Table 1 – Accessory Heater Usage

ELECTRIC HEATER PART NUMBER

SIZES USED WITH

kW

INTERNAL CIRCUIT PROTECTION

EHK2-05B

18-37

5

Circuit Breaker

EHK2-08B

18-37

7.5

Circuit Breaker

EHK2-10B

18-37

10

Circuit Breaker

Table 2 – Minimum CFM

Fan Coil Unit Size

EHK2-05B

EHK2-08B

EHK2-10B

18, 19

325

350

375

24, 25

450

475

500

30, 31

575

600

625

36, 37

700

725

750

Heater 

assembly 

locations

Breaker box 

locations

Unit sizes 18-25

Unit sizes 31-37

(Top View)

(Top View)

(Front View)

(Front View)

A13365

Fig. 1 -- Installation Locations for EHK2 Heaters

Ground

Lug

Field

Power

Wiring

Field

Ground

Wiring

ON

OFF

L1

L2

A00077

Fig. 2 -- 5--kW, 7.5--kW, 10--kW Circuit Breaker

and Disconnect Heaters

Ground Connections

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury

or death.
According to NEC, ANSI/NFPA 70, and local codes, cabinet

must have an uninterrupted or unbroken ground to minimize

personal injury if an electrical fault should occur. The ground

may consist of electrical wire or metal conduit when installed

in accordance with existing electrical codes. (See

Ground/Conduit Note below.)

!

WARNING

NOTE

:

Use UL--listed conduit and conduit connector for

connecting supply wire(s) to unit to obtain proper grounding. If
conduit connection uses reducing washers, a separate ground wire
must be used. Grounding may also be accomplished by using
grounding lugs provided in control box.