Table 4B — Electrical Data, 30HXA Units

LEGEND

*Units with one MCA, MOCP, and fuse size value have one terminal block and

require one power supply. Units with two MCA, MOCP, and fuse values have
2 terminal blocks.

†Wye-delta start is standard. Not available in across-the-line start.
NOTES:
1. Main power must be supplied from a field-supplied fused electrical service

with a (factory- or field-installed) disconnect located in sight from the unit.

2. Control circuit power must be supplied from a separate source through a

field-supplied disconnect (except for 380/415-50 units). An accessory con-
trol transformer may be used to provide control circuit power from the main
unit power supply.

3. Maximum incoming wire size for each terminal block is 500 kcmil.
4. Maximum allowable phase imbalance is: voltage, 2%; amps, 5%.
5. Use copper conductors only.

6. The MOCP is calculated as follows:

MOCP = (2.25) (largest RLA) + the sum of the other RLAs. Size the fuse
one size down from the result. The RLAs are listed on the unit nameplate.

7. The recommended fuse size in amps (RFA) is calculated as follows:

RFA = (1.50) (largest RLA) + the sum of the other RLAs. Size the fuse one
size up from the result. The RLAs are listed on the unit nameplate.
Units have the following power wiring terminal blocks and parallel
conductors:

UNIT

30HXA

UNIT VOLTAGE

POWER CIRCUIT*

CONTROL CIRCUIT

V-Hz

(3 Ph)

Supplied

Power

Supply

Qty

Req’d

No. of

Power Supply

Conductors

Req’d

MCA

MOCP

ICF

Recommended

Fuse Size

V-Hz

(Single Ph)

Supplied

MCA

and

MOCP

Min

Max

XL

WD

Min

Max

076

230-60

207

253

1

3

291.2

400

436.4

350

115-60

104

127

15

208/230-60

187

253

1

3

323.6

450

450.8

400

115-60

104

127

15

460-60

414

506

1

3

146.0

200

549.9

217.9

175

115-60

104

127

15

575-60

518

633

1

3

116.8

150

439.9

174.9

150

115-60

104

127

15

380-60

342

418

1

3

177.1

250

614.7

247.7

200

230-60

207

254

15

380/415-50

342

440

1

3

183.4

250

686.5

272.5

225

230-50

198

254

15

230-50

207

253

1

3

303.3

400

439.8

350

230-50

207

254

15

086

230-60

207

253

1

3

322.8

450

496.4

400

115-60

104

127

15

208/230-60

187

253

1

3

358.7

500

510.8

450

115-60

104

127

15

460-60

414

506

1

3

161.9

225

644.9

247.9

200

115-60

104

127

15

575-60

518

633

1

3

129.5

175

535.9

198.9

150

115-60

104

127

15

380-60

342

418

1

3

196.2

250

719.7

281.7

225

230-60

207

254

15

380/415-50

342

440

1

3

205.5

300

796.5

307.5

250

230-50

198

254

15

230-50

207

253

1

3

339.7

500

495.8

400

230-50

207

254

15

096

230-60

207

253

1

3

365.4

500

562.4

450

115-60

104

127

15

208/230-60

187

253

1

6

406.1

600

576.8

500

115-60

104

127

15

460-60

414

506

1

3

183.4

250

749.9

280.9

225

115-60

104

127

15

575-60

518

633

1

3

146.5

200

599.9

224.9

175

115.60

104

127

15

380-60

342

418

1

3

221.1

300

835.7

317.7

300

230-60

207

254

15

380/415-50

342

440

1

3

231.4

350

937.5

351.5

300

230-50

198

254

15

230-50

207

253

1

6

382.6

500

566.8

450

230-50

207

254

15

106

230-60

207

253

1

6

416.9

600

647.4

500

115-60

104

127

15

208/230-60

187

253

1

6

463.2

700

661.8

600

115-60

104

127

15

460-60

414

506

1

3

209.2

300

884.9

323.9

250

115-60

104

127

15

575-60

518

633

1

3

167.2

250

707.9

258.9

200

115-60

104

127

15

380-60

342

418

1

3

253.3

350

984.7

364.7

300

230-60

207

254

15

380/415-50

342

440

1

3

263.3

400

1041.5

384.5

300

230-50

198

254

15

230-50

207

253

1

6

435.1

600

619.8

500

230-50

207

254

15

116

230-60

207

253

1

6

442.1

600

672.7

500

115-60

104

127

15

208/230-60

187

253

1

6

491.3

700

689.9

600

115-60

104

127

15

460-60

414

506

1

3

221.9

300

897.6

336.6

300

115-60

104

127

15

575-60

518

633

1

3

177.4

250

718.1

269.1

225

115-60

104

127

15

380-60

342

418

1

3

268.6

400

1000.0

380.0

350

230-60

207

254

15

380/415-50

342

440

1

3

281.0

400

1059.2

402.2

350

230-50

198

254

15

230-50

207

253

1

6

464.2

700

648.9

600

230-50

207

254

15

126

230-60

207

253

1

6

476.3

700

706.8

600

115-60

104

127

15

208/230-60

187

253

1

6

529.2

700

727.8

600

115-60

104

127

15

460-60

414

506

1

3

239.1

350

914.8

353.8

300

115-60

104

127

15

575-60

518

633

1

3

191.0

250

731.7

282.7

225

115-60

104

127

15

380-60

342

418

1

3

289.3

400

1020.7

400.7

350

230-60

207

254

15

380/415-50

342

440

1

3

301.7

400

1079.9

422.9

350

230-50

198

254

15

230-50

207

253

1

6

498.5

700

683.2

600

230-50

207

254

15

136

230-60

207

253

1

6

539.1

800

769.8

700

115-60

104

127

15

208/230-60

187

253

1

6

599.1

800

790.8

700

115-60

104

127

15

460-60

414

506

1

3

270.7

400

1014.8

385.8

350

115-60

104

127

15

575-60

518

633

1

3

216.2

300

811.7

308.7

250

115-60

104

127

15

380-60

342

418

1

3

327.5

450

1131.7

435.7

400

230-60

207

254

15

380/415-50

342

440

1

3

343.4

500

1345.9

506.9

300

230-50

198

254

15

230-50

207

253

1

6

567.3

800

817.2

700

230-50

207

254

15

146

230-60

207

253

1

6

580.3

800

811.0

700

115-60

104

127

15

208/230-60

187

253

1

6

644.8

800

836.5

800

115-60

104

127

15

460-60

414

506

1

3

291.3

400

1035.4

406.4

350

115-60

104

127

15

575-60

518

633

1

3

232.7

300

828.2

325.2

300

115-60

104

127

15

380-60

342

418

1

3

352.5

500

1156.7

460.7

400

230-60

207

254

15

380/415-50

342

440

1

3

358.9

500

1371.4

532.4

450

230-50

198

254

15

230-50

207

253

1

6

609.3

800

859.2

700

230-50

207

254

15

FLA

Full Load Amps

ICF

Maximum Instantaneous Current Flow during start-up (the
point in the starting sequence where the sum of the LRA for the
start-up compressor, plus the total RLA for all running com-
pressors, plus the total FLA for all running fan motors is at a
maximum)

LRA

Locked Rotor Amps

MCA

Minimum Circuit Ampacity (for wire sizing)

MOCP  —

Maximum Overcurrent Protection

RLA

Rated Load Amps

WD

Wye-Delta Start

XL

Across-the-Line Start

VOLTAGE

TERMINAL BLOCKS

OR NON-FUSED

DISCONNECTS

CONDUCTORS

208/230

(Sizes 076-171)

1

6

208/230

(Sizes 186-271)

2

6

460

1

3

575

1

3

380

1

3

230 (Sizes 076-171)

1

6

230 (Sizes 186-271)

2

6

380/415

1

3

Summary of Contents for ComfortLink 30HXA076

Page 1: ...1 6 0 4 01 6 1 2 3 6 69 8 7 06 8 7 96 6 0 1 4 7 2 3 INTRODUCTION 1 0 6 06 6 68 2 01 9 1 0 6 0 06 6 9 1 8 0 6 7 6 6 INSTALLATION Step 1 Inspect Shipment 0 86 3 6 8 3 86 8 0 3 9 1 1 1 063 7 1 9 7 6 6 6...

Page 2: ...0 826 65 22 1657 30HXC106 54 12 1375 37 63 956 33 50 851 67 22 1707 NOTES 1 Denotes center of gravity 2 Dimensions are in inches mm and weights are in lb kg 3 36 in 914 4 recommended service clearance...

Page 3: ...ions are in inches mm and weights are in lb kg 3 36 in 914 4 recommended service clearance around machine 4 Victaulic nozzles are standard on all models Flow switch factory installed in cooler inlet v...

Page 4: ...6 in 914 4 recommended service clearance around machine 4 Victaulic nozzles are standard on all models Flow switch factory installed in cooler inlet victaulic nozzle NOTE See Fig 10 for weight distrib...

Page 5: ...0HXC246 34 38 873 30HXC261 34 38 873 30HXC271 34 38 873 NOTES 1 Denotes center of gravity 2 Dimensions are in inches mm and weights are in lb kg 3 36 in 914 4 recommended service clearance around mach...

Page 6: ...72 145 44 81 1138 46 25 1175 30HXA096 8 48 215 54 12 1375 37 63 956 32 50 826 43 50 1105 65 22 1657 21 15 537 42 77 1086 5 72 145 53 06 1348 38 00 965 30HXA106 10 48 266 54 12 1375 37 63 956 33 50 851...

Page 7: ...ounting points NOTES 1 Denotes center of gravity 2 Dimensions are in inches mm and weights are in lb kg 3 36 in 914 4 recommended service clearance around machine 4 Victaulic nozzles are standard on a...

Page 8: ...ne 4 Victaulic nozzles are standard on all models Flow switch factory installed in cooler inlet victaulic nozzle UNIT A B C E F 30HXA161 72 12 1832 50 63 1286 47 56 1208 71 06 1830 50 00 1270 30HXA171...

Page 9: ...sions are in inches mm and weights are in lb kg 3 36 in 914 4 recommended service clearance around machine 4 Victaulic nozzles are standard on all models Flow switch factory installed in cooler inlet...

Page 10: ...suit and cover insulate remaining open area for acoustic purposes 6 Recommended control wiring entry area Notch to suit and cover insulate remaining open area for acoustic purposes 7 Recommended coole...

Page 11: ...1201 545 3133 1421 1650 748 246 985 447 2515 1141 1306 592 1154 523 3276 1486 1733 786 261 985 447 2520 1143 1311 595 1154 523 3283 1489 1739 789 271 985 447 2529 1147 1318 598 1154 523 3294 1494 174...

Page 12: ...0 300 Fluid Connections Inlet and Outlet in 4 4 4 5 4 4 4 4 Drain in NPT 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 Relief Valve Connection in NPTF 3 4 3 4 3 4 3 4 3 4 3 4 3 4 3 4 Flow Capacity lb air min 31 7 3...

Page 13: ...220 220 Maximum Fluid Side Pressure psig 300 300 300 300 300 300 300 Fluid Connections Inlet and Outlet in 5 5 5 6 6 6 6 Drain NPT 1 2 1 2 1 2 3 4 3 4 3 4 3 4 Relief Valve Connection in NPTF 3 4 3 4 3...

Page 14: ...2068 2068 2068 2068 2068 2068 2068 2068 Fluid Connections Inlet and Outlet in 4 4 4 5 4 4 4 4 Drain NPT 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 Relief Valve Connection in NPTF 3 4 3 4 3 4 3 4 3 4 3 4 3 4 3 4...

Page 15: ...mum Fluid Side Pressure kPa 2068 2068 2068 2068 2068 2068 2068 Fluid Connections Inlet and Outlet in 5 5 5 6 6 6 6 Drain NPT 1 2 1 2 1 2 3 4 3 4 3 4 3 4 Relief Valve Connection in NPTF 3 4 3 4 3 4 3 4...

Page 16: ...9 01 D 6 6 8 86 1 363 8 1 6 16 4 6 3 8 63 1 9 655 6 16 6 1 3 3 4 5 6 9 1 8 16 33 6 1 00 6 7 0 0 7 06 0 6 4 6 69 1 06 0 6 0 6 6 9 1 1 00 6 7 16 1 066 1 0633 1 8 4 1 7 3 6 8 0 0 1 688 4 0 16 6 4 6 8 0 0...

Page 17: ...drawings 2 All wiring must comply with applicable codes 3 Refer to Carrier System Design Manual for details regarding piping techniques 4 Piping wiring switches valves vent gages strainers drain and...

Page 18: ...gs 2 Refer to Carrier System Design Manual for details regarding piping techniques 3 Piping and pressure relief devices are field supplied 4 Vent pipes properly per local codes Fig 13A Typical 30HXA R...

Page 19: ...7 9 1 1 8 6 1 H 06 6 86 6 1 60 6 6 68 1 9 01 0 1 9 01 0 6 4 6 8 1 9 01 1 9 1 1 H 06 86 6 6 3 4 1 9 01 1 9 1 1 01 6 H D 9 01 6 D I 0 6 I 0 F 1 4 0 9 1 36 8 1 36 6 1 6 6 1 3 0 7 4 5 91 1 01 69 1 6 6 1...

Page 20: ...0 6 6 1 06 6 0 4 6 3 6 88 1 6 3 06 1 36 86 3 0 6 1 91 6 9 1 6 0 6 1 9 655 6 06 36 46 6 9 8 36 8 8 63 06 9 1 6 4 8 63 1 1 01 1 6 1 4 9 1 9 8 1 8 1 6 1 1 4 60 688 1 8 06 0 6 36 1 86 3 4 60 1 06 0 6 3 7...

Page 21: ...EQUIVALENT LINE LENGTH FT 30 40 50 60 70 80 90 105 141 176 211 246 281 316 100 110 120 130 140 150 352 387 422 457 492 527 TONS COOLING kW COOLING 160 170 180 190 200 562 598 633 668 703 3 1 8 79 4 mm...

Page 22: ...6 6 8 7 6 86 01 0 8 6 8 2 6 6 0 1 8 69 7 9 7 1 00 6 7 0 6 0 1 6 1 1 8 1 60 6 1 01 4 9 1 3 88 1 01 1 688 1 60 06 Step 4 Make Electrical Connections 1 0 0 01 0 0 68 1 4 69 7 3 9 1 1 3 7 6 3 4 9 1 1 3 1...

Page 23: ...RED FOR BRINE APPLICATIONS TO PREVENT CONDENSER FREEZE UP BYPASS VALVE OPTIONAL BYPASS VALVE FOR NORMAL DUTY BYPASS VALVE REQUIRED FOR BRINE APPLICATIONS TO PREVENT CONDENSER FREEZE UP 4 to 20 mA WATE...

Page 24: ...ater Pump CWP Chilled Water Pump CWPI Chilled Water Pump Interlock EMM Energy Management Module EWT Entering Fluid Temperature HPC Head Pressure Control LLSV Liquid Line Solenoid Valve LWT Leaving Flu...

Page 25: ...69 69 7 2 1 3 3 3 6 69 86 1 7 D 1 6 6 Step 5 Install Accessories 6 6 06 6 00 6 4 6 6 1 86 69 8 6 6 86 3 66 3 60 66 3 06 6 36 1 0 7 36 3 36 6 688 69 06 6 00 07 01 3 3 06 6 2 36 3 6 3 2 36 6 06 6 6 9 6...

Page 26: ...342 440 1 3 157 9 225 561 8 215 8 200 230 50 198 254 15 230 50 207 253 1 3 260 7 350 347 1 300 230 50 207 254 15 106 230 60 207 253 1 3 285 6 400 395 3 350 115 60 104 127 15 208 230 60 187 253 1 3 317...

Page 27: ...0 115 60 104 127 15 460 60 414 506 1 3 232 0 300 788 1 319 1 300 115 60 104 127 15 575 60 518 633 1 3 185 4 250 630 4 255 4 225 115 60 104 127 15 380 60 342 418 1 3 280 8 400 881 8 363 8 350 230 60 20...

Page 28: ...37 5 351 5 300 230 50 198 254 15 230 50 207 253 1 6 382 6 500 566 8 450 230 50 207 254 15 106 230 60 207 253 1 6 416 9 600 647 4 500 115 60 104 127 15 208 230 60 187 253 1 6 463 2 700 661 8 600 115 60...

Page 29: ...127 15 380 60 342 418 1 6 430 2 600 1490 2 601 2 500 230 60 207 254 15 380 415 50 342 440 1 6 452 7 600 1466 2 601 2 600 230 50 198 254 15 230 50 207 253 1 6 747 7 1000 970 3 1000 230 50 207 254 15 2...

Page 30: ...209 98 1 209 230 60 154 7 367 129 4 307 460 60 53 6 104 44 3 104 575 60 42 8 83 35 4 83 380 60 64 9 115 53 7 115 230 50 111 8 213 92 1 174 380 415 50 67 7 134 55 8 109 096 XL 208 230 60 230 60 460 60...

Page 31: ...144 9 256 230 60 230 0 518 188 8 433 460 60 79 2 153 65 5 128 575 60 63 3 123 52 3 102 380 60 95 9 169 79 2 141 230 50 161 7 305 134 9 255 380 415 50 97 8 191 81 7 160 136 XL 208 230 60 230 60 460 60...

Page 32: ...71 XL 208 230 60 230 60 460 60 86 1 580 103 1 685 575 60 68 8 484 82 4 548 380 60 104 2 641 124 8 757 230 50 380 415 50 105 8 715 128 6 856 171 WD 208 230 60 190 6 367 228 8 433 230 60 258 2 581 314 6...

Page 33: ...216 71 2 175 103 1 216 575 60 82 4 173 56 9 140 82 4 173 380 60 124 8 239 86 2 193 124 8 239 230 50 212 5 432 145 7 348 212 5 432 380 415 50 128 6 270 88 2 200 128 6 270 261 XL 208 230 60 230 60 460 6...

Page 34: ...3 8 307 230 60 106 7 209 88 3 209 460 60 77 6 183 64 9 153 575 60 62 1 147 51 9 123 380 60 94 0 203 78 7 169 230 50 163 9 361 134 8 305 380 415 50 99 2 226 81 5 191 096 XL 208 230 60 230 60 460 60 94...

Page 35: ...47 230 60 157 9 307 130 4 256 460 60 115 4 259 94 8 216 575 60 92 2 207 75 7 173 380 60 139 7 286 114 7 239 230 50 240 2 485 198 2 432 380 415 50 145 4 303 119 9 270 136 XL 208 230 60 230 60 460 60 14...

Page 36: ...208 230 60 230 60 460 60 129 6 920 157 9 1175 575 60 103 6 736 126 2 940 380 60 156 9 1017 191 2 1299 230 50 380 415 50 161 7 1226 201 2 1265 171 WD 208 230 60 286 9 581 349 6 743 230 60 171 5 367 20...

Page 37: ...06 6 259 157 9 371 575 60 126 2 297 85 1 207 126 2 297 380 60 191 2 410 129 0 286 191 2 410 230 50 332 3 638 220 3 485 332 3 638 380 415 50 201 2 400 133 4 303 201 2 400 261 XL 208 230 60 230 60 460 6...

Page 38: ...06 76 1 01 0 0 9 1 6 1 1 06 066 3 6 8 5 5 3 06 4 3 7 6 1 9 7 7 3 01 1 1 01 9 1 1 1 066 8 06 3 6 6 4 063 6 3 1 1 69 06 3 6 UNIT 30HXA CIRCUIT A CHARGE CIRCUIT B CHARGE lb kg lb kg 076 75 34 0 75 34 0 0...

Page 39: ......

Page 40: ...ontinue or change at any time specifications or designs without notice and without incurring obligations PC 903 Catalog No 533 012 Printed in U S A Form 30HX 8SI Pg 40 8 00 Replaces 30HX 7SI Book 2 Ta...

Reviews: