background image

FX4D: Installation Instructions

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

9

A09391

Fig. 20 – Wiring Layout of Humidifier to Heat Pump

START-UP PROCEDURES

Refer  to  outdoor  unit  Installation  Instructions  for  system  start-up

instructions and refrigerant charging method details.

A09389

Fig. 21 – Wiring Layout of Humidifier to Fan Coil

with Electric Heat

CARE AND MAINTENANCE

To continue high performance and minimize possible equipment failure,

it is essential that periodic maintenance be performed on this equipment.

Consult  your  local  dealer  as  to  the  proper  frequency  of  maintenance

contract.
The ability to properly perform maintenance on this equipment requires

certain mechanical skills and tools. If you do not possess these, contact

your dealer for maintenance. The only consumer service recommended

or required is filter replacement or cleaning on a monthly basis.

CAUTION

!

PRODUCT DAMAGE HAZARD

Failure  to  follow  this  caution  may  result  in  poor  unit  performance

and/or product damage.
Never operate unit without a filter. Factory authorized filter kits may be

used  when  locating  the  filter  inside  the  unit.  For  those  applications

where access to an internal filter is impractical, a field-supplied filter

must be installed in the return air duct system.

R

G

C

E

L

O

Y

THERMOSTAT

R

R

C

O

Y

G

C

W

2

W

2

W

2

W

3

E

FAN COIL

HEAT PUMP

(CONTROL)

RED

GRY

BRN

WHT

WHT

BLU

VIO

HUMIDISTAT

RELAY

FAN HUMIDIFIER

115V

M

R

G

W

Y

THERMOSTAT

R

G

W

2

W

3

E

C

FAN COIL

C

Y

AIR COND.

HUMIDISTAT

FAN HUMIDIFIER

115V

RED

GRY

WHT

WHT

BLU

VIO

BRN

M

Table 2 – Air Delivery Performance Correction Component Pressure Drop (in. wc) at Indicated Airflow (Dry to Wet Coil)

FX

Size

CFM

500

600

700

800

900

1000

1100

1200

1300

1400

1500

1600

1700

1800

1900

2000

019

0.034

0.049

0.063

--

--

--

--

--

--

--

--

--

--

--

--

--

025

0.016

0.027

0.038

0.049

0.059

--

--

--

--

--

--

--

--

--

--

--

031

--

--

--

0.049

0.059

0.070

0.080

--

--

--

--

--

--

--

--

--

037

--

--

--

--

--

0.055

0.064

0.073

0.081

--

--

--

--

--

--

--

043

--

--

--

--

--

--

--

0.049

0.056

0.063

0.070

--

--

--

--

--

049

--

--

--

--

--

--

--

--

--

0.038

0.043

0.049

0.054

0.059

--

--

061

--

--

--

--

--

--

--

--

--

--

--

0.027

0.031

0.035

0.039

0.043

Table 3 – Factory-Installed Filter Static Pressure Drop (in. wc)

FX SIZE

CFM

400

600

800

1000

1200

1400

1600

1800

2000

019

0.020

0.044

0.075

-

-

-

-

-

-

025 - 031

-

0.022

0.048

0.072

0.100

-

-

-

-

037-049

-

-

-

0.051

0.070

0.092

0.120

0.152

-

061

-

-

-

-

-

-

0.086

0.105

0.130

Summary of Contents for FX4D 019

Page 1: ...quipped with an electric heater package For units not equipped with factory installed heat a factory approved field installed UL listed heater package is available from your equipment supplier See unit rating plate for a list of factory approved heaters Heaters that are not factory approved could cause damage which would not be covered under the equipment warranty If fan coil contains a factory in...

Page 2: ...asing flange 3 Remove coil assembly 4 Lay fan coil on its right side and reinstall coil assembly with condensate pan down See Fig 5 5 Attach coil to casing flange using previously removed coil mounting screw 6 Make sure pan cap in fitting door is properly seated on fitting door to retain low air leak rating of the unit 7 Add gaskets from kit KFAHD 8 Align holes with tubing connections and condensa...

Page 3: ...de coil assembly into casing Be sure coil bracket on each corner of vertical pan engages coil support rails 9 Reinstall 2 snap in clips to correctly position and secure coil assembly in unit Be sure clip with large offset is used on right side of unit to secure horizontal pan 10 Remove two oval fitting caps from left side of the coil access panel and fitting panel 11 Remove insulation knockouts on...

Page 4: ...to top of fan coil using No 10 self tapping screws Angle strap down and away from back of fan coil remove all slack and fasten to wall stud of structure using 5 16 lag screws Typically both sides of the fan coil b If fan coil is against wall secure fan coil to wall stud using 1 8 3mm wide right angle brackets Attach brackets to fan coil using No 10 self tapping screws and to wall stud using 5 16 l...

Page 5: ...ts with a factory installed disconnect with pull out removed service and maintenance can be safely performed on only the load side of the control package LINE VOLTAGE CONNECTIONS If unit contains an accessory electric heater remove and discard power plug from fan coil and connect male plug from heater to female plug from unit wiring harness See Electric Heater Installation Instructions For units w...

Page 6: ...HAOT0201SEC must be used A09387 Fig 13 Wiring Layout Heat Pump Unit Cooling and 2 Stage Heat with 2 Outdoor Thermostats A09388 Fig 14 Wiring Layout Heat Pump Unit Cooling and 2 Stage Heat for Manufactured Housing A05182 Fig 15 Transformer Connections R G W Y THERMOSTAT RED GRY WHT BLU VIO BRN WHT R G W2 W3 E C FAN COIL C Y AIR COND R G W Y THERMOSTAT R G W2 W3 E C FAN COIL C Y AIR COND RED GRY WHT...

Page 7: ...LOW CONTROL DEVICE The FX4D is equipped with PuronR refrigerant TXV Use outdoor units designed for PuronR refrigerant only CONDENSATE DRAINS To connect drains the cap openings must be removed Use a knife to start the opening near the tab and using pliers pull the tab to remove the disk Clean the edge of the opening if necessary and install the condensate line Finally caulk around the lines where t...

Page 8: ...gizes R to G R to Y and R to O heat pump only G energizes fan relay on PCB which completes circuit to indoor blower motor When G is de energized there is a 90 second delay before fan relay opens NOTE Speed taps 1 2 and 3 have a 90 second blower off delay Speed taps 4 and 5 have 0 second blower off delay HEAT PUMP HEATING WITH AUXILIARY ELECTRIC HEAT Thermostat energizes R to G R to Y and R to W G ...

Page 9: ... in poor unit performance and or product damage Never operate unit without a filter Factory authorized filter kits may be used when locating the filter inside the unit For those applications where access to an internal filter is impractical a field supplied filter must be installed in the return air duct system R G C E L O Y THERMOSTAT R R C O Y G C W2 W2 W2 W3 E FAN COIL HEAT PUMP CONTROL RED GRY...

Page 10: ... 02 2 8 10 0 3 9 15 0 3 9 15 02 4 20 02 4 20 04 6 18 24 30 10 Table 5 Airflow Performance CFM in Cooling Mode Model Size Blower Speed EXTERNAL STATIC in wc 0 10 0 20 0 30 0 40 0 50 0 60 FX4D 019 Tap 5 776 745 696 660 609 572 Tap 4 683 644 589 548 494 461 Tap 3 683 644 589 548 494 461 Tap 2 631 563 500 443 409 361 Tap 1 625 524 457 417 367 319 FX4D 025 Tap 5 956 920 891 851 816 780 Tap 4 825 795 75...

Reviews: