Wiring and mounting the Equipment Touch
Equipment Touch
CARRIER CORPORATION ©2019
Installation and Setup Guide
All rights reserved
14
CAUTION
If the equipment is used in a manner not specified by the manufacturer, the protection provided
by the equipment may be impaired.
Mounting
The Equipment Touch must be mounted within the building interior. You can mount the Equipment Touch:
•
In a panel with the controller or on the panel door
•
On a wall up to 500 feet from the controller
Wiring
•
The Equipment Touch requires a 24 Vac power supply. It is not powered by the Rnet.
CAUTION
The Equipment Touch can share a power supply with the Carrier controller as long as you:
○
Maintain the same polarity.
○
User the power supply only for Carrier controllers.
•
You can also wire an external 10 kOhm, Type II thermistor (Carrier part number 33ZCT55SPT) to the
Equipment Touch. See
Appendix: External sensor resistance requirements
(page 26).
See:
Wiring specifications
(page 15)
To wire and mount the Equipment Touch
(page 16)
Wire the Equipment Touch in one of the following ways:
•
Wire the Equipment Touch directly to the controller's Rnet port as shown below.
Wiring and mounting the Equipment Touch