background image

6

event of the 3-minute timeout or when installer exits from con-

figuration menu. See Table 1.

Table 1 — Configuration Options

                  LEGEND

* These settings are accessible by the user from the display without
entering Configuration mode.

Configuration Options

OPTION 01 — EQUIPMENT TYPE — This  option  deter-

mines the control method of the thermostat. It should match the

type of equipment used. The range is HP and AC.

When it is set to HP, the thermostat will be three-stage heat /

two-stage cool. When it is set to AC, the thermostat will be

two-stage heat / two-stage cool. The default is AC.
OPTION 02 — REPLACE FILTER REMINDER  —   This

configuration selects the hours of fan operation (heating, cool-

ing, or fan) before CHECK FILTER icon is displayed. With OF

selected, icon will never come on, disabling this feature. Time

selection can range from 600 to 5400 hours by selecting num-

bers 1 through 9. The time is 600

 

hours times the number se-

lected. Default is

 

1 (600 hr).

OPTION 03 — FAHRENHEIT/CENTIGRADE SELEC-

TION — This  configuration  selects between Fahrenheit (F)

and Centigrade (C) operation. Factory default is Fahrenheit (F).
OPTION 04 — FAN (G) ON WITH W/W1 SELEC-

TION — This selection determines whether fan (G) output is

to be on or off when the W/W1 is energized in either AC or HP

configurations, and when the O/W2 output is energized in the

AC configurations. Allowable selections are On and OF (off).

Default is OF (off).
OPTION 05 — SPACE TEMPERATURE SENSING —

This selection determines which sensor the control will use for

measuring space

 

temperature. Space temperature can be

sensed in one of three ways: the local sensor (L) located on the

display module, the remote sensor (r), or the average of local

and remote sensors (Lr). Settings are L, r, Lr. The default is L

(local).
NOTE: Only Carrier sensors (part no. ZONECCORRS01)

may be used for standard space temperature sensor averaging.

Sensors must be used as a single sensor, 4 sensors, or 9 sen-

sors, with total sensor wiring not to exceed 1,000 feet.
OPTION 06 — COOLING LOCKOUT   —   This  selection

disables cooling when outdoor temperature is below the speci-

fied temperature. Temperature can be set from 20 to 60 F in in-

crements of 5° F. It requires an outdoor temperature sensor.

Setting is not available if valid outdoor sensor is not connected.

Set to OF (off) to allow cooling below at all times. Allowable

settings are OF (off) and 20 through 60. Factory default is OF

(off).
OPTION 07 — EQUIPMENT DDC CONTROLLER —

This selection should be set to On when control is to be used

with an equipment DDC (direct digital controller). It is

assumed that the equipment DDC will take care of time guard

and cycle timers. The minimum on time is still controlled by

the thermostat. Allowable settings are On and OF (off). The

default is OF (off).
OPTION 08 — AUXILIARY HEAT LOCKOUT TEM-

PERATURE SETTING — This selection is available on heat

pump systems with a valid outdoor temperature sensor con-

nected. Available settings are: Off, 5, 10, 15, 20, 25, 30, 35, 40,

45, 50, and 55. 

When set to OF (off), the function is disabled. Auxiliary

heat is allowed to operate whenever sufficient demand for heat

is available.

When set to 5 through 55 F, this is the outdoor temperature

above which the auxiliary heat is not allowed to operate (unless

MODE is set to Emergency Heat). 

The default is OF (off).

OPTION 09 — UNUSED 
OPTION 10 — REVERSING VALVE — This  selection  is

only available on heat pump systems. The “O” terminal can be

configured to be energized in either heating mode or in cooling

mode, depending on heat pump operation. The “C” configura-

tion is used to describe a heat pump system that energizes its

reversing valve in cooling. The “H” configuration is used to de-

scribe a heat pump system that energizes its reversing valve in

heating. Allowable selections are C and H.The default is C.
OPTION 11 — ADJUSTABLE SET POINT DEAD-

BAND — The selection allows the installer to choose how

much differential will exist between the heating and cooling set

points. Allowable selections are 1 to 10 F. The default is 5 F.
OPTION 12 — SMART RECOVERY  —   Smart  Recovery

OF (off) means set points change precisely at setback recovery

time. A value of 30, 60, or 90 selects the number of minutes re-

covery starts before programmed recovery time. Recovery

takes place smoothly during the selected recovery time, ending

at the recovery time and temperature which is programmed.

This is not available when thermostat is configured as

OPTION

NUMBER

CONFIGURATION

01

Equipment Type

02

Replace Filter Reminder 

03*

Fahrenheit/Centigrade Selection

04

Fan (G) on with W/W1 Selection

05

Space Temperature Sensing 

06

Cooling Lockout

07

Equipment DDC Controller

08

Auxiliary Heat Lockout Temperature Setting

09

Unused

10

Reversing Valve

11

Adjustable Set Point Deadband

12

Smart Recovery

13

Space Temperature Offset Adjustment

14

Humidity Offset Adjustment 

15

Enable Auto Mode

16

Cycles Per Hour

17

Time Between Stages

18*

Backlight Configuration

19

Dry Contact 

20

Outdoor Air Temperature Offset Adjustment

21*

Keypad Lockout 

22

High Cool Latch Temperature

23

High Heat Latch Temperature

24*

Programmable/Non-Programmable

25*

Number of Programmable Periods per Day 

26

Minimum Cooling Set Point

27

Maximum Heating Set Point

28

UV Light Reminder

29

Service Reminder

30*

Unused

31*

Daylight Savings Time Configuration 

32

Unused

33

Single or Two-Piece Installation

34

OAT/SRTN Terminals for OAT or LAT Sensor

35

Emergency Heat Mode Availability

36

Fan Selection During Occupied Periods

37

Fan Selection During Unoccupied Periods

38

Maximum Temporary Hold For Hours

99

Reset to Factory Defaults

DDC

Direct Digital Controller

LAT

Leaving-Air Temperature

OAT

Outdoor-Air Temperature

UV

Ultraviolet

Summary of Contents for EDGE PRO 33CS2PP2S-01

Page 1: ...fies the most serious hazards which will result in severe personal injury or death WARNING signifies a haz ard which could result in personal injury or death CAUTION is used to identify unsafe practices which would result in minor personal injury or property damage GENERAL Carrier s 7 day 5 2 day or 1 day programmable commer cial thermostat control is a wall mounted low voltage control which provi...

Page 2: ... in a frequently used room preferably on an inside wall on a section of wall without pipes or ductwork where temperature operating limits are within 67 to 257 F 55 to 125 C where humidity operating range is within 0 to 95 rela tive humidity non condensing The thermostat should NOT be mounted close to a window on an outside wall or next to a door leading to the outside where exposed to direct light...

Page 3: ...ole in wall to prevent air leaks Leaks can af fect operation and cause incorrect temperature and or hu midity measurement 11 Attach 2 wire pigtail to display module Pigtail is packed loose in the box from the factory Pigtail is attached to the back of the display module via 2 pin keyed connector 12 Reattach display module body to mounting base by first setting the module on at top of mounting base...

Page 4: ...ig 10 18 Turn on power to equipment On power up all display segments will light for 5 seconds For the next 5 seconds a 2 digit code will appear on the center of the large dis play which identifies the equipment configuration AC Two stage heat Two stage cool HP Three stage heat Two stage cool Fig 10 Cover Installed on Equipment Control Module Fig 9 Control Module Connector Block Terminals a33 9169 ...

Page 5: ...r to be connected to it for proper operation The thermostat will not operate without these connections The Rh and Rc terminals are connected via the PCB breakout jumper For applications using a single 24 VAC transformer for power the breakout jumper should remain in tact For applications using two 24 VAC transformers the breakout jumper must be broken because possible voltage dif ferences between ...

Page 6: ... default is OF off OPTION 08 AUXILIARY HEAT LOCKOUT TEM PERATURE SETTING This selection is available on heat pump systems with a valid outdoor temperature sensor con nected Available settings are Off 5 10 15 20 25 30 35 40 45 50 and 55 When set to OF off the function is disabled Auxiliary heat is allowed to operate whenever sufficient demand for heat is available When set to 5 through 55 F this is...

Page 7: ...ttons to change to the desired value When set to 2 the dry contact will operate as a DEHUM re lay This option is only available on the 33CS2PPRH 01 mod el There is a 1 4 hysteresis around the dehumidification set point to prevent rapid on off cycling of the DEHUM output When configured for dehumidification the Rc terminal must be connected to one of the dry contact terminals This provides power to...

Page 8: ...ed the installer will then choose the end date for daylight savings time Fall which will be a month range of 7 to 12 To activate the function the installer changes the 2 by pressing the up button and On is displayed The setting should be left On to enable the Daylight Savings Time func tion Default is On OPTION 32 UNUSED OPTION 33 SINGLE OR TWO PIECE INSTALLA TION This configuration allows the the...

Page 9: ...te use MODE button to select between HEAT COOL AUTO or EM HEAT to provide desired operation Default Schedule If the programmed schedule is to be used make sure the triangle icon next to the FOLLOW SCHEDULE icon is turned on The default schedule is shown in Table 2 Pressing the Schedule button will cycle the triangle icon through the FOLLOW SCHEDULE HOLD and HOLI DAY selections If fixed temperature...

Page 10: ...Press the softkey below the dehumidification icon button to bring up dehumidification se lections Dehumidification options are only available when in Cooling mode When system is in AUTO mode dehumidifica tion options are available if the last system operation was a call for cooling If FAN is set for continuous operation Fan On icon dis played then the G output is turned off for 30 seconds at the e...

Page 11: ...ion func tion For dehumidification control 24 volts is applied from Rc to the dehumidifier through relay contacts D1 and D2 A sepa rate jumper wire is needed between Rc and one dry contact ter minal such as D1 If timed control of the system fan is required the dry con tact can be used for this function For fan control 24 volts is applied from Rh to G through relay contacts D1 and D2 A sep arate ju...

Page 12: ...X COMMERCIAL THERMOSTAT CONNECTION BOARD TB2 Humidi MiZer FIOP Connection not required TB2 for 48 50HJ015 028 and 48 50TJ TM016 028 units Connection Board for all other units LEGEND FIOP Factory Installed Option FU Fuse LTLO Low Temperature Lockout a33 9174 Rc Rh W W1 G Y Y2 C O W2 B Y1 OAT RRS SRTN HUM D1 D2 V Vg R Y1 Y2 W1 W2 G C X COMMERCIAL THERMOSTAT BASE UNIT CONNECTION BOARD HM OC W2 W1 W2 ...

Page 13: ...2 V Vg R Y1 Y2 W1 W2 G C X COMMERCIAL THERMOSTAT TB1 TB2 1 2 HUMIDISTAT Humidi MiZer FIOP Connection not required TB1 for 48 50PG03 16 units and TB2 for 48 50PG PM20 28 units and 48 50HG014 028 units a33 9176 Rc Rh W1 G Y2 C O W2 B Y1 OAT RRS SRTN HUM D1 D2 V Vg X C G W2 W1 Y2 Y1 R COMMERCIAL THERMOSTAT COMMAND CENTER Connection not required a33 9177 ...

Page 14: ...Q024 028 Heat Pump Units Rc Rh W1 G Y2 C O W2 B Y1 OAT RRS SRTN HUM D1 D2 V Vg RC RH W1 W2 Y1 Y2 G C X 11 TB2 COMMERCIAL THERMOSTAT R R ISOLATION RELAY Connection not required a33 9178 Rc Rh W1 G Y2 C O W2 B Y1 OAT RRS SRTN HUM D1 D2 V Vg R W1 W2 C Y1 Y2 G COMMERCIAL THERMOSTAT TB3 a33 9179 ...

Page 15: ...R Y1 Y2 W1 W2 G C X 8 38ARD012 LLSV 1 IFC COMMERCIAL THERMOSTAT CONNECTION BOARD TB LLSV 2 1 2 3 W1 W2 4 9 5 38ARD014 024 TB2 Connection not required LEGEND IFC Indoor Fan Contactor LLSV Liquid Line Solenoid Valve a33 9180 Rc Rh W1 G Y2 C O W2 B Y1 OAT RRS SRTN HUM D1 D2 V Vg COMMERCIAL THERMOSTAT FAN COIL 40 SERIES CONDENSING UNIT 38 SERIES R G C R C INDOOR UNIT OUTDOOR UNIT a33 9181 ...

Page 16: ...C PEC PS PSW PT RHC RHE RHR RHS RTG RVC RVE RVR RVS RWS VQL Water Source Heat Pump Units with Deluxe D Controls Rc Rh W1 G Y2 C O W2 B Y1 OAT RRS SRTN HUM D1 D2 V Vg COMMERCIAL THERMOSTAT COMPLETE C P1 Y W O G R C AL1 COMPLETE C P1 SECOND COMPRESSOR Y FIRST COMPRESSOR a33 9182 Rc Rh W1 G Y2 C O W2 B Y1 OAT RRS SRTN HUM D1 D2 V Vg COMMERCIAL THERMOSTAT DELUXE D P1 Y1 R O W2 G W1 C AL1 Y2 a33 9183 ...

Page 17: ...g 24 Thermostat Wiring Outdoor Air Temperature and Remote Room Temperature Sensors Rc Rh W1 G Y2 C O W2 B Y1 OAT RRS SRTN HUM D1 D2 V Vg COMMERCIAL THERMOSTAT TERMINAL BOARD Y Y2 C O W2 W W1 G R Y1 W2 DELUXE D P2 R H a33 9184 Rc Rh W1 G Y2 C O W2 B Y1 OAT RRS SRTN HUM D1 D2 V Vg OAT SENSOR REMOTE ROOM COMMERCIAL THERMOSTAT SENSOR a33 9185 ...

Page 18: ...T SENSOR 4 SENSOR 1 SENSOR 1 SENSOR 1 SENSOR 8 SENSOR 7 SENSOR 5 SENSOR 9 SENSOR 6 SENSOR 1 SENSOR 2 SENSOR 3 SPACE TEMPERATURE AVERAGING 9 SENSOR APPLICATION RRS STRN SPACE TEMPERATURE AVERAGING 4 SENSOR APPLICATION SENSOR 1 SENSOR 2 SENSOR 3 SENSOR 4 COMMERCIAL THERMOSTAT RRS STRN a33 9190 ...

Page 19: ...ol 24 V is provided from the HUM terminal to operate the equipment 4 For dehumidifer control 24 V is applied from Rc to the dehumidifier through relay contacts D1 and D2 a33 9186 Rc Rh W1 G Y2 C O W2 B Y1 OAT RRS SRTN HUM D1 D2 V Vg COMMERCIAL THERMOSTAT HUMIDIFIER NOTES 1 D1 and D2 can be used independently for equipment requiring a dry contact 2 If humidifier has its own low voltage power supply...

Page 20: ...ht to discontinue or change at any time specifications or designs without notice and without incurring obligations Catalog No 04 53330010 01 Printed in U S A Form 33CS 65SI Pg 20 8 08 Replaces New Copyright 2008 Carrier Corporation ...

Page 21: ......

Page 22: ......

Page 23: ......

Page 24: ...ter Reminder Option 03 _____ Fahrenheit Centigrade Selection Option 04 _____ Fan G on with W W1 Selection Option 05 _____ Space Temperature Sensing Option 06 _____ Cooling Lockout Option 07 _____ Equipment DDC Controller Option 08 _____ Auxiliary Heat Lockout Temperature Setting only available when heat pump is used and when outdoor air temperature sensor is present Option 09 Unused Option 10 ____...

Reviews: