background image

5

Fig. 7 — Install Screws to Locate Power Exhaust Fan 

Assembly for Vertical Return Air Applications

Fig. 8 — Install Power Exhaust Fan Assembly on 

Vertical Return Air Applications

NOTE: Figures 8 and 9 are shown with the economizer hood re

-

moved to provide a clear view of the flange at the top of the power

exhaust fan assembly (Fig. 8) and the tops of the block off panels

(Fig. 9).

5. Install  three  1/4-14  x  3/4  in.  gasket  head  screws

(AL31AZ308) in the three locations at the top flange of the

power exhaust fan assembly. (See Fig. 8.)

6. Tighten the three screws at the bottom of the power exhaust

fan assembly, installed in Step 3 above. (See Fig. 8.)

7. Install the left block-off panel with two No. 10 x 5/8 in. ser

-

rated  head  screws  (AL48M217)  at  the  bottom  edge.  Make

sure the top edge of left block-off panel is behind the flange

of the upper economizer panel. Install three 1/4-14 x 3/4 in.

gasket head screws (AL31AZ308) to secure the left block-off

panel to the flange on the power exhaust fan assembly. Install

four  No.10  x  7/8  in.  gasket  head  screws  (AL31AZ219)  to

secure the left block-off plate to the unit corner post and the

upper economizer panel. (See Fig. 9.)

8. Remove  two  small  plug  access  plates  located  in  the

economizer  motor  compartment.  The  economizer  motor

compartment is accessible by removing the control box side

economizer hood screen, if the economizer hood is already

installed on the unit.

9. Route  the PL-9  plug,  supplied  with  the  power  exhaust fan

assembly, through the bottom plug access hole in the econo

-

mizer motor compartment and through the top plug access

hole. Route the PL-9 through the grommet located in the top

left corner of the control box.

10. Connect the 6 pin plug PL-9 from the wiring harness into the

6 pin plug of the power exhaust fan assembly. Make sure that

the PL-9 connection is made inside the control box.

Fig. 9 — Power Exhaust Block-Off Panels Installed 

for Vertical Return Air Applications

11. Bundle  up  excess  wire  of  the  motor  harness  and  secure

with  wire  ties.  When  bundling  wires,  be  sure  to  gather

wires as close as possible so that the wires cannot contact

moving parts for the power exhaust fans or the economizer

mechanisms.

12. Replace  plug  access  plates  in  economizer  motor  compart

-

ment.

13. Install  the  right  block-off  panel  with  two  No.  10  x  5/8  in.

serrated  head  screws  (AL48AM217)  at  the  bottom  edge.

Make sure the top edge of the right block-off panel is behind

the  flange  of  the  upper  economizer  panel.  Install  three

1/4 -14 x 3/4 in. gasket head screws (AL31AZ308) to secure

the right block-off panel to the flange of the power exhaust

fan assembly. Install four No. 10 x 7/8 in. gasket head screws

(AL31AZ219) to secure the right block-off panel to the unit

corner post and upper economizer panel. (See Fig. 9.)

14. Install six 1/4-14 x 3/4 in. gasket head screws (AL31AZ308)

in three holes in the left and right side block-off panels to pre

-

vent water leakage into the unit. These holes are for mounting

the power exhaust in the shipping position but are not needed

for accessory power exhaust applications. (See Fig. 9.)

15. Apply  silicone  caulking  to  corners  and  flanges  of  power

exhaust fan assembly at the block-off panels to prevent water

leakage.

16. Replace control box access panel. 

Install three No. 10 x 5/8 in.
serrated head screws
at the indicated locations. 

Install three 1/4-14 x 3/4 in.
gasket head screws at the
indicated locaitons.

Left
Block-Off
Panel

Right
Block-Off
Panel

Summary of Contents for CRPWREXH068A00

Page 1: ...tial for personal injury Understand the signal words DANGER WARNING CAUTION and NOTE These words are used with the safety alert symbol DANGER identifies the most serious hazards which will result in s...

Page 2: ...1 460 3 60 CRPWREXH069A00 1 575 3 60 CRPWREXH070A00 1 17 5 208 230 3 60 CRPWREXH068A00 1 460 3 60 CRPWREXH069A00 1 575 3 60 CRPWREXH070A00 1 20 208 230 3 60 CRPWREXH068A00 1 460 3 60 CRPWREXH069A00 1...

Page 3: ...l box is PEM2 Fig 1 Power Exhaust Relay Installation Vane Axial Fan Units Fig 2 Power Exhaust Relay Installation Belt Drive Fan Units 5 Install wiring harness 50HEMRAX A00 in the control box as shown...

Page 4: ...serrated head screws AL48AM217 Fig 5 Unit Return Air Panel Removal for Vertical Return Air Applications 3 Install three No 10 x 5 8 in serrated head screws AL48AM217 in the three locations shown in Fi...

Page 5: ...t located in the top left corner of the control box 10 Connect the 6 pin plug PL 9 from the wiring harness into the 6 pin plug of the power exhaust fan assembly Make sure that the PL 9 connection is m...

Page 6: ...Fig 11 3 Apply silicone caulking to corners and back side of mating flanges of the power exhaust fan assembly 4 Set the power exhaust hood assembly into the opening in the duct bottom lip first as sho...

Page 7: ...ntrol box 14 Bundle up excess wire of the motor harness and secure with wire ties When bundling wires be sure to gather wires as close as possible so that the wires can not contact moving parts for th...

Page 8: ...d indoor fan systems USER INTERFACE The user interface consists of a LCD display and a 4 button keypad on the front of the economizer controller KEYPAD The four navigation buttons see Fig 15 are used...

Reviews: