background image

EVD4X, ESD4X, WMVC, WMSC: Installation Instructions

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

6

3. Remove fitting  door  with rubber grommets and slide fitting  door

with grommets onto the refrigerant lines (field line-set), away from

braze joints.

4. Fit  refrigerant  lines  into  coil  stubs. Wrap  a  heat sinking  material

such as a wet cloth behind braze joints.

5. Wrap TXV and nearby tubing with a heat-sinking material such as a

wet cloth.

6. Use 1/2 psig Nitrogen purge in the suction and out the liquid line.
7. Braze using a Sil-Fos or Phos-copper alloy. Do not use soft solder.
8. After  brazing,  allow  joints  to  cool.  Carefully  remove  TXV  bulb

insulation and verify that the TXV bulb is securely fastened with

hose  clamp. Tighten  screw  a  half-turn  past hand  tight  with TXV

bulb placed in the indentation with full contact with the vapor line

tube. Re-wrap TXV bulb with insulation. 

9. Leak check connections before insulating entire suction line.
10. Slide fitting door with rubber grommets over joints. Position tubing

at center  of each  grommet to ensure  an air  seal around  the tube.

Reinstall cabinet door.

Refrigerant Metering Device

These Coils have a factory installed hard shut-off TXV designed only for

use with R-410A refrigerant. Use only with outdoor units designed for

R-410A.

NOTE: 

These  TXVs  are  factory  set  at  approximately  10°  superheat

measured at the suction service valve, and are 

not

 field adjustable.

These  furnace  coils  use  an  R410A TXV. The TXVs  are  preset  at  the

factory and do not need adjustment for reliable operation. Reference the

outdoor  unit  instructions  to  properly  charge  the  unit  to  the  correct

subcooling.  Let  the  system  stable  out  approximately  15  minutes  after

each charge adjustment.

Condensate Drain Line Connection

The coil is  designed to  dispose of  accumulated water  through  built-in

condensate drain fittings. It is recommended that PVC fittings be used

on the  condensate  pan.  Do  not  over-tighten.  Finger tighten  plus  1-1/2

turns. 

Be sure to install PVC plugs in all unused condensate drain

fittings  (if  not  factory  supplied).

  Four  ¾-inch  female  threaded  pipe

connections are provided in each coil condensate pan.
It  is  highly  RECCOMMENDED  and  in  some  locals  is  it  a  code

requirement to install a trap on the drain line(s). Please use the following

guidelines to assure proper drainage:
• Install a trap in condensate line of coil as close to the coil as possible.

• Make  trap  at  least  3  inches  (76  mm)  deep  and  no  higher  than  the

bottom of unit condensate drain opening (

Fig. 8

).

• Pitch condensate line 1 inch (25.4 mm) for every 10 ft. of length to an

open drain or sump.

• Make  sure  that  the  outlet  of  each  trap  is  below  its  connection  to

condensate pan to prevent condensate from overflowing the drain pan.

• Prime all traps, test for leaks, and insulate traps and lines if located

above a living area.

A200230C

Fig. 8 – Condensate Trap

NOTE: 

If unit is located in or above a living space, where damage may

result from condensate overflow, a field-supplied, external condensate

pan  should  be  installed  underneath  the  entire  unit,  and  a  secondary

CAUTION

!

UNIT DAMAGE HAZARD

Failure to follow this caution may result in damage.
All aluminum tubing and coils must be adequately shielded from any

copper braze splatter.

CAUTION

!

UNIT DAMAGE HAZARD

Failure to follow this caution may result in product damage.
To avoid valve damage to the refrigerant control device while brazing,

valves  must  be  wrapped  with  a  heat-sinking  material  such  as  a  wet

cloth.

CAUTION

!

UNIT DAMAGE HAZARD

Failure to follow this caution may result in product damage.
DO NOT BURY MORE THAN 36 IN. OF REFRIGERANT TUBING

IN GROUND. If any section of tubing is buried, there must be a 6-in.

vertical rise to the valve connections on the outdoor unit. If more than

the recommended  length  is buried,  refrigerant may migrate  to cooler

buried  section  during  extended  periods  of  unit  shutdown,  causing

refrigerant slugging and possible compressor damage at start-up.

CAUTION

!

PROPERTY DAMAGE HAZARD

Failure to follow this caution may result in property damage.
It is required that all drain connections that are not being used be fitted

with ¾-inch male PVC plugs.
When  installing  over  a  finished  ceiling  and/or  living  area,  install  a

field-fabricated secondary condensate pan under the entire unit.

CAUTION

!

PROPERTY DAMAGE HAZARD

Failure to follow this warning could result in

property damage.

Provide  trap  with  air gap  in  drain  line when

connecting to waste (sewer) line.

3

 (76mm)

Ø1

 (25.4) 

KNOCK-OUT 

(IF PRESENT)

SECONDARY DRAIN PORT 

(IF PRESENT)

PRIMARY DRAIN PORT (IF PRESENT)

¾

 (19.05) NPT DRAIN x 4

Summary of Contents for EVD4X

Page 1: ...ath CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage NOTE is used to highlight suggestions which will result in enhanced installati...

Page 2: ...refrigerant Use only with outdoor units designed for R 410A NOTE These TXVs are factory set at approximately 10 superheat measured at the suction service valve and are not field adjustable A210138 Fi...

Page 3: ...he factory installed foil faced insulation in the front and rear of the coil are required to prevent bypass airflow Heat shields for the condensate drain pan in upflow installations and cross members...

Page 4: ...sted and therefore full performance specifications have not been certified In instances where a not recommended installation configuration is required it is the responsibility of the installer to ensu...

Page 5: ...using field supplied tubing of refrigerant grade Always evacuate tubing and reclaim refrigerant when making connections or flaring tubing Leak check connections before insulating entire suction line S...

Page 6: ...n It is highly RECCOMMENDED and in some locals is it a code requirement to install a trap on the drain line s Please use the following guidelines to assure proper drainage Install a trap in condensate...

Page 7: ...is to be connected to a waste sewer line an open trap must be installed ahead of the waste line to prevent escape of sewer gases Fig 9 Humidifier Application When installing a humidifier in a system...

Reviews: