background image

3

INSTALLATION

Power and Control Wiring

1. Unpack the contents of the crate. Use Table to confirm that

the kit contains all of its parts.

2. The power exhaust motor is factory wired to the high speed

tap (terminal 1). To change the motor speed move the black

wire to the desired speed tap on the motor per Table 4.
NOTE: When using the power exhaust in a horizontal appli

-

cation, some wiring may have to be field lengthened.

3. Remove the control box access panel.
4. Install the Power Exhaust Relay (PER) in the control box, at

the position shown in Fig. 1 for vane axial units and Fig. 2 for

belt  drive fan  units,  using  two  8-18 in. x  1/2  in.  pan  head

screws (AL56AU166).

NOTE: The power exhaust motor closest to the control box is PEM1.

The motor furthest from the control box is PEM2.

Fig. 1 — Power Exhaust Relay Installation

(Vane Axial Fan Units)

Fig. 2 — Power Exhaust Relay Installation

 (Belt Drive Fan Units)

5. Install wiring harness (50HEMRAX-A00) in the control box

as shown in Fig. 3. Refer to Fig. 4 for point to point connec

-

tions. Wiring harness label near terminals should match con

-

nection point in control box.

6. Connect violet wire in unit wiring harness from PL6-11 to the

Power Exhaust Relay (PER) coil terminal 1.

7. Bundle the power exhaust wiring harness to existing control

box wiring harness with 6 of the supplied wire ties.

p

Fig. 3 — Power Exhaust Wiring Installation

Table 4 — Motor Speed Tap Configuration

MOTOR TERMINAL NUMBER

POWER 

EXHAUST 

MOTOR

1

2

3

PEM1

High

Medium

Low

PEM2

High

Medium

Low

LEGEND

PEM

— Power Exhaust Motor

Power 
Terminal
Block

Unit
Control
Board

Power Exhaust Relay 
Mounting Location

Power Exhaust Relay
Mounting Location

Power
Terminal
Block

Central
Terminal
Board

Harness
Assembly

PER

OFC

PL9

PL6

Summary of Contents for CRPWREXH068A00

Page 1: ...tial for personal injury Understand the signal words DANGER WARNING CAUTION and NOTE These words are used with the safety alert symbol DANGER identifies the most serious hazards which will result in s...

Page 2: ...1 460 3 60 CRPWREXH069A00 1 575 3 60 CRPWREXH070A00 1 17 5 208 230 3 60 CRPWREXH068A00 1 460 3 60 CRPWREXH069A00 1 575 3 60 CRPWREXH070A00 1 20 208 230 3 60 CRPWREXH068A00 1 460 3 60 CRPWREXH069A00 1...

Page 3: ...l box is PEM2 Fig 1 Power Exhaust Relay Installation Vane Axial Fan Units Fig 2 Power Exhaust Relay Installation Belt Drive Fan Units 5 Install wiring harness 50HEMRAX A00 in the control box as shown...

Page 4: ...serrated head screws AL48AM217 Fig 5 Unit Return Air Panel Removal for Vertical Return Air Applications 3 Install three No 10 x 5 8 in serrated head screws AL48AM217 in the three locations shown in Fi...

Page 5: ...t located in the top left corner of the control box 10 Connect the 6 pin plug PL 9 from the wiring harness into the 6 pin plug of the power exhaust fan assembly Make sure that the PL 9 connection is m...

Page 6: ...Fig 11 3 Apply silicone caulking to corners and back side of mating flanges of the power exhaust fan assembly 4 Set the power exhaust hood assembly into the opening in the duct bottom lip first as sho...

Page 7: ...ntrol box 14 Bundle up excess wire of the motor harness and secure with wire ties When bundling wires be sure to gather wires as close as possible so that the wires can not contact moving parts for th...

Page 8: ...d indoor fan systems USER INTERFACE The user interface consists of a LCD display and a 4 button keypad on the front of the economizer controller KEYPAD The four navigation buttons see Fig 15 are used...