ERROR AND STATUS CODES

6

5

For the following three tables, the indicator light mentioned in the first 

column is the green LED on the front cover, under the power switch.

Indicator Light Code

Explanation

Possible Cause

Recommended Action

OFF

No incoming 

AC power to air 

purifier control 

electronics

Normal operation when airflow is 

not present for models without flow 

sensor due to AC power to purifier 

being off at furnace control board  

(EAC terminals)

ON/OFF power switch  

turned to OFF

Turn purifier power switch  

to ON position

Power to entire system is off 

(furnace and air purifier)

Check that the HVAC system  

is switched on

Blown fuse or tripped circuit 

breaker for HVAC system

Replace fuse or reset circuit 

breaker, call for service if 

problem reoccurs

Misaligned or damaged  

purifier door

Insure that door is undamaged 

and properly installed on  

purifier cabinet

Damaged or disconnected 

incoming power wiring

Call for service

ON (continuously)

Air purifier on

Normal operation when  

airflow is present

Flashing  

(one flash every  

four seconds)

Standby mode

Normal operation when airflow  

is not present for models with  

flow sensor

Ions detected in airflow  

due to missing replaceable  

filter element

Place filter in air purifier

Debris is covering airflow sensor 

(for models including an  

airflow sensor)

Make sure flow sensor is  

clean and unobstructed

Flow sensor is damaged  

(for models including an  

airflow sensor)

Replace flow sensor,  

available as replacement kit  

(KIT160000)

Flow sensor bypass assembly is 

damaged (for models without an 

airflow sensor)

Replace flow sensor bypass 

assembly, available as 

replacement kit (KIT161000)

One or more of the three airflow 

sensor contact springs on purifier 

cabinet downstream rail are bent  

of damaged

Replace flow sensor contact 

spring assembly, included as part 

of the flow sensor kits  

(KIT160000) and flow sensor 

bypass kit (KIT161000)

Table 1: Operating Status Codes

 When the rapid flashing code occurs on the green light, the controls for the high voltage need to be reset. 

To reset the controls, the power switch needs to be turned on and off for three cycles.

1. 

Turn off power by depressing the power switch.

2.  

Wait approximately two seconds before turning  

the power back on.

3.  

Wait approximately two seconds before turning  

the power off.

4. 

Repeat Steps 2 and 3 for two more on/off cycles.

5.  

After the three on/off cycles are completed, turn 

on power by depressing the power switch on. The 

rapid flashing code on the green light should no 

longer be displayed. If the rapid flashing code on 

the green light is still displayed, repeat Steps 1 

through 5.

Note:

  By resetting the air purifier controls the issue 

with air purifier will need to be addressed by 

cleaning or servicing the air purifier.

Reset Procedure

Summary of Contents for DGAPA 1625 Series

Page 1: ...sory Kits are available if your installation does not match these recommendations see KIT160000 or KIT161000 Models DGAPAXX1625 DGAPAXX2025 DGAPAXX1620 DGAPAXX2020 DGAPAXX2420 There are three main mounting options for the air purifier product top mount bottom mount or side mount The location of the Air Purifier should be readily accessible Enough room should be provided for periodic replacement of...

Page 2: ...ound Chassis A Route the power conduit from the purifier to a knockout on the furnace that provides access to the EAC terminals on the furnace control board Affix the end of the conduit to the furnace using the included conduit fitting B Attach the quick connect terminals on the wires exiting the power conduit assembly to the furnace EAC 1 and EAC 2 spade connections Attach the ground ring termina...

Page 3: ...els including an airflow sensor Make sure flow sensor is clean and unobstructed Flow sensor is damaged for models including an airflow sensor Replace flow sensor available as replacement kit KIT160000 Flow sensor bypass assembly is damaged for models without an airflow sensor Replace flow sensor bypass assembly available as replacement kit KIT161000 One or more of the three airflow sensor contact ...

Page 4: ...ll be displayed after 10 seconds purifier will not operate until cause of error condition is rectified and purifier is reset An error code was registered in the purifier controls prior to the purifier being turned off The purifier controls may be reset during the 10 seconds in which the LED is flashing rapidly see the Reset Procedure on previous page if the problem persists follow the actions reco...

Reviews: