background image

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

Catalog No. 04-53480350-01

Printed in U.S.A.

Form IIK-CRPWREXH068-05

Pg 8 

6-22

Replaces: IIK-CRPWREX068-04

© 2022 Carrier

5. Turn the minimum position potentiometer (MIN POS) on the

Economizer IV controller clockwise to open until the exhaust

LED (EXH) lights up. (See Fig. 13.)

6. Dry contacts on the Economizer IV controller should close

and  energize  the  Power  Exhaust  Relay  (PER).  The  power

exhaust should turn on.

7. If the power exhaust fan does not turn on, de-energize main

power to the unit and then check the power exhaust installa

-

tion wiring.

8. Set the unit back to its original configuration by turning

the  minimum  position  potentiometer  (MIN  POS)

counter

-

clockwise, back to the marked setting and remove

the jumpers placed in Steps 2 and 3 of this procedure.

NOTE: For units with DDC control see Service and Maintenance

Manual for power exhaust functional check instructions.

For Units with W7220 Economizer

The economizer controller used on electro mechanical units is a

Honeywell W7220 which is to be located in the RTU base unit’s

control box. See the Installation Instruction for your base unit for

the location of the control box access panel.

NOTE: W7220  control  is  able  to  run  the  check-up  routine  for

economizer/exhaust directly. This routine can be accessed and ran

using the keypad and navigating through menus.

The W7220 controller provides the following:

• 2-line  LCD  interface  screen  for  setup,  configuration  and

troubleshooting

• On-board fault detection and diagnostics

• Sensor failure loss of communications identification

• Automatic sensor detection

• Capabilities  for  use  with  multiple-speed  indoor  fan

systems

USER INTERFACE
The  user  interface  consists  of  a  LCD  display  and  a  4-button

keypad on the front of the economizer controller.
KEYPAD
The  four  navigation  buttons  (see  Fig.  15)  are  used  to  scroll

through the menus/menu items, select menu items, and to change

parameter and configuration settings.
USING THE KEYPAD WITH MENUS
To use the keypad when working with menus:

• Press  the  ▲

 

Up  (arrow)  button  to  move  to  the  previous

menu.

• Press  the  ▼  (Down  arrow)  button  to  move  to  the  next

menu.

• Press the 

 (Enter) button to display the first item in the

currently displayed menu.

• Press the 

 (Menu Up/Exit) button to exit a menu’s item

and return to the list of menus.

MENU STRUCTURE
The Menus in display order are:

• STATUS

• SETPOINTS

• SYSTEM SETUP

• ADVANCED SETUP

• CHECKOUT

• ALARMS

Fig. 15 — W7220 Controller

CHECKOUT TEST
NOTE: See User Interface for information about menu navigation

and use of the keypad.

To perform a Checkout test:

1. Scroll to DAMPER OPEN in the Checkout menu using the

▲ and ▼ buttons.

2. Press the 

 button to select the item.

3. RUN appears.
4. Press the 

 button to start the test.

5. The unit pauses and then displays IN PROGRESS.
6. Exhaust fan contacts enable during the DAMPER OPEN test.

Make sure you pause in the mode to allow exhaust contacts to

energize due the delay in the system.

7. When the test is complete, DONE appears.
8. When  all  desired  parameters  have  been  tested,  press

the 

 (Menu up) button to end the test.

NOTE: Checkout test can be performed at any time during the op

-

eration of the system as a test that the system is operable.

START-UP

Refer to the base unit’s Service and Maintenance Manual for de

-

tailed Start-up instructions.

CAUTION

EQUIPMENT DAMAGE HAZARD

Failure  to  follow  this  caution  may  result  in  equipment

damage.

Be  sure  to  allow  enough  time  for  compressor  startup  and

shutdown  between  checkout  tests  so  that  you  do  not  short-

cycle the compressors.

2 LINE

LCD

MENU UP

(EXIT)

BUTTON

SCROLL

UP/DOWN

BUTTONS

SELECT

(ENTER)
BUTTON

Summary of Contents for CRPWREXH068A00

Page 1: ...tial for personal injury Understand the signal words DANGER WARNING CAUTION and NOTE These words are used with the safety alert symbol DANGER identifies the most serious hazards which will result in s...

Page 2: ...1 460 3 60 CRPWREXH069A00 1 575 3 60 CRPWREXH070A00 1 17 5 208 230 3 60 CRPWREXH068A00 1 460 3 60 CRPWREXH069A00 1 575 3 60 CRPWREXH070A00 1 20 208 230 3 60 CRPWREXH068A00 1 460 3 60 CRPWREXH069A00 1...

Page 3: ...l box is PEM2 Fig 1 Power Exhaust Relay Installation Vane Axial Fan Units Fig 2 Power Exhaust Relay Installation Belt Drive Fan Units 5 Install wiring harness 50HEMRAX A00 in the control box as shown...

Page 4: ...serrated head screws AL48AM217 Fig 5 Unit Return Air Panel Removal for Vertical Return Air Applications 3 Install three No 10 x 5 8 in serrated head screws AL48AM217 in the three locations shown in Fi...

Page 5: ...t located in the top left corner of the control box 10 Connect the 6 pin plug PL 9 from the wiring harness into the 6 pin plug of the power exhaust fan assembly Make sure that the PL 9 connection is m...

Page 6: ...Fig 11 3 Apply silicone caulking to corners and back side of mating flanges of the power exhaust fan assembly 4 Set the power exhaust hood assembly into the opening in the duct bottom lip first as sho...

Page 7: ...ntrol box 14 Bundle up excess wire of the motor harness and secure with wire ties When bundling wires be sure to gather wires as close as possible so that the wires can not contact moving parts for th...

Page 8: ...d indoor fan systems USER INTERFACE The user interface consists of a LCD display and a 4 button keypad on the front of the economizer controller KEYPAD The four navigation buttons see Fig 15 are used...

Reviews: