FSFXXAOA1180: Installation and User Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
4
Grayed out values are the recommended settings and should be preferred.
7. Remove the screw holding the electronic compartment cover, as well as the cover itself.
8. Set the Speed Switch to 130 CFM or 180 CFM, according to the settings chosen in step 6. The unit is factory set to 130 CFM.
A200590
9. Using the terminal block located on the electronic board, perform the low voltage connection
. Connection to a
low voltage power source is mandatory.
• Make sure that the polarity of the connections is respected.
• Pay special attention to the sensor located above the terminal block and the potentiometer buttons on the electronic board; they are very fragile,
do not damage them while performing the connections.
• Run the low voltage wires along with the other wires all the way to the hole and grommet in the housing, where the low voltage wires should
exit. Make sure that the wire seal foam is reinstalled.
NOTE:
If the unit is to be connected to a supply fan optional wall control, the low voltage wire should be connected to the terminal block now. Refer
to
(Connection to the Supply Fan Optional Wall Control on p8)
IMPORTANT:
Make sure that the wire seal foam is put back in place.
10. Reinstall the electronic compartment cover (make sure not to pinch wires), and set the Mode and Run time % buttons according to the settings
previously chosen.
A200591
11. Reinstall the main filter in the unit.
NOTE:
An optional MERV filter may be installed now. The main filter should remain as a prefilter, and the MERV filter should be installed as
indicated above.
Mounting the Unit
NOTE:
When choosing a location for this unit, keep in mind that maintenance will have to be performed by the end user on a regular basis. Choose an
easily accessible location and plan for a 14¼-in. clearance for the door to open.
Table 1 – Run Time % According to Speed Setting and Required Airflow
Required Airflow (CFM)
Speed Setting
30
35
40
45
50
55
60
65
70
75
80
85
90
95
100
105
130 CFM
25
30
30
35
40
40
45
50
55
60
60
65
70
75
80
80
180 CFM
20
20
20
25
30
30
35
35
40
40
45
50
50
55
55
60
Run time % button value
Required Airflow (CFM)
Speed Setting
110
115
120
125
130
135
140
145
150
155
160
165
170
175
180
130 CFM
85
90
90
95
100
–
–
–
–
–
–
–
–
–
–
180 CFM
60
65
70
70
70
75
80
80
85
85
70
90
95
95
100
Run time % button value
Sensor
Terminal
block
Speed
switch
Mode &
run time
settings
130 CFM (Low Speed)
180 CFM (High Speed)
MERV Filter
Main Filter
Refer to the manual for more details.
Test
20
30
40
50
60
70
80
90
100
MODE
RUN
TIME %
1
2
3
A
B
C
D
E
on the electronic board
SPEED SWITCH
130 CF
M
180
CF
M
AIRFLOW DIRECTION