background image

EVD4X, ESD4X, WMVC, WMSC: Installation Instructions

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

5

A221110

Fig. 6 – 90° Rotation (shown in downflow)

4" Transition Required (not recommended)

A221111

Fig. 7 – 180° Rotation (shown in upflow)

(not recommended)

Downflow Coil Installation

NOTE: 

In downflow installation with a 4-way multipoise furnace, break

off  perforated  duct  flanges  on  furnace.  See  furnace  Installation

Instructions.

Refrigerant Line Connections

NOTE: 

Factory nitrogen charge  may  escape  past rubber  plugs during

storage. This does not indicate a leaking coil nor warrant return of the

coil.
Size and install refrigerant lines according to information provided with

outdoor  unit.  Coil  connection  tube  sizes  are  shown  in 

Table 1

.  Route

refrigerant  lines  to  the  coil  in  a  manner  that  will  not  obstruct  service

access to the unit or removal of the filter.
Do not use damaged, dirty, or contaminated tubing because it may plug

refrigerant  flow-control  device.  ALWAYS  evacuate  the  coil  and

field-supplied tubing before opening outdoor unit service valves.

Connect Refrigerant, Liquid, and Suction Lines

For matched and mismatched systems, use line sizes recommended in

outdoor unit Installation Instructions.

The coil can be connected to outdoor units using field-supplied tubing of

refrigerant grade. Always evacuate tubing and reclaim refrigerant when

making  connections  or  flaring  tubing.  Leak  check  connections  before

insulating entire suction line.
See 

Table 1

 for coil connection tube size.

1. Remove cabinet access door.
2. Remove rubber plugs, suction plug then liquid plug, from coil stubs

using a pulling and twisting motion. Hold coil stubs steady to avoid

bending or distorting.

4”  Transition

Required

Front of Coil

Front of 
Furnace

CAUTION

!

WATER MANAGEMENT HAZARD

Failure  to  follow  this  caution  could  cause  product  and/or  property

damage.
The  furnace  coil door  must be properly  installed  when the  coil  is in

operation. To ensure proper  condensate water  management,  the  drain

pan must not touch the coil. When properly installed the furnace coil

door will correctly align the condensate pan with the coil.

WARNING

!

PERSONAL INJURY HAZARD

Failure to follow this warning could result in personal injury.

Wear eye  protection.  Coil  is  factory  charged  with 7–10  psi nitrogen.

The coil is under pressure and TXV screen is in place behind liquid line

plug. DO NOT remove liquid line plug first, always remove the suction

line plug first to depressurize the coil.

CAUTION

!

UNIT OR PROPERTY DAMAGE HAZARD

Failure to follow this caution may result in property damage.
Take  precautions  to  ensure Aluminum  tubes  do  not  come  in  direct

contact  or  allow  for  condensate  run  off  with  a  dissimilar  metal.

Dissimilar metals can cause galvanic corrosion and possible premature

failure.

Summary of Contents for EVD4X

Page 1: ...ath CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage NOTE is used to highlight suggestions which will result in enhanced installati...

Page 2: ...refrigerant Use only with outdoor units designed for R 410A NOTE These TXVs are factory set at approximately 10 superheat measured at the suction service valve and are not field adjustable A210138 Fi...

Page 3: ...he factory installed foil faced insulation in the front and rear of the coil are required to prevent bypass airflow Heat shields for the condensate drain pan in upflow installations and cross members...

Page 4: ...sted and therefore full performance specifications have not been certified In instances where a not recommended installation configuration is required it is the responsibility of the installer to ensu...

Page 5: ...using field supplied tubing of refrigerant grade Always evacuate tubing and reclaim refrigerant when making connections or flaring tubing Leak check connections before insulating entire suction line S...

Page 6: ...n It is highly RECCOMMENDED and in some locals is it a code requirement to install a trap on the drain line s Please use the following guidelines to assure proper drainage Install a trap in condensate...

Page 7: ...is to be connected to a waste sewer line an open trap must be installed ahead of the waste line to prevent escape of sewer gases Fig 9 Humidifier Application When installing a humidifier in a system...

Reviews: