PERFORMANCE AND ELECTRICAL DATA
MODEL 52CE (265-1-60)
LEGEND
EER —
Energy Efficiency Ratio
*Rated in accordance with ARI Standard 310-93.
†Electric resistance heater power and fan motor power.
**All 265-v units require an electrical subbase (receptacle or hard-
wire model).
RECEPTACLES AND FUSE TYPES
LEGEND
MODEL
NUMBER
52CE
CAPACITY* (Btuh)
HEATER
kW
EER
VOLTAGE
RANGE
(Volts)
AMPS
WATTS
Cooling
Heating
Cooling
Heating†
Cooling
Heating
207---4
7,000
7,800
2.3
11.1
239-292
2.4
9.2
631
2396
307---4
7,000
11,600
3.4
11.1
2.4
13.3
631
3496
209---4
8,900
7,800
2.3
10.7
3.1
9.2
832
2396
309---4
8,900
11,600
3.4
10.7
3.1
13.3
832
3496
212---4
12,000
7,800
2.3
10.1
4.6
9.4
1188
2470
312---4
12,000
11,600
3.4
10.1
4.6
13.5
1188
3570
512---4
12,000
17,000
5.0
10.1
4.6
19.6
1188
5170
215---4
14,500
7,800
2.3
9.4
6.0
9.7
1543
2517
315---4
14,500
11,600
3.4
9.4
6.0
13.8
1543
3617
515---4
14,500
17,000
5.0
9.4
6.0
19.9
1543
5217
MODEL
NUMBER
52CE
POWER
FACTOR
%
FAN MOTOR
MAX. FUSE
SIZE
(Amps)
MIN.
CIRCUIT
AMPS
RECEP-
TACLE
TYPE**
R-22
CHARGE
(oz)
DEHUMIDI-
FICATION
(Pints/Hr)
SENSIBLE
HEAT
FACTOR
APPROX.
CHASSIS
SHIP WT
(lb)
Horsepower
Full
Load
Amps
Indoor
CFM
LO/HI
207---4
97
0.075
0.46
220/260
15
11.3
A
26
1.5
0.78
125
307---4
20
16.5
B
209---4
97
0.075
0.46
220/260
15
11.3
A
24
2.4
0.73
125
309---4
20
16.5
B
212---4
99
0.125
0.71
270/340
15
11.6
A
34
3.4
0.71
140
312---4
20
16.7
B
512---4
25
24.3
C
215---4
95
0.25
1.00
270/340
15
11.9
A
36
5.2
0.65
150
315---4
20
17.0
B
515---4
25
24.6
C
UNIT NAMEPLATE VOLTAGE
265
OUTLET RATED VOLTS/AMPS
277/15
277/20
277/30
OUTLET BLADE CONFIGURATION
A
B
C
NEMA CONFIGURATION
7-15R
7-20R
7-30R
TIME DELAY FUSE OR HACR
CIRCUIT BREAKER (AMPS)
15
20
30
HEATER (KILOWATTS)
2.3
3.4
5.0
HACR —
Heating, Air Conditioning, and Refrigeration
NEMA —
National Electrical Manufacturers Association