Table 5A — Compressor Electrical Data, 30HXC Units (cont)
LEGEND
*Units are shipped with wye-delta start as standard. Across-the-line start is not available.
UNIT SIZE
30HXC
NAMEPLATE
V-Hz (3 Phase)
COMPRESSOR NUMBERS
A1
B1
RLA
LRA
RLA
LRA
161-XL
208/230-60
*
*
*
*
230-60
*
*
*
*
460-60
103.1
685
71.2
525
575-60
82.4
548
56.9
420
380-60
124.8
757
86.2
580
230-50
*
*
*
*
380/415-50
128.6
856
88.2
600
161-WD
208/230-60
228.8
433
157.6
350
230-60
314.6
743
212.3
527
460-60
103.1
216
71.2
175
575-60
82.4
173
56.9
140
380-60
124.8
239
86.2
193
230-50
212.5
432
145.7
348
380/415-50
128.6
270
88.2
200
171-XL
208/230-60
*
*
*
*
230-60
*
*
*
*
460-60
86.1
580
103.1
685
575-60
68.8
484
82.4
548
380-60
104.2
641
124.8
757
230-50
*
*
*
*
380/415-50
105.8
715
128.6
856
171-WD
208/230-60
190.6
367
228.8
433
230-60
258.2
581
314.6
743
460-60
86.1
183
103.1
216
575-60
68.8
147
82.4
173
380-60
104.2
203
124.8
239
230-50
174.8
361
212.5
432
380/415-50
105.8
233
128.6
270
186-XL
208/230-60
*
*
*
*
230-60
*
*
*
*
460-60
103.1
685
103.1
685
575-60
82.4
548
82.4
548
380-60
124.8
757
124.8
757
230-50
*
*
*
*
380/415-50
128.6
856
128.6
856
186-WD
208/230-60
228.8
433
228.8
433
230-60
314.6
743
314.6
743
460-60
103.1
216
103.1
216
575-60
82.4
173
82.4
173
380-60
124.8
239
124.8
239
230-50
212.5
432
212.5
432
380/415-50
128.6
270
128.6
270
LRA
—
Locked Rotor Amps
RLA
—
Rated Load Amps
WD
—
Wye-Delta Start
XL
—
Across-the-Line Start