlet Openings of Primary Heat Exchangers PAM RTV A93087 Fig 9 Combustion air Intake Housing Gasket Repair 58MVC ...

Page 7: ...lure to follow this warning could result in personal injury death or property damage Gas valve switch MUST be facing forward or tilted slightly WARNING FIRE OR EXPLOSION HAZARD Failure to follow this warning could result in personal injury or death or property damage Never test for gas leaks with an open flame Use a commercially available soap solution made specifically for the detection of leaks ...

Page 8: ...ion air intake housing If foamed gasket was removed check for any damage If gasket is damaged in any way it must be repaired To repair remove damaged gasket section apply sealant releasing agent such as PAM cooking spray or equivalent must not contain corn nor canola oil halogenated hydrocarbons nor aromatic content to prevent inadequate seal from occurring to burner box and apply a small bead of ...

Page 9: ...ccur If leaks are found correct the problem 15 Check for gas leaks 16 Replace main furnace door RTV PAM A93081 Fig 12 Gasket on Collector Box FIRE AND EXPLOSION HAZARD Failure to follow this warning could result in personal injury death or property damage Never test for gas leaks with an open flame Use a commercially available soap solution made specifically for the detection of leaks to check all...

Page 10: ...ensor The 24 v circuit contains an automotive type 3 amp fuse located on the furnace control See Fig 16 Any direct shorts of the 24 v wiring during installation service or maintenance will cause this fuse to blow If fuse replacement is required use ONLY a fuse of identical size The furnace control LED will flash status code 24 when fuse needs to be replaced With power to the unit disconnected chec...

Page 11: ...e condensate enters open drain See Fig 19 UNIT DAMAGE HAZARD Failure of plastic components may occur Do not use ethylene glycol Prestone II antifreeze coolant or equivalent automotive type CAUTION 6 Replace drain connection cap and clamp to inducer housing 7 Replace main furnace door 8 Propylene glycol need not be removed before restarting furnace WIRING DIAGRAMS See Fig 15 16 and 21 for the Delux...

Page 12: ...e through 1 heat cycle to check for proper operation and check LED status j If furnace is operating properly and LEDs indicateproper operation replace main furnace door 3 The control can also assist in troubleshooting by performing a Component Test The Component Test will functionally operate all furnace components except the gas valve NOTE The component test feature will not operate if the furnac...

Page 13: ... LED LIGHTS SW1 SETUP SWITCHES AND BLOWER OFF DELAY MODEL PLUG CONNECTOR AIR CONDITIONING A C AIRFLOW SETUP SWITCHES USER INTERFACE OR ADVANCED PRODUCT MONITOR CONNECTOR CONTINUOUS FAN CF AIRFLOW SETUP SWITCHES OAT CONNECTOR HUMIDIFIER TERMINAL 24 VAC 0 5 AMP MAX ACRDJ AIR CONDITIONING RELAY DISABLE JUMPER FLASH UPGRADE CONNECTOR FACTORY ONLY SW4 SETUP SWITCHES BOARD SERIAL NUMBER EXAMPLE V12 HK42...

Page 14: ...F MINIMUM INSTALLED AMBIENT OR FREEZE PROTECTION REQUIRED A93058 Fig 17 Freeze Protection A99118 Fig 18 Inducer Housing Drain Tube A99119 Fig 19 Funnel in Drain Tube and Antifreeze Running Through Trap 58MVC ...

Page 15: ...15 A07564 Fig 20 Service Label 58MVC ...

Page 16: ...16 A06677 Fig 21 Wiring Diagram 58MVC ...

Page 17: ...switch SW1 1 in the ON position and jumpering R W W1 and Y Y2 simultaneously setup switch SW1 1 in the OFF position Was there a previous status code other than 11 Go to section below for the status code Does the control respond to W W1 W2 Y1 Y Y2 and G 24V thermostat signals Run system through a low heat medium heat high heat or cooling cycle to check operation Status codes are erased after 72 hou...

Page 18: ...l is lost during the blower on delay period blower will come on for the selected blower off delay Check the following items first before proceeding to the next step Gas valve turned off Manual shut off valve Green Yellow wire MUST be connected to furnace sheet metal Flame sensor must not be grounded To determine whether the problem is in the gas valve igniter or flame sensor the system can be oper...

Page 19: ...en wire or bad terminal on either the RED or GREEN wire between the furnace control and the blower motor YES Is there 5 VDC at PL13 2 YELLOW and PL13 4 GREEN Is there 5 VDC at PL3 3 YELLOW and PL3 2 GREEN NO NO You have an open wire or bad terminal on the YELLOW wire between the furnace control and the blower motor YES YES The voltage just measured should be very stable and should not fluctuate mo...

Page 20: ...panion book Classroom ServiceTraining plus hands on the products in our labs can mean increased confidence that really pays dividends in faster troubleshooting fewer callbacks Course descriptions and schedules are in our catalog CALL FOR FREE CATALOG 1 800 644 5544 Packaged Service Training Classroom Service Training Copyright 2007 Carrier Corp S 7310 W Morris St S Indianapolis IN 46231 Manufactur...

Reviews: