Using the Equipment Touch's temperature and humidity sensors to control equipment
Equipment Touch
CARRIER CORPORATION ©2019
Installation and Setup Guide
All rights reserved
19
To set up the sensors on the Equipment Touch
Go to
Setup
>
Touchscreen Setup
>
Sensor Setup
.
On this screen, you can:
•
Select the temperature sensor
—You can use values from the Equipment Touch's internal temperature
sensor. Or, you can wire an external (remote) thermistor to the Equipment Touch and use its temperature
value instead of the internal temperature sensor's value.
NOTE
The
Deg F
and
Deg C
setting is determined by the controller's control program.
•
Disable transmission of the temperature and humidity
—See NOTE below.
•
Set an offset
—Enter a correct temperature/humidity value to create an offset for all future values.
To use the temperature or humidity value in a control program
1
In Snap, place a BACnet Analog Value Parameter microblock
in your control program.
2
Enable the
Network Visible
field.
3
In the
Object Instance
field, select
Use specific value
, then enter one of the following:
1902 for Temperature
1904 for Humidity
NOTE
By default, the Equipment Touch transmits its temperature value (av: 1902, writes every 1 minute) and
relative humidity value (av: 1904, writes every 5 minutes). If the 1902 or 1904 object instance numbers are
to be used in a different manner, you can turn off the transmission of the temperature and humidity values.
See
To edit touchscreen settings
(page 21).
To display the temperature or humidity value on a custom screen
In ViewBuilder, add a Primary Value or Number control to the screen, and then set the
Path To Microblock
Using the Equipment Touch's temperature and humidity sensors to
control equipment