background image

5

MANIFOLD

PIPE PLUG

C99019

Fig. 5 -- Two--Stage Burner Assembly

REGULATOR COVER SCREW

PLASTIC ADJUST SCREW

LOW STAGE  
GAS PRESSURE 
REGULATOR ADJUSTMENT

MANIFOLD
PRESSURE TAP

INLET
PRESSURE TAP

ON/OFF SWITCH

REGULATOR SPRING

(Propane - White,
Natural - Silver)

HIGH STAGE GAS
PRESSURE REGULATOR
ADJUSTMENT

A07804

Fig. 6 -- Two--Stage Gas Valve

22. Install plastic adjust screw into the low stage gas regulator.

turn clockwise 9.5 turns (see Fig. 6).

23. Verify igniter, flame sensor, orifice/main burner

relationship prior to completing conversion. (See Fig. 4.)
Partially slide burner rack assembly into unit.

24. Disconnect the orange wire from the combustion air

pressure switch and connect it to the orange wire on the low
gas pressure switch (LGPS) equipped with a 1/4 in. male

quick--connect

terminal. The low gas pressure switch

should have one unconnected orange wire remaining.

Connect this wire to the vacant terminal on the combustion
air pressure switch (see Fig. 8).

25. Reconnect the violet wires removed in item 5 to the rollout

switch and reinstall the rollout switch.

26. Reconnect orange sparker cable to sparker and reconnect

the white flame sensor wire to the flame sensor.

27. Reconnect the remaining wires removed in item 5 to the gas

valve. Connect the gray wires to (HI). Connect the blue

wires to (M). Connect the brown and green/yellow wires to
(C).

28. Slide burner rack assembly into base pan. Align burner rack

with screws on sheet metal partition and slide assembly
back tight to the partition. Replace the screw attaching the

burner rack to the base pan removed in step 4. If the Fan
partition mounting bracket was removed, slide bracket back

into placed and fasten with 2 screws. (See Fig. 2.)

29. Reconnect the brown wire from the burner assembly to the

fan partition panel, using the ground screw saved from Step
8.

30. Remove the 1/8 in. pipe plug on the gas manifold and

connect a pressure manometer (see Fig. 5).

31. Reconnect electrical power and gas supply to the unit. For

propane applications, the gas pressure must not be less than

11.0 IN. W.C. or greater than 13 IN. W.C. at the unit
connection. A 1/8--in. NPT plugged tapping, accessible for
test gauge connection, must be installed immediately

upstream of the gas supply connection to the gas valve and
downstream of manual equipment shutoff valve.

The newly installed low gas pressure switch is a safety device used
to guard against adverse burner operating characteristics that can

result from low gas supply pressure. Switch opens at not less than
6.5 IN. W.C. and closes at not greater than 10.2 IN. W.C.
This switch also prevents operation when the propane tank level is

low which can result in gas with a high concentration of impurities,
additives, and residues that have settled to the bottom of the tank.

Operation under these conditions can cause harm to the heat
exchanger system.
This normally open switch closes when gas is supplied to gas valve
under normal operating pressure. The closed switch completes

control circuit. Should an interruption or reduction in gas supply

occur, the gas pressure at switch drops below low gas pressure
switch setting, and switch opens. Any interruption in control

circuit (in which low gas pressure switch is wired) quickly closes
gas valve and stops gas flow to burners.

FIRE AND EXPLOSION HAZARD

Failure to follow this warning could result in personal

injury and/or property damage.
Never test for gas leaks with an open flame. Use a

commercially available soap solution made specifically for

the detection of leaks to check all connections.

!

WARNING

IMPORTANT

: Restart unit and leak check all gas connections

including the main service connection, gas valve, gas spuds, and
manifold pipe plug. All leaks must be repaired before firing unit.

32. Fire unit and verify proper ignition and proper sequence of

operation (Table 2). See Table 4 for proper low stage and

high stage manifold pressure settings for your unit. Adjust
the gas valve setting for high and low stages by turning the
plastic adjustment screws clockwise to increase pressure and

counter--clockwise to decrease pressure for the respective
stages. Refer to Table 3 for required rated heating input

rates. Replace regulator cover screws when finished (see
Fig. 6).

33. With control access panel removed, observe unit heating

operation in both low stage operation and high stage opera-
tion. Watch burner flames to see if they are blue in appear-

ance, and that the flames are approximately the same for
each burner (see Fig. 9).

34. Turn off unit, remove pressure manometer and replace the

1/8 in. pipe fitting on the gas manifold (see Fig. 5).

35. Attach warning label (P/N 48DU500076) to visible side of

gas valve.

36. Attach conversion label (P/N 48VL500206) above unit

rating plate on exterior of unit.

37. Attach completed conversion responsibility label (see Fig.

10, P/N 48VL500207) inside control access panel.

CPL

P

CONV

Summary of Contents for CPLPCONV013A00

Page 1: ...and in instructions or manu als be alert to the potential for personal injury Understand these signal words DANGER WARNING and CAUTION These words are used with the safety alert symbol DANGER identifi...

Page 2: ...MUST be shut off before disconnecting electrical power and proceeding with conversion WARNING ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death Before in...

Page 3: ...er access to the burner assembly The bracket may be removed by removing 2 screws on the control side and sliding the bracket forward bottom first If the fan partition bracket was removed slide bracket...

Page 4: ...e four screws saved from item 11 15 Remove the plug on the inlet end of the gas valve using a 3 16 in hex wrench 16 Install the 1 8 in NPT x 3 4 in 19 mm close pipe nipple where the plug was removed s...

Page 5: ...re switch is a safety device used to guard against adverse burner operating characteristics that can result from low gas supply pressure Switch opens at not less than 6 5 IN W C and closes at not grea...

Page 6: ...E ORIFICE 2 FLAME SENSOR MANIFOLD 40 000 BTUH UNITS CLOSED END PIPE PLUG CLOSED END BURNER 3 BURNER RACK SPARKER FLAME SENSOR ORIFICE 3 MANIFOLD 60 000 BTUH PIPE PLUG CLOSED END GAS VALVE LO HI O FF O...

Page 7: ...igniter is de energized and a 2 sec flame proving period begins NOTE The unit always lights on high speed inducer and low stage gas valve operation Flame Proving When the burner flame is proved at the...

Page 8: ...ks to check all connections A fire or explosion could result causing property damage personal injury and or loss of life WARNING 38 After all leaks are eliminated replace control access panel EXPLOSIO...

Page 9: ...8 NPTx 3 4 IN 19 1 MM CLOSE PIPE NIPPLE 1 8 ELBOW 1 8 ELBOW 1 8 NPTx 3 4 IN 19 1 MM CLOSE PIPE NIPPLE 1 8 NPTx 2 IN 50 8 MM NIPPLE LOW GAS PRESSURE SWITCH TWO A09016 Fig 11 Installing Elbows Nipples...

Page 10: ...easier access to the burner assembly The bracket may be removed by removing 2 screws located on the left side of the control compartment on the fan partition panel and sliding the bracket forward bott...

Page 11: ...on air pressure switch and connect it to the orange wire on the low gas pressure switch LGPS equipped with a 1 4 in male quick connect terminal The low gas pressure switch should have one unconnected...

Page 12: ...Fig 15 Single Stage Orifice Installation 1 2 3 4 5 6 7 8 9 10 11 12 LGPS PLUG J2 FURNACE CONTROL BOARD LEGEND ORN ORANGE YEL YELLOW LGPS LOW GAS PRESSURE SWITCH CAPS COMBUSTION AIR PRESSURE SWITCH ORN...

Page 13: ...occur the gas pressure at switch drops below low gas pressure switch setting and switch opens Any interruption in control circuit in which low gas pressure switch is wired quickly closes gas valve and...

Page 14: ...l 45 sec to energize the indoor blower motor On removal of the call for heat the gas valve will immediately shut down the inducer motor will run for an additional 5 sec and the indoor blower will run...

Page 15: ...ELBOW LOW GAS PRESSURE SWITCH 1 8 NPTx 2 IN 50 8 MM NIPPLE 1 8 NPTx 3 4 19 1MM CLOSE PIPE NIPPLE 1 8 NPTx 3 4 IN 19 1 MM CLOSE PIPE NIPPLE A09017 Fig 19 Installing Elbows Nipples and Pressure Switch o...

Page 16: ...St D Indianapolis IN 46231 Printed in U S A Edition Date 04 10 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No IIK CP...

Reviews: