7

Fig. 12 — Hood Assembly Placed in Duct Work

6. Install  three  1/4-14  x  3/4  in.  gasket  head  screws

(AL31AZ308) along the top of the hood. 

7. Install  three  1/4-14  x  3/4  in.  gasket  head  screws

(AL31AZ308) along the bottom of the hood.

8. Install 3 more 1/4-14 x 3/4 screws om right and left side of

hood assembly.

9. Remove shipping tape from damper blades.
10. Remove two small plug access plates located in the econo

-

mizer motor compartment. The economizer motor compart

-

ment is accessible by removing the economizer hood screen,

if the economizer hood is already installed on the unit.

11. Connect  wiring  harness  (50HE401639)  to  power  exhaust

assembly PL-9 to extend harness if needed.

12. Route  the  PL-9  plug, supplied  with the  power  exhaust fan

assembly, through the bottom plug access hole in the econo

-

mizer motor compartment and through the top plug access

hole. Route the PL-9 through the grommet located in the top

left corner of the control box. 

13. Connect the 6 pin plug PL-9 from the wiring harness into the

6 pin plug of the power exhaust fan assembly. Ensure that the

PL-9 connection is made inside the control box.

14. Bundle up excess wire of the motor harness and secure with

wire ties. When bundling wires, be sure to gather wires as

close as possible so that the wires can not contact moving

parts for the power exhaust fans or the economizer mecha

-

nisms.

15. Replace  plug  access  plates  in  economizer  motor

compartment.

16. Replace the control box access panel.

POWER EXHAUST FUNCTIONAL CHECK

For Units with EconoMi$er IV Controls 

(HH63AW001-W7212 Honeywell Controller)

1. With  main  power  shut  off,  mark  minimum  position  on

EconoMi$er

®

 IV controller. (See Fig.13.)

Fig. 13 — EconoMi$er IV Controller (HH63AW001-

W7212 Honeywell Controller)

2. The  controller  must  be  in  occupied  mode  to  energize  the

power exhaust fans. To set the controller to occupied mode,

check the “CUT FOR OCCUPANCY” jumper on the central

terminal board. (See Fig. 14).

Fig. 14 — Central Terminal Board

• If the jumper has not been cut, proceed to Step 3.

• If the jumper has been cut, place a jumper wire across the

OCCUPANCY terminal.

3. Place jumper wire on thermostat inputs across terminals R

and  G  to  activate  a  call  for  indoor  fan  to  energize.  (See

Fig. 14.)

4. Energize main power to the unit.

TR1

24 Vac

COM

TR

24 

Vac

HOT

1

2

3

4

5

EF

EF1

+

_

P1

T1

P

T

N

EXH

2V

10V

EXH

Set

Set

2V

10V

2V

10V

DCV

DCV

Free
Cool

B

C

A

D

SO+

SR+

SR

SO

AQ1

AQ

DCV

Min
Pos

Open

Max

N1

Summary of Contents for CRPWREXH068A00

Page 1: ...tial for personal injury Understand the signal words DANGER WARNING CAUTION and NOTE These words are used with the safety alert symbol DANGER identifies the most serious hazards which will result in s...

Page 2: ...1 460 3 60 CRPWREXH069A00 1 575 3 60 CRPWREXH070A00 1 17 5 208 230 3 60 CRPWREXH068A00 1 460 3 60 CRPWREXH069A00 1 575 3 60 CRPWREXH070A00 1 20 208 230 3 60 CRPWREXH068A00 1 460 3 60 CRPWREXH069A00 1...

Page 3: ...l box is PEM2 Fig 1 Power Exhaust Relay Installation Vane Axial Fan Units Fig 2 Power Exhaust Relay Installation Belt Drive Fan Units 5 Install wiring harness 50HEMRAX A00 in the control box as shown...

Page 4: ...serrated head screws AL48AM217 Fig 5 Unit Return Air Panel Removal for Vertical Return Air Applications 3 Install three No 10 x 5 8 in serrated head screws AL48AM217 in the three locations shown in Fi...

Page 5: ...t located in the top left corner of the control box 10 Connect the 6 pin plug PL 9 from the wiring harness into the 6 pin plug of the power exhaust fan assembly Make sure that the PL 9 connection is m...

Page 6: ...Fig 11 3 Apply silicone caulking to corners and back side of mating flanges of the power exhaust fan assembly 4 Set the power exhaust hood assembly into the opening in the duct bottom lip first as sho...

Page 7: ...ntrol box 14 Bundle up excess wire of the motor harness and secure with wire ties When bundling wires be sure to gather wires as close as possible so that the wires can not contact moving parts for th...

Page 8: ...d indoor fan systems USER INTERFACE The user interface consists of a LCD display and a 4 button keypad on the front of the economizer controller KEYPAD The four navigation buttons see Fig 15 are used...

Reviews: