background image

Fan Performance Table - 7 (cont)

RPM

KWI

BHP

RPM

KWI

BHP

RPM

KWI

BHP

RPM

KWI

BHP

RPM

KWI

BHP

5000

583

1.30

1.48

642

1.51

1.73

698

1.75

2.00

754

1.99

2.28

805

2.25

2.58

5500

617

1.62

1.86

672

1.86

2.13

724

2.10

2.41

775

2.36

2.70

825

2.63

3.01

6000

654

2.01

2.30

704

2.26

2.58

752

2.51

2.88

800

2.79

3.19

847

3.07

3.51

6500

689

2.44

2.80

735

2.71

3.10

781

2.98

3.41

826

3.27

3.74

871

3.57

4.08

7000

725

2.95

3.37

768

3.22

3.69

811

3.51

4.02

854

3.81

4.36

895

4.12

4.72

7500

761

3.51

4.02

802

3.80

4.35

842

4.11

4.70

882

4.42

5.06

921

4.74

5.43

RPM

KWI

BHP

RPM

KWI

BHP

RPM

KWI

BHP

RPM

KWI

BHP

RPM

KWI

BHP

5000

856

2.52

2.88

906

2.80

3.20

954

3.08

3.53

998

3.37

3.86

1040

3.67

4.20

5500

874

2.91

3.34

920

3.20

3.67

966

3.50

4.01

1009

3.81

4.36

1052

4.13

4.72

6000

893

3.37

3.85

938

3.67

4.20

980

3.98

4.56

1023

4.30

4.93

1064

4.63

5.30

6500

913

3.87

4.43

956

4.19

4.79

998

4.51

5.17

1038

4.85

5.55

1077

5.20

5.95

7000

936

4.44

5.08

976

4.77

5.46

1016

5.11

5.85

1055

5.46

6.25

1094

5.82

6.66

7500

959

5.07

5.80

998

5.41

6.20

1035

5.77

6.60

1073

6.13

7.02

1110

6.50

7.44

RPM

KWI

BHP

RPM

KWI

BHP

RPM

KWI

BHP

RPM

KWI

BHP

RPM

KWI

BHP

5000

583

1.25

1.48

642

1.46

1.73

698

1.69

2.00

754

1.92

2.28

805

2.17

2.58

5500

617

1.57

1.86

672

1.79

2.13

724

2.03

2.41

775

2.28

2.70

825

2.54

3.01

6000

654

1.94

2.30

704

2.18

2.58

752

2.42

2.88

800

2.69

3.19

847

2.96

3.52

6500

689

2.36

2.80

735

2.61

3.10

781

2.88

3.41

826

3.15

3.74

871

3.44

4.08

7000

725

2.84

3.37

768

3.11

3.69

811

3.39

4.02

854

3.68

4.36

895

3.98

4.72

7500

761

3.39

4.02

802

3.67

4.35

842

3.96

4.70

882

4.26

5.06

921

4.57

5.43

RPM

KWI

BHP

RPM

KWI

BHP

RPM

KWI

BHP

RPM

KWI

BHP

RPM

KWI

BHP

5000

856

2.43

2.88

906

2.70

3.20

954

2.97

3.53

998

3.25

3.86

1040

3.54

4.20

5500

874

2.81

3.34

920

3.09

3.67

966

3.38

4.01

1009

3.67

4.36

1052

3.98

4.72

6000

893

3.25

3.86

938

3.54

4.20

980

3.84

4.56

1023

4.15

4.93

1064

4.47

5.31

6500

913

3.73

4.43

956

4.04

4.80

998

4.36

5.17

1038

4.68

5.56

1077

5.01

5.95

7000

936

4.28

5.08

976

4.60

5.46

1016

4.93

5.85

1055

5.26

6.25

1094

5.61

6.66

7500

959

4.89

5.81

998

5.22

6.20

1035

5.56

6.60

1073

5.91

7.02

1110

6.27

7.44

8. Conversion - Bhp to KWI

7. Use of field-supplied motor may affect wiring size. Contact your Carrier representative for details.

KWI=

Bhp X 0.746

Motor efficiency

Unit - 50TJM - 24 - 19 Tons - 50Hz (High Efficiency Motor)

Bold, Italics

 - 

Standard Motor and Drive Package

1.2

1.4

1.6

Bold , Italics

 - 

High Efficiency Motor and Drive Package

BHP - 

Brake Horsepower Input to Fan

0.6

0.8

1.0

1.8

2.0

2. Static Pressure (i.e Filters) must be added to external static pressure before entering fan performance table.

6. Bold data shows the range of air flow rate for unit management system, other rpms require field-supplied drive.

Air Flow Rate 

(CFM)

KWI - 

Kilo Watts Input to Motor

RPM - 

Revolutions Per Minute

Legend:

Air Flow Rate 

(CFM)

Unit - 50TJM - 24 - 19 Tons - 50Hz (High Efficiency Motor) (cont)

5. Extensive motor and drive testing on these units ensures that the full brake horsepower and watts range of the motor can be utilized with confidence. Using 

your fan motors up to the watts or bhp rating shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.

4. Fan performance is based on wet coils, clean filters and casing loses.

3. Interpolation is permissible. Do not extrapolate.

1. Do not adjust motor rpm such that motor maximum bhp and/or watts is exceeded at the maximum operatin cfm.

Notes:

CFM - 

Cubic Feet per Minute

1.6

1.8

2.0

Unit - 50TJM - 24 - 19 Tons - 50Hz (Standard Motor)

Air Flow Rate 

(CFM)

Unit - 50TJM - 24 - 19 Tons - 50Hz (Standard Motor) (cont)

Available External Static Pressure (in. wg)

Available External Static Pressure (in. wg)

0.2

0.4

1.2

1.4

Air Flow Rate 

(CFM)

Available External Static Pressure (in. wg)

Available External Static Pressure (in. wg)

0.2

0.4

0.6

0.8

1.0

Page 21

Summary of Contents for DesertMaster 50TJM

Page 1: ...amiliarized with all steps and to identify if any additional reference materials as required The 50TJM units are single side discharge rooftop cooling unit utilizing electric heat as an option Units a...

Page 2: ...l Wiring Schematic 13 14 3 0 START UP INSTRUCTIONS 15 3 1 Unit Preparation 15 3 2 Internal Wiring 15 3 3 Compressor Mounting 15 3 4 Refrigerant Service Ports 15 3 5 Compressor Rotation 15 3 6 Evaporat...

Page 3: ...d to highlight suggestions which will result in enhanced installation reliability or operation 1 2 Installation Safety Considerations After the unit has been received and when it is ready to be instal...

Page 4: ...nal unit disposal Wear safety glasses and gloves when handling refrigerants Keep torches and other ignition sources away from refrigerants and oils NOTE IMPORTANT Before performing service or maintena...

Page 5: ...Diameter mm 100 28 132 38 Motor Pulley Pitch Diameter Min Max in 4 3 5 6 Fan RPM Range RPM 1030 745 1029 740 Fan Pulley Pitch Diameter in 8 4 Belt Quantity Type 1 BX71 Pulley Center To Center Distanc...

Page 6: ...porator and condenser coil plate fins 5 With the exception of clearance for the condenser coil and the damper power exhaust as stated in Note no 6 a removal fence or barricade requires no clearance TO...

Page 7: ...from the top TOP 1829mm to assure proper condenser fan operation SIDE 1219mm for Compressor Filter and Control boxes access Local codes or jurisdiction may prevail 5 With the exception of clearance fo...

Page 8: ...m clearance REAR 2134mm for coil removal This dimension can be reduced to 1219mm if conditions permit coil removal from the top TOP 1829mm to assure proper condenser fan operation SIDE 1219mm for Comp...

Page 9: ...ing or replacing the blower wheel Insulate and weatherproof all external ductwork joints and roof openings with counter flashing and mastic in accordance with applicable codes Ducts passing through an...

Page 10: ...single leads of no 18 AWG American Wire Gage colored wire from sub base terminals through conduit in unit to low voltage connection Settings may be changed slightly to provide a greater degree of com...

Page 11: ...d and Notes for Electrical Data Table HACR Heating Air Conditioning and Refrigeration AB 392v BC 404v AC 395v 1191 3 AB 397 392 5v BC 404 397 7v AC 457 397 2v 7 397 MCA MOCP 18 50TJM Size 18 34 Compre...

Page 12: ...ion Factors table below to determine heater capacity for your particular voltage 40 40 50TJ601162 50TJ600730 Duct heater assembly 50TJM 18 480 V Heater capacity kW is based on heater voltage of 380v o...

Page 13: ...Page 13 Fig 6...

Page 14: ...Page 14 Fig 7...

Page 15: ...the suction pressure does not drop and the discharge pressure does not rise to normal levels 1 Note that the evaporator fan is probably also rotating in the wrong direction 2 Turn off power to the uni...

Page 16: ...IL Clean condenser coil annually and as required by location and outdoor air conditions Inspect coil monthly clean as required CONDENSATE DRAIN Check and clean each year at start of cooling season FIL...

Page 17: ...cement 1 Remove supply air section panel The bolts holding the flexible connection to the panel should be removed 2 Remove the Control Side panel 3 Remove the Belt refer to the previous section for Be...

Page 18: ...nt until conditions of the chart are met Note that charging chart is different from those normally used An accurate pressure gage and temperature sensing device is required Charging is accomplished by...

Page 19: ...and bottom of the evaporator coil It detects frost build up and turns off the compressor allowing the coil to clear Once the frost has melted the compressor can be reenergized 4 9 Control Circuit 24...

Page 20: ...51 4500 875 2 29 2 69 924 2 55 3 00 971 2 82 3 31 1018 3 09 3 64 1062 3 38 3 97 5000 891 2 66 3 12 939 2 94 3 45 986 3 22 3 79 1030 3 51 4 13 1073 3 81 4 48 5500 909 3 07 3 60 955 3 36 3 95 998 3 65 4...

Page 21: ...8 4 72 6000 893 3 25 3 86 938 3 54 4 20 980 3 84 4 56 1023 4 15 4 93 1064 4 47 5 31 6500 913 3 73 4 43 956 4 04 4 80 998 4 36 5 17 1038 4 68 5 56 1077 5 01 5 95 7000 936 4 28 5 08 976 4 60 5 46 1016 4...

Page 22: ...BHP 5000 801 2 22 2 64 849 2 51 2 98 898 2 83 3 35 944 3 16 3 75 989 3 51 4 17 5500 813 2 50 2 97 859 2 80 3 32 904 3 12 3 70 948 3 45 4 10 990 3 79 4 50 6000 827 2 83 3 35 870 3 12 3 70 913 3 44 4 09...

Page 23: ...6 24 7500 887 4 27 5 12 924 4 61 5 53 961 4 96 5 95 996 5 32 6 38 1032 5 70 6 84 8000 908 4 80 5 76 944 5 15 6 18 978 5 51 6 61 1012 5 88 7 06 1046 6 26 7 52 8500 930 5 38 6 46 964 5 74 6 89 997 6 11...

Page 24: ...e Add charge if above upper curve 40 50 60 70 80 90 100 110 120 130 140 150 200 250 300 350 400 450 500 550 600 Liquid Temperature at Valve F Liquid Pressure PSIG CHARGING CHART 50TJM 18 Both Circuits...

Page 25: ...curve Add charge if above upper curve 40 50 60 70 80 90 100 110 120 130 140 150 200 250 300 350 400 450 500 550 600 Liquid Temperature at Valve F Liquid Pressure PSIG CHARGING CHART 50TJM 34 Both Circ...

Page 26: ...ak repair and recharge Air in system Recover refrigerant evacuate system and recharge Condenser coil dirty or restricted Clean coil or remove restriction Dirty drier filter Replace filter Dirty conden...

Page 27: ...10 SEALED ALL POWER AND CONTROL WIRES ENTRY INTO THE UNIT AND INSIDE THE BOX L3 L1 L3 L3 START UP CHECKLIST Remove and Store in Job File II PRE START UP Insert checkmark in box as each item is complet...