FSFXXAOA1180: Installation and User Instructions

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

6

Connecting the Insulated Ducts to the Unit

1. Slide the inner flexible duct over the port and tie it using a tie-wrap.
2. Pull  the  insulation  over  the  outer  ring  of  the  port  without

compressing it.

3. Use duct tape to seal the outer membrane of the insulated duct to

the outer ring of the port.

IMPORTANT: 

Avoid blocking the test ports with the duct tape.

A200598

NOTE: 

Make sure that the outdoor intake hood is easily accessible for

annual maintenance. If located above the first floor, place it close to a

window or balcony to allow ease of access.

WARNING

!

PERSONAL INJURY HAZARD

Make  sure  the  outdoor  intake  hood  is  at  least  12  inches  above  the

ground  and  6  feet  away  from  any  of  the  following:  Dryer  exhaust,

high-efficiency furnace vent, central vacuum vent, gas meter exhaust,

gas barbecue-grill, any exhaust from a combustion source, garbage bin

and any other source of contamination.

WARNING

!

PERSONAL INJURY HAZARD

Failure to follow this warning could result in personal injury or death.

Never  install  a  stale  air  exhaust  register  in  a  room  where  there  is  a

combustion  device,  such  as  a  gas  furnace,  a  gas  water  heater  or  a

fireplace. A negative pressure could be created in the area of the fuel

burning unit and draw carbon monoxide into the room. CO can cause

personal injury or death.

Summary of Contents for FSFXXAOA1180

Page 1: ...s used to highlight suggestions which will result in enhanced installation reliability or operation LIMITATION For residential domestic installation only Installation work and electrical wiring must b...

Page 2: ...act the manufacturer 2 Before servicing or cleaning this unit disconnect power cord from electrical outlet 3 This unit is not designed to provide combustion and or dilution air for fuel burning applia...

Page 3: ...F The in line heater shall have an integrated airflow sensor and an over temperature sensor to prevent heating in no flow or low flow conditions A200589 When deciding if a preheater is required and w...

Page 4: ...ll Control on p8 for the wiring diagram IMPORTANT Make sure that the wire seal foam is put back in place 10 Reinstall the electronic compartment cover make sure not to pinch wires and set the Mode and...

Page 5: ...kets on the unit as illustrated below DO NOT USE OTHER SCREWS 2 Using 4 screws no 10 12 x 0 625 in or longer screws if necessary secure the unit to the wall or ceiling into the studs joists or other s...

Page 6: ...ated above the first floor place it close to a window or balcony to allow ease of access WARNING PERSONAL INJURY HAZARD Make sure the outdoor intake hood is at least 12 inches above the ground and 6 f...

Page 7: ...A VE0450A K1 M1 Power Supply 12V Line Neutral Low Voltage 24VAC K2 R C G Gf PTC AC Line Filter J1 2 J4 7 J4 6 J4 4 J4 5 F1 High Voltage 120VAC J1 1 To J10 J2 1 J2 2 Power Supply 3 3V MCU K1 K2 M2 Step...

Page 8: ...5 Remove the test port cap located on the port on the intake side of the unit closest to the filter 6 Test the airflow using a Pitot tube The distance between the test port and VD0472 the center of th...

Page 9: ...ion standards and maintain a high standard of safety Any third party replacement part used may cause serious damage and drastically reduce the performance level of your unit which will result in prema...

Page 10: ...ing but was in a standby period This Supply Fan is designed to provide fresh air at the best me of the day Is the unit connected to a working wall outlet Use a small electric appliance to test the out...

Page 11: ...e damper does not move within 15 seconds replace the electronic board If the damper now works replace it Wall control error 4 blinks There is a short circuit in the wall control wiring Inspect wiring...

Page 12: ...A A200609 VN0011A Selected mode Climatic Zones 1 Ashrae 2016 Zones 1 4 2 Ashrae 2010 factory setting Zones 1 4 3 IRC IMC 2012 2015 Zones 1 4 A Comfort mode Hot Humid 1 Zones 2A and 1 B Comfort mode Ho...

Page 13: ...FSFXXAOA1180 Installation and User Instructions Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 13 APPENDIX B A200610...

Page 14: ...Company Edition Date 12 20 Catalog No IM FSF 01 Replaces New FSFXXAOA1180 Installation and User Instructions Manufacturer reserves the right to change at any time specifications and designs without n...