background image

10

Fig. 12 for outdoor temperature/indoor humidity relationship in

auto humidification mode.
Humidification Off — The humidification function can be

turned off completely. This does not require changing existing

set points.
To Select Humidification — Press the softkey below the hu-

midification icon to bring up humidity select screen. Humidifi-

cation options are only available when in Heating mode. When

system is in AUTO mode, humidification options are available

if the last system operation was a call for heat.

The humidifier is actually turned on when humidity is 1%

below set point and turned off when it reaches 4% above set

point. This built-in hysteresis prevents humidification output

from toggling on and off when humidity level is near the set

point.
DEHUMIDIFICATION — Dehumidification is done only

during cooling. Depending on type of equipment used, com-

pressor speed, fan speed, set point adjustment, and equipment

cycling are modified to provide added dehumidification. A de-

humidification set point (separate from humidification set

point) is available to the user. It can range from 46% to 98%

relative humidity.

When actual humidity is higher than the set point, a dehu-

midification demand exists. The thermostat responds by acti-

vating the dry contacts (D1/D2 when enabled in Option 19).

The thermostat may also control the compressor and fan, de-

pending on equipment type and dehumidification selection

choice. The 3 available selections are described below. A man-

datory 30-second fan off delay will be enforced if there has

been a call for dehumidification during a cooling call. The

amount of extra dehumidification available is very dependent

on the type of equipment. Without a variable-speed fan, the

system’s ability to adjust dehumidification is very limited.
Normal Dehumidification Operation — When normal dehu-

midification is selected, the compressor will not turn on with-

out a cooling demand. If dehumidification demand exists while

cooling, dry contact will also be active. This output commands

variable-speed fans to reduce their airflow, which improves

water removal from the cooled air.
Cool to Dehumidification — The cool to dehumidification se-

lection tells the system to operate the compressor, within limits,

when there is a dehumidification demand even if there is no

cooling demand. The limits are that the system may overcool

up to 3 F, but no more, while attempting to satisfy a dehumidi-

fication demand. Within this 3 F range, there is an additional

balance between overcooling and humidity satisfaction.

When overcooling must occur, the dehumidification set

point is adjusted upward by 2% per degree of overcooling. For

example, a cooling set point of 76 F and a dehumidification set

point of 60% is equivalent to a cooling set point of 75 F and a

dehumidification set point of 62%. This dehumidification set

point change is internal to the thermostat and is not shown on

the display. See Fig. 12.

Fig. 12 —

 

Auto Humidification

Dehumidification Off — Dehumidification can be turned off

completely. This can be done without changing existing set

points.
To Select Dehumidification — Press the softkey below the

dehumidification icon button to bring up dehumidification se-

lections. Dehumidification options are only available when in

Cooling mode. When system is in AUTO mode, dehumidifica-

tion options are available if the last system operation was a call

for cooling.

If FAN is set for continuous operation (Fan On icon dis-

played), then the G output is turned off for 30 seconds at the

end of each cooling cycle as long as dehumidification demand

exists. Like humidification, dehumidification actions are initi-

ated when humidity is 1% above set point and are terminated

when humidity drops to 4% below set point. This prevents un-

necessary toggling of dehumidification actions when humidity

is near the set point. 

Holiday — 

A holiday selection is available specifically for

times when the space will not be occupied for an extended peri-

od. Holiday mode has an automatic hold, meaning that set

points are not affected by the programmed schedule. Holiday

mode is active for a specified period of time. While in Holiday

mode, the system provides temperature and humidity protec-

tion for the space in the selected mode, but not comfort. When

Holiday mode is active, an arrow will be displayed beside

“HOLIDAY” in the upper left corner of the display.
HOLIDAY SET POINTS — A special set of temperature and

humidity set points are active in Holiday mode. They are ad-

justable by the user and are used exclusively for Holiday mode.

They are remembered from one holiday selection to the next.

See Table 4 for default holiday values.

Table 4 – Holiday Default Values

HOLIDAY HUMIDIFICATION — Normal  humidification

is available using holiday set points. Auto humidification is

available, adjusting its set point with outdoor temperature the

same as when occupied. Holiday humidification can be turned

off independently of occupied humidification. While setting

the Holiday set points, the Holiday humidification set point is

accessible by pressing the softkey below the humidification

icon when the box is around the heating set point.
HOLIDAY DEHUMIDIFICATION — Normal  Dehumidifi-

cation, Cool to Dehumidification, and Dehumidification OFF

are all available in Holiday mode. The selection of one of these

can be different from that of occupied mode. Holiday dehumid-

ification selection and set points are remembered the next time

holiday is used. While setting holiday set points, the holiday

dehumidification set point is accessible by pressing the softkey

below the dehumidification icon when the box is around the

cooling set point.

OPERATION

Timers

FIVE-MINUTE  COMPRESSOR  TIMEGUARD  —   This

timer prevents compressor from starting unless it has been off

for at least 5 minutes. It can be overridden for 1 cycle by simul-

taneously pressing the OCCUPIED

 

and UP buttons.

CYCLE TIMER — Based on the selection of 4, 6, or 8 cycles

per hour, this timer is set to 15, 10 or 7.5 minutes. This time

must elapse from the start of one cycle before another cycle can

start. It serves to impose the cycles per hour limits. It can be

OUT

S

IDE TEMPERATURE (F)

-20 -15 -10   -5    0    5   10   15  20   25  

3

0  

3

5  40  45   50

45%

40%

3

5%

3

0%

25%

20%

15%

10%

  5%

  0%

T

ARGET HUMIDITY

9

8

7

6

5

4

3

2 1

a33-9173

MODE

AUTO SET POINTS

Fan

Follows setting of Option 37

Heat Set Point

55 F

Cool Set Point

85 F

Humidification Set Point

20

%

Dehumidification Set Point

98

%

Summary of Contents for EDGE PRO 33CS2PP2S-01

Page 1: ...fies the most serious hazards which will result in severe personal injury or death WARNING signifies a haz ard which could result in personal injury or death CAUTION is used to identify unsafe practices which would result in minor personal injury or property damage GENERAL Carrier s 7 day 5 2 day or 1 day programmable commer cial thermostat control is a wall mounted low voltage control which provi...

Page 2: ... in a frequently used room preferably on an inside wall on a section of wall without pipes or ductwork where temperature operating limits are within 67 to 257 F 55 to 125 C where humidity operating range is within 0 to 95 rela tive humidity non condensing The thermostat should NOT be mounted close to a window on an outside wall or next to a door leading to the outside where exposed to direct light...

Page 3: ...ole in wall to prevent air leaks Leaks can af fect operation and cause incorrect temperature and or hu midity measurement 11 Attach 2 wire pigtail to display module Pigtail is packed loose in the box from the factory Pigtail is attached to the back of the display module via 2 pin keyed connector 12 Reattach display module body to mounting base by first setting the module on at top of mounting base...

Page 4: ...ig 10 18 Turn on power to equipment On power up all display segments will light for 5 seconds For the next 5 seconds a 2 digit code will appear on the center of the large dis play which identifies the equipment configuration AC Two stage heat Two stage cool HP Three stage heat Two stage cool Fig 10 Cover Installed on Equipment Control Module Fig 9 Control Module Connector Block Terminals a33 9169 ...

Page 5: ...r to be connected to it for proper operation The thermostat will not operate without these connections The Rh and Rc terminals are connected via the PCB breakout jumper For applications using a single 24 VAC transformer for power the breakout jumper should remain in tact For applications using two 24 VAC transformers the breakout jumper must be broken because possible voltage dif ferences between ...

Page 6: ... default is OF off OPTION 08 AUXILIARY HEAT LOCKOUT TEM PERATURE SETTING This selection is available on heat pump systems with a valid outdoor temperature sensor con nected Available settings are Off 5 10 15 20 25 30 35 40 45 50 and 55 When set to OF off the function is disabled Auxiliary heat is allowed to operate whenever sufficient demand for heat is available When set to 5 through 55 F this is...

Page 7: ...ttons to change to the desired value When set to 2 the dry contact will operate as a DEHUM re lay This option is only available on the 33CS2PPRH 01 mod el There is a 1 4 hysteresis around the dehumidification set point to prevent rapid on off cycling of the DEHUM output When configured for dehumidification the Rc terminal must be connected to one of the dry contact terminals This provides power to...

Page 8: ...ed the installer will then choose the end date for daylight savings time Fall which will be a month range of 7 to 12 To activate the function the installer changes the 2 by pressing the up button and On is displayed The setting should be left On to enable the Daylight Savings Time func tion Default is On OPTION 32 UNUSED OPTION 33 SINGLE OR TWO PIECE INSTALLA TION This configuration allows the the...

Page 9: ...te use MODE button to select between HEAT COOL AUTO or EM HEAT to provide desired operation Default Schedule If the programmed schedule is to be used make sure the triangle icon next to the FOLLOW SCHEDULE icon is turned on The default schedule is shown in Table 2 Pressing the Schedule button will cycle the triangle icon through the FOLLOW SCHEDULE HOLD and HOLI DAY selections If fixed temperature...

Page 10: ...Press the softkey below the dehumidification icon button to bring up dehumidification se lections Dehumidification options are only available when in Cooling mode When system is in AUTO mode dehumidifica tion options are available if the last system operation was a call for cooling If FAN is set for continuous operation Fan On icon dis played then the G output is turned off for 30 seconds at the e...

Page 11: ...ion func tion For dehumidification control 24 volts is applied from Rc to the dehumidifier through relay contacts D1 and D2 A sepa rate jumper wire is needed between Rc and one dry contact ter minal such as D1 If timed control of the system fan is required the dry con tact can be used for this function For fan control 24 volts is applied from Rh to G through relay contacts D1 and D2 A sep arate ju...

Page 12: ...X COMMERCIAL THERMOSTAT CONNECTION BOARD TB2 Humidi MiZer FIOP Connection not required TB2 for 48 50HJ015 028 and 48 50TJ TM016 028 units Connection Board for all other units LEGEND FIOP Factory Installed Option FU Fuse LTLO Low Temperature Lockout a33 9174 Rc Rh W W1 G Y Y2 C O W2 B Y1 OAT RRS SRTN HUM D1 D2 V Vg R Y1 Y2 W1 W2 G C X COMMERCIAL THERMOSTAT BASE UNIT CONNECTION BOARD HM OC W2 W1 W2 ...

Page 13: ...2 V Vg R Y1 Y2 W1 W2 G C X COMMERCIAL THERMOSTAT TB1 TB2 1 2 HUMIDISTAT Humidi MiZer FIOP Connection not required TB1 for 48 50PG03 16 units and TB2 for 48 50PG PM20 28 units and 48 50HG014 028 units a33 9176 Rc Rh W1 G Y2 C O W2 B Y1 OAT RRS SRTN HUM D1 D2 V Vg X C G W2 W1 Y2 Y1 R COMMERCIAL THERMOSTAT COMMAND CENTER Connection not required a33 9177 ...

Page 14: ...Q024 028 Heat Pump Units Rc Rh W1 G Y2 C O W2 B Y1 OAT RRS SRTN HUM D1 D2 V Vg RC RH W1 W2 Y1 Y2 G C X 11 TB2 COMMERCIAL THERMOSTAT R R ISOLATION RELAY Connection not required a33 9178 Rc Rh W1 G Y2 C O W2 B Y1 OAT RRS SRTN HUM D1 D2 V Vg R W1 W2 C Y1 Y2 G COMMERCIAL THERMOSTAT TB3 a33 9179 ...

Page 15: ...R Y1 Y2 W1 W2 G C X 8 38ARD012 LLSV 1 IFC COMMERCIAL THERMOSTAT CONNECTION BOARD TB LLSV 2 1 2 3 W1 W2 4 9 5 38ARD014 024 TB2 Connection not required LEGEND IFC Indoor Fan Contactor LLSV Liquid Line Solenoid Valve a33 9180 Rc Rh W1 G Y2 C O W2 B Y1 OAT RRS SRTN HUM D1 D2 V Vg COMMERCIAL THERMOSTAT FAN COIL 40 SERIES CONDENSING UNIT 38 SERIES R G C R C INDOOR UNIT OUTDOOR UNIT a33 9181 ...

Page 16: ...C PEC PS PSW PT RHC RHE RHR RHS RTG RVC RVE RVR RVS RWS VQL Water Source Heat Pump Units with Deluxe D Controls Rc Rh W1 G Y2 C O W2 B Y1 OAT RRS SRTN HUM D1 D2 V Vg COMMERCIAL THERMOSTAT COMPLETE C P1 Y W O G R C AL1 COMPLETE C P1 SECOND COMPRESSOR Y FIRST COMPRESSOR a33 9182 Rc Rh W1 G Y2 C O W2 B Y1 OAT RRS SRTN HUM D1 D2 V Vg COMMERCIAL THERMOSTAT DELUXE D P1 Y1 R O W2 G W1 C AL1 Y2 a33 9183 ...

Page 17: ...g 24 Thermostat Wiring Outdoor Air Temperature and Remote Room Temperature Sensors Rc Rh W1 G Y2 C O W2 B Y1 OAT RRS SRTN HUM D1 D2 V Vg COMMERCIAL THERMOSTAT TERMINAL BOARD Y Y2 C O W2 W W1 G R Y1 W2 DELUXE D P2 R H a33 9184 Rc Rh W1 G Y2 C O W2 B Y1 OAT RRS SRTN HUM D1 D2 V Vg OAT SENSOR REMOTE ROOM COMMERCIAL THERMOSTAT SENSOR a33 9185 ...

Page 18: ...T SENSOR 4 SENSOR 1 SENSOR 1 SENSOR 1 SENSOR 8 SENSOR 7 SENSOR 5 SENSOR 9 SENSOR 6 SENSOR 1 SENSOR 2 SENSOR 3 SPACE TEMPERATURE AVERAGING 9 SENSOR APPLICATION RRS STRN SPACE TEMPERATURE AVERAGING 4 SENSOR APPLICATION SENSOR 1 SENSOR 2 SENSOR 3 SENSOR 4 COMMERCIAL THERMOSTAT RRS STRN a33 9190 ...

Page 19: ...ol 24 V is provided from the HUM terminal to operate the equipment 4 For dehumidifer control 24 V is applied from Rc to the dehumidifier through relay contacts D1 and D2 a33 9186 Rc Rh W1 G Y2 C O W2 B Y1 OAT RRS SRTN HUM D1 D2 V Vg COMMERCIAL THERMOSTAT HUMIDIFIER NOTES 1 D1 and D2 can be used independently for equipment requiring a dry contact 2 If humidifier has its own low voltage power supply...

Page 20: ...ht to discontinue or change at any time specifications or designs without notice and without incurring obligations Catalog No 04 53330010 01 Printed in U S A Form 33CS 65SI Pg 20 8 08 Replaces New Copyright 2008 Carrier Corporation ...

Page 21: ......

Page 22: ......

Page 23: ......

Page 24: ...ter Reminder Option 03 _____ Fahrenheit Centigrade Selection Option 04 _____ Fan G on with W W1 Selection Option 05 _____ Space Temperature Sensing Option 06 _____ Cooling Lockout Option 07 _____ Equipment DDC Controller Option 08 _____ Auxiliary Heat Lockout Temperature Setting only available when heat pump is used and when outdoor air temperature sensor is present Option 09 Unused Option 10 ____...

Reviews: