FSFXXAOA1180: Installation and User Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
11
All Units Troubleshooting
A200608
LED Blinking Codes
Sensor Error
1 blink
Damper Error
2 blinks
Wall Control Error
4 blinks
Filter Maintenance
Slow blink (2 s ON, 2 s OFF)
Learning Mode
Very slow blink (1 s ON, 10 s OFF)
Sensor error
1 blink
Replace the electronic
board.
Damper error
2 blinks
Perform a visual
inspecon. Is
there an
obstacle
hindering
damper
movement?
Are the damper
wires in good
condion and well
connected to the J5
connector on the
electronic board?
Remove the obstacle. Restore
power to the unit, note down
the Runme % seng, and
turn it to "Test". The damper
should now work normally.
Put the Run me % back to its
previous value.
Restore the connecons or, if
the wires are damaged,
replace the damper. Restore
power to the unit, note down
the Run me % seng, and
turn it to "Test". The damper
should now work normally.
Put the Run me % back to its
previous value.
Try connecng an other damper to the board
(without completely installing it). Restore power
to the unit, note down the Runme % seng,
and turn it to "Test". If the damper does not
move within 15 seconds, replace the electronic
board. If the damper now works, replace it.
Wall control
error
4 blinks
There is a short circuit in the wall
control wiring. Inspect wiring at the
wall control and on the terminal
block. Restore any connecon that
may be causing a short circuit. Is
the problem fixed?
The wall control
may be
damaged. Test
using an other
wall control.
Test the wall
control using a
new wire. Is
the problem
fixed?
Wall control does
not work
Inspect the connecons at
the control and at the
terminal block. Restore any
wrong connecon.
Is the problem fixed?
If there is no short,
the wall control may
be damaged. Test
using an other wall
control.
Test the wall
control using a
new wire. Is
the problem
fixed?
Learning mode
Very slow blink
During the first 48 hours of operaon, the unit is gathering environmental
data.
This can be triggered by a change of seng, a power shortage, or powering
unit back. This blinking code is not an error.
Unit does not
provide the
required airflow
Are filter(s) grille,
and/or hood
clogged?
Are the speed
switches on the
board properly
posionned?
Is the measuring tool
accurate? Try using a
different tool.
You are not sure
that your venlaon
needs are met.
Review the Speed, Mode
and Runme % sengs.
Refer to Secon 3.
Verify the W and Y
connecons.
YES
NO
NO
YES
NO
NO
NO
NO
Perform
maintenance.
Refer to Secon 3.
Calibrate tool.
YES
NO
NO
YES
NO