e. Tank shall be insulated with
3
/
4
-in.
(19 mm) closed-cell, polyvinyl-chloride
foam with a maximum K factor of 0.28.
f. Tank shall be baffled to prevent tempera-
ture stratification.
g. Tank shall have NPT threaded connections.
h. Tank shall have vent and drain plugs acces-
sible from outside tank enclosure.
i. Internal heaters shall provide freeze protec-
tion to –20 F (–29 C). A separate 230/1/
60 power source is required.
16. BACnet™ Translator Control:
Unit shall be supplied with field-installed inter-
face between the chiller and a BACnet Local
Area Network (LAN, i.e., MS/TP EIA-485).
17. LON Translator Control:
Unit shall be supplied with field-installed inter-
face between the chiller and a Local Operat-
ing Network (LON, i.e., LonWorks FT-10A
ANSI/EIA-709.1).
18. Navigator™ Hand Held Display Module:
a. Portable hand held display module with a
minimum of 4 lines and 20 characters per
line, or clear English, Spanish, Portuguese
or French language.
b. Display menus shall provide clear language
descriptions of all menu items, operating
modes, configuration points and alarm
diagnostics. Reference to factory codes
shall not be accepted.
c. RJ-14 connection plug shall allow display
module to be connected to factory-installed
receptacle.
d. Industrial grade coiled extension cord shall
allow the display module to be moved
around the chiller.
e. Magnets shall hold the display module to
any sheet metal panel to allow hands-free
operation.
f. Display module shall have NEMA 4x hous-
ing suitable for use in outdoor environments.
g. Display shall have back light and contrast
adjustment for easy viewing in bright sun-
light or night conditions.
h. Raised surface buttons with positive tactile
response.
19. Touch Pilot™ display:
Unit shall be supplied with a remote mount
touch screen display for network attachment
to the chiller
20. GFI Convenience Outlet:
Shall be factory or field-installed or mounted
with easily accessible 115-v female receptacle.
Shall include 4 amp GFI receptacle.