Fan Speeds

Before operating unit, be sure that the proper blower speed has

been selected. Fan speeds are selected manually. (See Table 3)

NOTE

:

The low fan speed tap should not be used for

simultaneous heat pump and electric heat applications. Always
ensure the minimum CFM shown in Table 2 is met.

To change the fan speed on fan coils with PSC motors

:

The factory default is medium speed. To select the desired fan
speed for cooling, simultaneous heat pump and electric heat

operation, and anytime a “G” signal is present; connect the desired
fan motor speed tap wire to Fan Relay Terminal No. 4.

To select the desired fan speed for heating operation, anytime the

“G” signal is not present; connect the desired fan motor speed tap
wire to Fan Relay Terminal No. 6.
Always connect the unused fan--motor wire to the dummy terminal
block. The factory default for electric heat only operation is low

speed.

Table 3 – Color Code for PSC Motor Lead Wires

MOTOR SPEED TAP

WIRE COLOR

Common

Purple

High

Black

Medium

Red

Low

Blue

To change the fan speed on fan coils equipped with multi--tap

ECM motors:

Fan speeds are selected manually (See Table 4). At the motor

connection plug (See Fig. 3) connect the green wire to the desired

motor tap number indicated on the motor plug. For the electric heat
fan speed selection connect the white wire to the desired motor tap

number indicated on the motor plug.

1   2   3   4   5

Speed Taps may be located on motor,
or on plug close to motor.

CL

G

N

1   2   3   4   5

A11048

Fig. 3 -- ECM Motor Speed Taps

Table 4 – ECM Motor Speed Taps

Tap

Delay---

off

Time (s)

19

25

31

37

Tap 1

30

---

---

---

---

Tap 2

90

Default

---

Default

---

Tap 3

30

---

---

---

---

Tap 4

90

---

Default

---

Default

Tap 5

30

---

---

---

---

*The defaults shown are for cooling and simultaneous heat---pump / electric---
heat operation.

Transformer

All units are shipped from factory wired for 240VAC transformer
operation. For 208VAC operation, move primary lead from

240VAC terminal to 208VAC terminal, see Fig. 4.

240

COM

208

BLK
YEL

BLK
RED

SECONDARY

PRIMARY

A13092

Fig. 4 -- Connection of Transformer

VERIFY INSTALLATION

After completion of heater installation, check wiring to ensure
tightness and that proper connections and routings have been

made. Ensure all electrical covers are in place. Reinstall blower

access panel before turning unit power on.