106
PRE--COOLING SCHEDULES
Pre--Cooling Default Settings
Default settings for Pre--Cooling 1 and 2 (PC1and PC2) would be as follows:
PC1
START = 1pm, OFFSET = 2 degrees, DURATION = 1 hour
PC2
START = 11am, OFFSET = 0 degrees, DURATION = 0 hour
When user tries to setup pre--cool settings, defaults should be pretty close to what
may be expected. After the above settings for pre--cooling are configured, the
user would use the NEXT button to select the dates in which to run these
pre--cool settings.
Modifying Pre--Cooling Date Settings:
The user would then see the two screens below which allow them to select
START and END dates they wish to have pre--cooling run. This allows for a one
time setup of the summer months if desired. After making that selection, use the
NEXT button to complete the setup or CANCEL if you wish to quit.
A14014
Fig. 71 -- Pre--Cooling Time Period Setting