background image

ZONEBB3Z(AC/HP)01: Quick Reference Guide

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

2

Component Location and Wiring 

Considerations

Locating Bryant 3-Zone System

All  wiring  is  connected  back  to  the  Bryant  3-Zone  System.  Select  a

location near the furnace or fan coil where wiring from each thermostat,

each damper actuator, and the equipment itself can come together easily.
The Bryant 3-Zone System is approved for indoor use only and should

never be installed with any of its components exposed to the elements. It

may be installed in any area where the temperature remains between 32°

and 158°F, and there is no condensation. The cover must be installed to

prevent  damage  from  other  sources.  Do  not  locate  where  it  will  be

accessible to children. Remember that wiring access is likely the most

important consideration. 

Wiring Considerations

• All wiring in the Bryant 3-Zone system may be unshielded

• Ordinary thermostat wire is ideal

• Use 22 gage or larger for normal wiring

• Lengths over 100 ft should use 20 gage or larger wire

• Each damper actuator required 3 conductors

• The  connection  to  thermostat  and  equipment  (furnace  or  fan  coil)

could require as many as 8 conductors for a multi-state installation

• The 

Leaving  Air  Temperature  (LAT)

    and 

Heat  Pump  Temperature

(HPT)

-(used with heat pumps only) sensors require 2 conductors each

• Cables with excess conductors are acceptable

Step 1 – Mounting the Bryant 3-Zone System

The  Bryant  3-Zone  System  can  be  mounted  in  either  vertical  or

horizontal  position  near  the  HVAC  system  inside  the  home.  It  is

designed so that wires can enter it from behind, above, or below. Plan

wire routing before mounting.

Fig. 2 – Mounting the System

1. Remove  the  front  cover  from  the  base  and  use  the  base  as  a

template to mark drilling locations on the wall, stud , or roof truss.

2. Mount using 4 screws (and wall anchors) provided. (See 

Fig. 2

.)

3. Level for appearance and tighten screws.

Step 2 – Install Thermostats in each desired Zone 

Location

1. Install each thermostat according to the manufacturer’s instructions

in their designated Zone location.

2. Connect the thermostats wires to their respective Zone designation

on the right side of the the 3-Zone Panels. (See 

Fig. 3

).

Step 3 – Install Zone Dampers

Each  damper  has  3  connections: 

Close  (CLS)

Open  (OPN),

  and

Common (COM)

. Find the connection points along the lower left side

of  the  3-Zone  Control.  Suggested  colors  are  CLS  =  RED;  OPN  =

GREEN, COM = WHITE. Field label and make the connections at the

dampers  and  at  the  3-Zone  Control.  Be  careful  not  to  cross  zone

numbers.
If  duct  work  required  multiple  dampers  for  a  single  zone,  up  to  5

dampers may be wired in parallel and may be installed in any position.

WARNING

!

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury or death.

Turn off  unit  before  routing  control  wiring or any  service  operation.

Remember, there may be more than one power supply to unit.

CAUTION

!

EQUIPMENT DAMAGE HAZARD

Failure to follow this caution may result in equipment  damage.
To prevent possible damage to Bryant 3-Zone System, do not mount

control on plenum, duct work, or flush against furnace.

Summary of Contents for bryant ONEBB3ZAC01

Page 1: ... hr cph providing maximum equipment protection Selection Jumpers Designed for easy configuration Additional Options Timeguard override Compressor protection Modulating damper control in emergency situations Damper fuse protection High and low temperature limits Auto changeover from any zone RH and RC for voltage isolation Bypass setup routine Staging time for energy savings Automatic checkout with...

Page 2: ...stem The Bryant 3 Zone System can be mounted in either vertical or horizontal position near the HVAC system inside the home It is designed so that wires can enter it from behind above or below Plan wire routing before mounting Fig 2 Mounting the System 1 Remove the front cover from the base and use the base as a template to mark drilling locations on the wall stud or roof truss 2 Mount using 4 scr...

Page 3: ... detect a cooling overload condition and is connected to the LAT and LATC terminals Polarity does not matter Locate LAT sensor in main supply trunk after heating and cooling coil and before bypass damper and first branch Cycling on internal equipment limits is to be avoided because it over stresses and can shorten the life of the equipment The LAT limit setting should be selected to trip below the...

Page 4: ...tion Default OFF Optional Settings 1 Auto changeover time between heating and cooling or vice versa Auto changeover time ENABLED OFF Auto changeover time DISABLED 2 Together with dipswitch 3 determines chanegover time 20 minutes auto changeover time OFF 30 minutes auto changeover time ON 3 Multiplier for the modified time set on dipswitch 2 1 0 multiplier OFF 0 5 multiplier ON 4 Installer Test Mod...

Page 5: ...N R C Y Y2 G Rz C REV VALVE R C Y1 G W1 Y2 W2 O SWITCH 9 OFF SWITCH 10 OFF Rh Y1 G W1 Y2 W2 O R C Y G C Y Rc O O W R HP 2S 3 ZONE CONTROL ZONE 1 INPUT ZONE 1 2SACTS TAT EQIUPMENT PO WE R FURNACE OR FAN COIL LO COOL LO HEAT FA N R C G Rz C HI HEAT R C Y1 G W1 Y2 W2 O SWITCH 9 ON SWITCH 10 ON Rh Y1 G W1 Y2 W2 O R C Y1 G C Y1 Rc R Y Y2 HI COOL Y2 W2 Y2 2 SPEED AIR CONDITIONER HP 2S3 ZONECONTROL ZONE ...

Page 6: ...d designs without notice and without obligations 6 Training My Learning Center is your central location for professional residential HVAC training resources that help strengthen careers and businesses We believe in providing high quality learning experiences both online and in the classroom Access My Learning Center with your HVACpartners credentials at www mlctraining com Please contact us a myle...

Reviews: