4

Table 5 – Electric Heater Electrical Data for PSC Motor Units

Heat

Kit

Model

Used

on

Size

Nominal

Heat

Capacity

@ 240V

Ship-

ping

Weight

Heater

Capacity

(MBH)

Minimum

Circuit

Ampacity

(MCA)

MAX. Fuse

or Breaker

Heat---Kit

Ampacity

(HACR)

Min Wire

Size

(AWG) ††

Min Ground

Wire Size

Max Wire

Length (Ft)

‡‡

KW

lbs. (kg) 208

240

208

240

208

240

208

240

208

240

208

240

EHK2-05B

1---1/2

Ton

5

5.1 (2.3)

12.3

16.4

23.6

27.1

30

30

10

10

10

10

73

74

EHK2-08B

7.5

22.2

25.6

34.9

40.1

50

50

8

8

10

10

76

77

EHK2-10B

10

24.6

32.8

46.2

53.1

60

60

6

6

10

10

92

92

EHK2-05B

2

Ton

5

5.1 (2.3)

12.3

16.4

23.9

27.3

30

30

10

10

10

10

73

73

EHK2-08B

7.5

22.2

25.6

35.2

40.4

50

50

8

8

10

10

76

76

EHK2-10B

10

24.6

32.8

46.4

53.4

60

60

6

6

10

10

91

92

EHK2-05B

2---1/2

Ton

5

5.1 (2.3)

12.3

16.4

24.2

27.7

30

30

10

10

10

10

72

72

EHK2-08B

7.5

22.2

25.6

35.5

40.7

50

50

8

8

10

10

75

76

EHK2-10B

10

24.6

32.8

46.8

53.7

60

60

6

6

10

10

91

91

EHK2-05B

3

Ton

5

5.1 (2.3)

12.3

16.4

24.9

28.3

30

30

10

10

10

10

70

71

EHK2-08B

7.5

22.2

25.6

36.2

41.4

50

50

8

8

10

10

74

74

EHK2-10B

10

24.6

32.8

47.4

54.4

60

60

6

6

10

10

90

90

* †† Copper wire must be used. If other than uncoated (non---plated), 75

_

C ambient, copper wire (solid wire for 10 AWG and smaller, stranded wire for larger

than 10 AWG) is used, consult applicable tables of the National electric Code (ANSI/NGPA 70).

* ‡‡ Length shown is as measured 1 way along wire path between unit and service panel for a voltage drop not to exceed 2%.

Table 6 – Electric Heater Electrical Data for ECM Motor Units

Heat

Kit

Model

Used

on

Size

Nominal

Heat

Capacity

@ 240V

Ship-

ping

Weight

Heater

Capacity

(MBH)

Minimum

Circuit

Ampacity

(MCA)

MAX. Fuse

or Breaker

Heat---Kit

Ampacity

(HACR)

Min Wire

Size

(AWG) ††

Min Ground

Wire Size

Max Wire

Length (Ft)

‡‡

KW

lbs. (kg) 208

240

208

240

208

240

208

240

208

240

208

240

EHK2-05B

1---1/2

Ton

5

5.1 (2.3)

12.3

16.4

25

28.5

30

30

10

10

10

10

69

70

EHK2-08B

7.5

22.2

25.6

36.3

41.5

50

50

8

8

10

10

73

74

EHK2-10B

10

24.6

32.8

47.6

54.5

60

60

6

6

10

10

89

90

EHK2-05B

2

Ton

5

5.1 (2.3)

12.3

16.4

25

28.5

30

30

10

10

10

10

69

70

EHK2-08B

7.5

22.2

25.6

36.3

41.5

50

50

8

8

10

10

73

74

EHK2-10B

10

24.6

32.8

47.6

54.5

60

60

6

6

10

10

89

90

EHK2-05B

2---1/2

Ton

5

5.1 (2.3)

12.3

16.4

26

29.5

30

30

10

10

10

10

67

68

EHK2-08B

7.5

22.2

25.6

37.3

42.5

50

50

8

8

10

10

71

72

EHK2-10B

10

24.6

32.8

48.6

55.5

60

60

6

6

10

10

87

88

EHK2-05B

3

Ton

5

5.1 (2.3)

12.3

16.4

26

29.5

30

30

10

10

10

10

67

68

EHK2-08B

7.5

22.2

25.6

37.3

42.5

50

50

8

8

10

10

71

72

EHK2-10B

10

24.6

32.8

48.6

55.5

60

60

6

6

10

10

87

88

* †† Copper wire must be used. If other than uncoated (non---plated), 75

_

C ambient, copper wire (solid wire for 10 AWG and smaller, stranded wire for larger

than 10 AWG) is used, consult applicable tables of the National electric Code (ANSI/NGPA 70).

* ‡‡ Length shown is as measured 1 way along wire path between unit and service panel for a voltage drop not to exceed 2%.

Copyright 2014 CAC / BDP / ICP

D

7310 W. Morris St.

D

Indianapolis, IN 46231

Edition Date: 01/14

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

Catalog No: AG---EHK2---04