Wiring and mounting the Equipment Touch
Equipment Touch
CARRIER CORPORATION ©2019
Installation and Setup Guide
All rights reserved
15
•
Wire the Equipment Touch in a daisy-chain configuration with up to 5 ZS zone sensors as shown below.
NOTE
You do not need to set an address for the Equipment Touch.
Wiring specifications
Power wiring
2-conductor wire 18 AWG for distances up to 100 feet. All transformer secondaries must be grounded. Wiring
connections must be in accordance with NEC and local codes.
Rnet wiring
NOTE
If you wire the Equipment Touch directly to the controller's Rnet port, you can use a 2-conductor cable
instead of the standard 4-conductor Rnet cable.
Description
4-conductor, shielded or unshielded, CMP, plenum rated cable
Conductor
22 AWG (7x0096) bare copper
Maximum length
500 feet (152 meters)
Insulation
Low-smoke PVC (or equivalent)
Color Code
Black, white, green, red
Shielding
If shielded, Aluminum/Mylar shield (100% coverage) with TC drain wire
UL temperature rating
32–167°F (0–75°C)
Voltage
300 Vac, power limited
Listing
UL: NEC CL2P, or better