3
Protection
Built-in surge and transient protection for power and communications in
compliance with EN61000-6-1.
Incoming power and network connections are protected by non-replaceable
internal solid-state polyswitches that reset themselves when the condition that
causes a fault returns to normal.
The power and network connections are also protected against transient excess
voltage/surge events lasting no more than 10 msec.
CAUTION
To protect against large electrical surges on serial EIA-485
networks, place a PROT485 at each place wire enters or exits the building.
Status indicators
LED status indicators for EIA-485 CCN communication, Ethernet port
communication, and low battery status. Seven segment status display for
running, error, and power status.
Environmental operating
range
-20 to 140°F (-29 to 60°C), 10–90% relative humidity, non-condensing
NOTE i-Vu® Link must be mounted within the building envelope.
Storage temperature range
-24 to 140°F (-30 to 60°C), 0 to 90% relative humidity, non-condensing
Physical
Rugged aluminum cover, removable screw-type terminal blocks
Overall dimensions
A:
B:
7-1/2 in. (19.1 cm)
11-5/16 in. (28.7 cm)
Mounting dimensions
C:
D:
E:
F:
5 in. (12.7 cm)
10-7/8 in. (27.6 cm)
1-1/4 in. (3.2 cm)
1/4 in. (.6 cm)
Mount with 6-32 by 1/2 in. mounting screws
Depth
2-3/4 in. (7cm)
Weight
1.4 lbs (0.64 kg)
Listed by
UL916 (Canadian Std C22.2 No. 205-M1983, CE, FCC Part 15 - Subpart B -
Class A
Safety considerations
WARNING
Disconnect electrical power to the i-Vu® Link before wiring it. Failure to follow this warning could
cause electrical shock, personal injury, or damage to the controller.