Fan Performance Table - 7 (cont)
RPM
KWI
BHP
RPM
KWI
BHP
RPM
KWI
BHP
RPM
KWI
BHP
RPM
KWI
BHP
7000
661
2.42
2.79
704
2.69
3.11
746
2.98
3.44
787
3.29
3.79
827
3.60
4.15
7500
691
2.86
3.30
732
3.15
3.63
773
3.46
3.99
811
3.77
4.34
849
4.10
4.72
8000
723
3.36
3.87
761
3.65
4.22
798
3.96
4.57
836
4.30
4.95
872
4.64
5.35
8500
754
3.90
4.50
791
4.22
4.86
826
4.55
5.25
860
4.88
5.63
896
5.23
6.04
9000
785
4.49
5.18
819
4.83
5.57
853
5.17
5.96
887
5.52
6.37
920
5.89
6.79
9500
814
5.13
5.92
846
5.48
6.32
879
5.83
6.72
910
6.19
7.14
943
6.57
7.58
10000
843
5.83
6.72
875
6.19
7.14
905
6.56
7.56
936
6.93
8.00
966
7.32
8.44
RPM
KWI
BHP
RPM
KWI
BHP
RPM
KWI
BHP
RPM
KWI
BHP
RPM
KWI
BHP
7000
867
3.94
4.55
906
4.28
4.94
945
4.65
5.36
983
5.02
5.79
1020
5.41
6.24
7500
887
4.44
5.12
924
4.79
5.53
961
5.16
5.95
996
5.53
6.38
1032
5.93
6.84
8000
908
4.99
5.76
944
5.36
6.18
978
5.73
6.61
1012
6.12
7.05
1046
6.51
7.51
8500
930
5.60
6.46
964
5.97
6.89
997
6.36
7.34
1029
6.75
7.78
1062
7.16
8.25
9000
952
6.25
7.21
985
6.64
7.65
1017
7.03
8.11
1049
7.44
8.58
1080
7.86
9.07
9500
973
6.96
8.02
1004
7.34
8.47
1035
7.75
8.94
1065
8.16
9.41
1095
8.59
9.91
10000
996
7.72
8.90
1026
8.12
9.36
1055
8.54
9.84
1085
8.97
10.34
1114
9.40
10.84
RPM
KWI
BHP
RPM
KWI
BHP
RPM
KWI
BHP
RPM
KWI
BHP
RPM
KWI
BHP
7000
661
2.32
2.79
704
2.59
3.11
746
2.87
3.44
787
3.16
3.80
827
3.46
4.15
7500
691
2.75
3.30
732
3.02
3.63
773
3.32
3.99
811
3.62
4.34
849
3.94
4.73
8000
723
3.23
3.87
761
3.51
4.22
798
3.81
4.57
836
4.13
4.96
872
4.46
5.35
8500
754
3.75
4.50
791
4.05
4.87
826
4.37
5.25
860
4.69
5.63
896
5.03
6.04
9000
785
4.32
5.19
819
4.64
5.57
853
4.97
5.96
887
5.31
6.37
920
5.66
6.79
9500
814
4.93
5.92
846
5.26
6.32
879
5.60
6.73
910
5.95
7.15
943
6.31
7.58
10000
843
5.60
6.73
875
5.95
7.15
905
6.30
7.57
936
6.66
8.00
966
7.04
8.45
RPM
KWI
BHP
RPM
KWI
BHP
RPM
KWI
BHP
RPM
KWI
BHP
RPM
KWI
BHP
7000
867
3.79
4.55
906
4.12
4.94
945
4.47
5.36
983
4.83
5.80
1020
5.20
6.24
7500
887
4.27
5.12
924
4.61
5.53
961
4.96
5.95
996
5.32
6.38
1032
5.70
6.84
8000
908
4.80
5.76
944
5.15
6.18
978
5.51
6.61
1012
5.88
7.06
1046
6.26
7.52
8500
930
5.38
6.46
964
5.74
6.89
997
6.11
7.34
1029
6.48
7.78
1062
6.88
8.26
9000
952
6.01
7.21
985
6.38
7.66
1017
6.76
8.12
1049
7.15
8.59
1080
7.56
9.07
9500
973
6.69
8.03
1004
7.06
8.47
1035
7.45
8.94
1065
7.84
9.42
1095
8.26
9.91
10000
996
7.42
8.91
1026
7.80
9.36
1055
8.20
9.85
1085
8.62
10.35
1114
9.03
10.84
8. Conversion - Bhp to KWI
Unit - 50TJM - 34 - 28 Tons - 50Hz (High Efficiency Motor)
1.8
2.0
Available External Static Pressure (in. wg)
Unit - 50TJM - 34 - 28 Tons - 50Hz (Standard Motor)
0.6
0.8
1.0
Unit - 50TJM - 34 - 28 Tons - 50Hz (Standard Motor) (cont)
Air Flow Rate
(CFM)
Available External Static Pressure (in. wg)
0.2
0.4
0.6
0.8
1.0
Bold , Italics
-
High Efficiency Motor and Drive Package
Legend:
RPM -
Revolutions Per Minute
KWI -
Kilo Watts Input to Motor
BHP -
Brake Horsepower Input to Fan
Available External Static Pressure (in. wg)
Available External Static Pressure (in. wg)
0.2
0.4
1.2
1.4
1.6
1.2
1.4
1.6
1.8
2.0
Air Flow Rate
(CFM)
Bold, Italics
-
Standard Motor and Drive Package
Air Flow Rate
(CFM)
Air Flow Rate
(CFM)
Unit - 50TJM - 34 - 28 Tons - 50Hz (High Efficiency Motor) (cont)
KWI=
Bhp X 0.746
Motor efficiency
CFM -
Cubic Feet per Minute
Notes:
1. Do not adjust motor rpm such that motor maximum bhp and/or watts is exceeded at the maximum operatin cfm.
2. Static Pressure (i.e Filters) must be added to external static pressure before entering fan performance table.
3. Interpolation is permissible. Do not extrapolate.
4. Fan performance is based on wet coils, clean filters and casing loses.
5. Extensive motor and drive testing on these units ensures that the full brake horsepower and watts range of the motor can be utilized with confidence. Using
your fan motors up to the watts or bhp rating shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.
6. Bold data shows the range of air flow rate for unit management system, other rpms require field-supplied drive.
7. Use of field-supplied motor may affect wiring size. Contact your Carrier representative for details.
Page 23
Summary of Contents for DesertMaster 50TJM
Page 13: ...Page 13 Fig 6...
Page 14: ...Page 14 Fig 7...