background image

 

 

 

 

 

 

CONDENSER AND EVAPORATOR-FAN MOTOR BEARINGS – The condenser and evaporator-fan motors have 
permanently-sealed bearings, so no field lubrication is necessary. 

4.3 – Evaporator Fan Performance Adjustment 
NOTE: 

To remove belts only, follow Steps 1, 2 & 6. Fan motor pulleys are factory set speed shown in Table 6. 

To change fan speeds: 
1. Shut off unit power supply. 
2. Loosen belt by loosening fan motor mounting plate nuts. Slide the Motor and remove belt. 
3. Loosen movable-pulley flange setscrew (see Fig. 8).  
4. Screw movable flange toward fixed flange to increase speed and away from fixed flange to decrease speed. 
Increasing fan speed increases load on motor. Do not exceed maximum speed specified in Table 6. See Table 7 for 
air flow. 
5. Set movable flange at nearest keyway of pulley hub and tighten setscrew. (See Table 1 & 6 for speed change for 
each full turn of pulley flange.) 
6. Replace and tighten belts. See Belt Tension Adjustment section on table 1. 

To align fan and motor pulleys: 
1. Loosen fan pulley setscrews. 
2. Slide fan pulley along fan shaft. 
3. Make angular alignment by loosening motor from mounting plate. 

4.4 – Evaporator Fan Service and Replacement 

1. Remove supply-air section panel (The bolts holding the flexible connection to the panel should be removed). 
2. Remove the Control Side panel. 
3. Remove the Belt (refer to the previous section for Belt removal). 
4. Remove the locking device of the hub & shaft from the both sides; it can be accessed throw the fan side panel. 
5. Pull the shaft gently from the control side, the blower will fall inside the blower housing. 
6. Loosen the (lower) first two bolts from each side of the scroll fan housing mid-plate. This can be done from the 
supply panel side, now the fan can be removed easily from the supply panel side. 
7. To assemble the fan, reverse the above procedure. 

 

 

 

 

 

 

 

Fig. 8 Evaporator – Fan Pulley Alignment and Adjustment 

 

 CAUTION 

UNIT DAMAGE HAZARD 

Failure to follow this caution may result in damage to components. 

1.  The compressor is in a Puron® refrigerant system and uses a (POE) lubricant Emkarate RL 32 3MAF. In 

the field the oil level could be topped up with Mobil EAL Arctic 22 CC if 3MAF is not available. POE oil is 
extremely hygroscopic, meaning it absorbs water readily. POE oils can absorb 15 times as much as 
other oils designed for HCFC and CFC refrigerants. Avoid exposure of the oil to the atmosphere.  

2.  Ensure that system is not subjected to liquid abuse. Turn the crankcase heater on 12 hours before 

starting the compressor. 

Page 17

Summary of Contents for DesertMaster 50TJM

Page 1: ...amiliarized with all steps and to identify if any additional reference materials as required The 50TJM units are single side discharge rooftop cooling unit utilizing electric heat as an option Units a...

Page 2: ...l Wiring Schematic 13 14 3 0 START UP INSTRUCTIONS 15 3 1 Unit Preparation 15 3 2 Internal Wiring 15 3 3 Compressor Mounting 15 3 4 Refrigerant Service Ports 15 3 5 Compressor Rotation 15 3 6 Evaporat...

Page 3: ...d to highlight suggestions which will result in enhanced installation reliability or operation 1 2 Installation Safety Considerations After the unit has been received and when it is ready to be instal...

Page 4: ...nal unit disposal Wear safety glasses and gloves when handling refrigerants Keep torches and other ignition sources away from refrigerants and oils NOTE IMPORTANT Before performing service or maintena...

Page 5: ...Diameter mm 100 28 132 38 Motor Pulley Pitch Diameter Min Max in 4 3 5 6 Fan RPM Range RPM 1030 745 1029 740 Fan Pulley Pitch Diameter in 8 4 Belt Quantity Type 1 BX71 Pulley Center To Center Distanc...

Page 6: ...porator and condenser coil plate fins 5 With the exception of clearance for the condenser coil and the damper power exhaust as stated in Note no 6 a removal fence or barricade requires no clearance TO...

Page 7: ...from the top TOP 1829mm to assure proper condenser fan operation SIDE 1219mm for Compressor Filter and Control boxes access Local codes or jurisdiction may prevail 5 With the exception of clearance fo...

Page 8: ...m clearance REAR 2134mm for coil removal This dimension can be reduced to 1219mm if conditions permit coil removal from the top TOP 1829mm to assure proper condenser fan operation SIDE 1219mm for Comp...

Page 9: ...ing or replacing the blower wheel Insulate and weatherproof all external ductwork joints and roof openings with counter flashing and mastic in accordance with applicable codes Ducts passing through an...

Page 10: ...single leads of no 18 AWG American Wire Gage colored wire from sub base terminals through conduit in unit to low voltage connection Settings may be changed slightly to provide a greater degree of com...

Page 11: ...d and Notes for Electrical Data Table HACR Heating Air Conditioning and Refrigeration AB 392v BC 404v AC 395v 1191 3 AB 397 392 5v BC 404 397 7v AC 457 397 2v 7 397 MCA MOCP 18 50TJM Size 18 34 Compre...

Page 12: ...ion Factors table below to determine heater capacity for your particular voltage 40 40 50TJ601162 50TJ600730 Duct heater assembly 50TJM 18 480 V Heater capacity kW is based on heater voltage of 380v o...

Page 13: ...Page 13 Fig 6...

Page 14: ...Page 14 Fig 7...

Page 15: ...the suction pressure does not drop and the discharge pressure does not rise to normal levels 1 Note that the evaporator fan is probably also rotating in the wrong direction 2 Turn off power to the uni...

Page 16: ...IL Clean condenser coil annually and as required by location and outdoor air conditions Inspect coil monthly clean as required CONDENSATE DRAIN Check and clean each year at start of cooling season FIL...

Page 17: ...cement 1 Remove supply air section panel The bolts holding the flexible connection to the panel should be removed 2 Remove the Control Side panel 3 Remove the Belt refer to the previous section for Be...

Page 18: ...nt until conditions of the chart are met Note that charging chart is different from those normally used An accurate pressure gage and temperature sensing device is required Charging is accomplished by...

Page 19: ...and bottom of the evaporator coil It detects frost build up and turns off the compressor allowing the coil to clear Once the frost has melted the compressor can be reenergized 4 9 Control Circuit 24...

Page 20: ...51 4500 875 2 29 2 69 924 2 55 3 00 971 2 82 3 31 1018 3 09 3 64 1062 3 38 3 97 5000 891 2 66 3 12 939 2 94 3 45 986 3 22 3 79 1030 3 51 4 13 1073 3 81 4 48 5500 909 3 07 3 60 955 3 36 3 95 998 3 65 4...

Page 21: ...8 4 72 6000 893 3 25 3 86 938 3 54 4 20 980 3 84 4 56 1023 4 15 4 93 1064 4 47 5 31 6500 913 3 73 4 43 956 4 04 4 80 998 4 36 5 17 1038 4 68 5 56 1077 5 01 5 95 7000 936 4 28 5 08 976 4 60 5 46 1016 4...

Page 22: ...BHP 5000 801 2 22 2 64 849 2 51 2 98 898 2 83 3 35 944 3 16 3 75 989 3 51 4 17 5500 813 2 50 2 97 859 2 80 3 32 904 3 12 3 70 948 3 45 4 10 990 3 79 4 50 6000 827 2 83 3 35 870 3 12 3 70 913 3 44 4 09...

Page 23: ...6 24 7500 887 4 27 5 12 924 4 61 5 53 961 4 96 5 95 996 5 32 6 38 1032 5 70 6 84 8000 908 4 80 5 76 944 5 15 6 18 978 5 51 6 61 1012 5 88 7 06 1046 6 26 7 52 8500 930 5 38 6 46 964 5 74 6 89 997 6 11...

Page 24: ...e Add charge if above upper curve 40 50 60 70 80 90 100 110 120 130 140 150 200 250 300 350 400 450 500 550 600 Liquid Temperature at Valve F Liquid Pressure PSIG CHARGING CHART 50TJM 18 Both Circuits...

Page 25: ...curve Add charge if above upper curve 40 50 60 70 80 90 100 110 120 130 140 150 200 250 300 350 400 450 500 550 600 Liquid Temperature at Valve F Liquid Pressure PSIG CHARGING CHART 50TJM 34 Both Circ...

Page 26: ...ak repair and recharge Air in system Recover refrigerant evacuate system and recharge Condenser coil dirty or restricted Clean coil or remove restriction Dirty drier filter Replace filter Dirty conden...

Page 27: ...10 SEALED ALL POWER AND CONTROL WIRES ENTRY INTO THE UNIT AND INSIDE THE BOX L3 L1 L3 L3 START UP CHECKLIST Remove and Store in Job File II PRE START UP Insert checkmark in box as each item is complet...

Page 28: ...serves the rights to discontinue or change at any time specifications or designs without notice and without incurring obligations Supersedes Version 50TJM IOM05 Version 50TJM IOM06 Effective Date 22 0...

Reviews: