8

SELECT LOCATION FOR THE AIR CLEANER

DIRECTION OF AIR FLOW THROUGH THE AIR CLEANER

PHYSICAL INSTALLATION

Select a location that is readily accessible for periodic inspection and

cleaning. Allow a minimum of 26" in front of the access panel for filter

removal. For complete dimensions required, refer to the section entitled

The air cleaner is set up for left to right air flow, when facing the access

door. For right to left air flow remove filter cartridge, turn it around and

replace in cabinet. The directional arrows on the filter cartridge must

point in the direction of air flow.

The air cleaner can be in any position, except with the access door

facing down. The section entitled

(page 5) shows proper air cleaner mounting with a variety of furnace

installations.

Prior to installing this product...

1. Read rules and instructions carefully for safe operation. Failure to

follow them could damage the product or cause a hazardous

condition.

2. Check the ratings given on the product to make sure it is suitable for

your application.

3. Remove the old furnace filter and discard.

4. The air cleaner cannot remove existing dirt from the blower and

ducts.

SPECIFICATIONS.

TYPICAL MOUNTING POSITIONS

Summary of Contents for EZXCAB-0016

Page 1: ...EZXCAB High Efficiency Air Filtration System Manual for Installation Operation Maintenance EZXCAB 0016 0020 Form Number EZCB 1SI IIEZCB 16 1 07 02 ...

Page 2: ...jury Understand the signal words DANGER WARNING and CAUTION These words are used with the safety alert symbol DANGER identifies the most serious hazards which result in severe personal injury or death WARNING signifies hazards which result in personal injury or death CAUTION is used to identify unsafe practices which result in minor personal injury or product and property damage The Model EZXCAB H...

Page 3: ...2 C02027 1 2 3 4 5 Figure 1 1 Cabinet Top 2 Filter Media 3 Access Handle 4 Access Door 5 Cabinet ...

Page 4: ...21 2 9 16 247 8 7 1 4 SPECIFICATIONS Dimensions Model Number Air Flow CFM Range 600 1600 600 2000 A 16 3 8 20 3 8 B 13 3 8 17 3 8 Replacement 3 12 months between changes Media Filter UL Class 2 EZXCAB 0016 EZXCAB 0020 ...

Page 5: ...4 Typical Pressure Drop EZXCAB 0016 EZXCAB 0020 Resistance In w c 600 04 03 800 07 04 1000 10 06 1200 14 08 1400 18 11 1600 23 13 1800 17 2000 18 Model Number Air Flow CFM AIR FLOW RESISTANCE ...

Page 6: ...etween the duct and the furnace move the return air drop SPACE SAVER HIGHBOY Installation beneath furnace Cleaner mounts horizontally where return air enters from below Raise furnace by installing a suitable wood structure and install air cleaner HORIZONTAL FURNACE Mounted vertically in return duct as close to the furnace as possible AIR FLOW MEDIA AIR CLEANER SHEET METAL TRANSITIONS AIR FLOW MEDI...

Page 7: ...air cleaner consider the application If a transition is required refer to section entitled The unit must be readily accessible for periodic inspection and replacement of media cartridge to maintain maximum efficiency and trouble free operation The air cleaner should be installed upstream of the cooling coil This will keep the coil clean and reduce air conditioning coil maintenance Improved cooling...

Page 8: ... the air cleaner Figure 3 Humidifiers Location of the system humidifier is important to the operation of the air cleaner When an evaporative type humidifier is used it may be installed between the furnace warm air duct and the return air duct without effecting the air cleaner Atomizing and spray type humidifiers should be installed upstream of the air cleaner ...

Page 9: ...et The directional arrows on the filter cartridge must point in the direction of air flow The air cleaner can be in any position except with the access door facing down The section entitled page 5 shows proper air cleaner mounting with a variety of furnace installations Prior to installing this product 1 Read rules and instructions carefully for safe operation Failure to follow them could damage t...

Page 10: ...gure 2 6 Mounting holes are provided for simple connection to duct work The 140 holes are sized for 8 sheet metal screws or 1 8 rivets If the adjoining duct work is flanged install the screws so that the screw heads are inside the cabinet This will prevent damage to the filter cartridge during removal and installation Figure 4 7 Remove media filter cartridge from plastic bag and replace media filt...

Page 11: ... 2 Pull used filter straight out of cabinet and disassemble and discard 3 Remove new filter cartridge from box and assemble 4 Slide new filter cartridge into cabinet with AIR FLOW arrow pointing in the direction of air flow 5 Replace door Remember periodic inspection and annual replacement of your filter will insure high efficiency air cleaning Contact your HVAC dealer for replacement filter cartr...

Page 12: ... MAY NOT BE ALTERED ENLARGED OR CHANGED BY ANY DISTRIBUTOR DEALER OR OTHER PERSON WHATSOEVER ALL WORK UNDER THE TERMS OF THIS WARRANTY SHALL BE PERFORMED DURING NORMAL WORKING HOURS ALL REPLACEMENT PARTS WHETHER NEW OR REMANUFACTURED ASSUME AS THEIR WARRANTY PERIOD ONLY THE REMAINING TIME PERIOD OF THIS WARRANTY 1 Normal maintenance as outlined in the installation and servicing instructions or own...

Reviews: