background image

30RA/30RH Puron

GB - 8

Connections and water circuits

70

60

50

40

30

20

10

0

0,25

0,28

0,31

0,33

0,36

0,39

0,42

0,44

RA/RH 009

RA/RH 011

80

70

60

50

40

30

20

10

0

0,20

0,25

0,30

0,35

0,40

0,45

0,50

0,55

0,60

0,65

Available static pressure

Water flow rate l/s

60

50

40

30

20

10

0

0,17

0,19

0,22

0,25

0,28

0,31

0,33

RA 007

A

vailable static pressure

(kPa)

Water flow rate l/s

A

vailable static pressure

(kPa)

Water flow rate l/s

Water flow rate l/s

RA/RH 013

80

70

60

50

40

30

20

10

0

0,20

0,25

0,30

0,35

0,40

0,45

0,50

0,55

0,60

0,65

Water flow rate l/s

60

50

40

30

20

10

0

0,17

0,19

0,22

0,25

0,28

0,31

0,33

RA/RH 005

Correction factors for ethylene glycol

Ethylene glycol

10%

20%

30%

40%

Freezing
temperature

–4

°

C

–9

°

C

–15

°

C

–23

°

C

Capacity

0.996

0.991

0.983

0.974

Power input

0.990

0.978

0.964

1.008

Water flow rate

1.000

0.979

0.979

1.025

Pressure drop

1.003

1.010

1.020

1.033

Connections and water circuits

 The hydraulic circuit must be designed to ensure a steady water

flow through the evaporator at any time.

 The water pipes in the circuit must be well supported and firmly

fastened to ensure that they do not put a strain on the
connections to the unit.

 Water inlet and outlet are identified by a tag.

 Air purge and water drain are located at the inlet and outlet

connections and are closed by appropriate plugs.

 Pipes must have shut-off valves to permit emptying of the heat

exchanger without draining the whole system, as suggested in
the diagram.

Control of a boiler

With a PRO-Dialog configuration, the unit (if it is in heating mode)
can control the start-up of a boiler via the mother board output
signal (see Service Interface Manual).
If the boiler is operating, the unit water pump is stopped.

The boiler output is activated:

– in 30RA units, by selecting heating mode

– in 30RH units, by selecting heating mode with the unit in fault

condition or with the unit operating at very low outdoor
temperature (see Service Interface Manual).

Water circulating pump

A  single-phase, three-speed water circulating pump, to be
selected at installation, is installed inside the unit.
The water circulating pump, can be fitted with a water system
resistor (pressure drop) as indicated in the diagrams, keeping
water flow at the correct values.
If the system pressure drop is higher then the pump available
head, water flow to the unit and unit performances are reduced.

To reduce to minimum system pressure drop it is necessary:

- to reduce number of bends;

- to avoid elbow bends;

- to reduce the system extension to a minimum;

- to use pipes of the correct diameter.

To avoid possible damage due to water freezing, it is
recommended to install the water refill system inside the building.

It is recommend:

• to fit a replaceable filter of at least 10 mesh/cm

2

 in the water

inlet, especially with welded joint iron pipes.
Water changes or additions should be reduced, if possible, as
they contribute to oxidation and to calcium deposit formation.
If the unit is not used for a long period, rotor shaft seizure can
occur; the user should unblock the rotor:

• switch off the system;

• remove the rubber plug from the panel (NOT available in the

versions 30RA005 / 30RA005H / 30RA007 / 30RA007H /
30RA007-9 / 30RA007H9);

• unscrew the air purge cap on the pump;

• insert a screwdriver in the slot and turn the rotor shaft;

• reassemble the air purge cap;

• put the rubber plug back on the panel;

• switch on the system.

Legend:

III high speed

II

medium speed

I

low speed

Water temperature 20

°

C

60

50

40

30

20

10

0

0,17

0,19

0,22

0,25

0,28

0,31

0,33

RH 007

A

vailable static pressure

(kPa)

Water flow rate l/s

A

vailable static pressure

(kPa)

A

vailable static pressure

(kPa)

A

vailable static pressure

(kPa)

Summary of Contents for AQUASNAP JUNIOR 30RA

Page 1: ...AQUASNAP JUNIOR 30RA 30RH INSTALLATION MANUAL L L O Y D S R E G I S TER QUALIT Y A S S U R A N C E IS O 900 1...

Page 2: ...refrigerant cylinders have a dip tube which allows liquid to flow out of the cylinder in upright position The R 410A units must be charged with refrigerant in a liquid state Use a commercial type met...

Page 3: ...1200 Heat exchanger WELDED PLATES Water content l 0 66 0 85 0 94 1 22 1 50 0 66 0 85 0 94 1 22 1 50 Expansion tank capacity l 1 1 2 2 2 1 2 3 3 3 Nitrogen charge pressure kPa 350 350 350 350 350 350 3...

Page 4: ...60 450 Water circulating pump 230 1 50 Current input A 0 3 0 3 0 3 0 5 0 9 0 9 0 97 0 3 0 5 0 5 0 5 0 9 0 9 0 97 Capacitor F V 3 400 3 400 3 400 4 400 7 400 7 400 7 400 3 400 4 400 4 400 4 400 7 400 7...

Page 5: ...about 1 3 mWG This precaution prevents cavitation noise and damage to the bearings due to low water flow and insufficient bearing lubrication Table V Water flow System water content Diameter outside i...

Page 6: ...ain all chiller functions to the owner Leave this manual with the owner for consultation during future periodic maintenance The chiller and its components must be periodically inspected to check for l...

Page 7: ...obstruction of the unit air outlet and intake or any obstacle that is too close see minimum clearances required Installation on grassy ground or soft surfaces in these cases a solid foundation must b...

Page 8: ...1 2 F Gas Difference in height between water chiller and highest system point Water connections Water circuit recommended wiring 1 Brazed plate heat exchanger 2 Closed expansion tank 3 Circulating pu...

Page 9: ...tput is activated in 30RA units by selecting heating mode in 30RH units by selecting heating mode with the unit in fault condition or with the unit operating at very low outdoor temperature see Servic...

Page 10: ...ted in the wiring diagram WARNING The supply line of three phase units must be three phase plus neutral Omission of the neutral N line could damage the single phase supplies The wiring diagram for the...

Page 11: ...ASNAP JUNIOR remote control Main switch Time delay fuse or circuit breaker see table III Electrical data A B Unit electrical panel Terminal blocks Electronic board connectors Power supply 230 V 1ph 50...

Page 12: ...OOL switch S3 Dual SET POINT switch standard economy NOTE The contact rating must be greater than 20 mA 24 V ac Unit without accessory AQUASNAP JUNIOR remote control Unit electrical panel Terminal blo...

Page 13: ...delay fuse or circuit breaker see table III Electrical data Water refrigerant heat exchanger Evaporator Condenser Water inlet Chilled water outlet Water inlet Hot water outlet Gas Refrigerant The unit...

Page 14: ...sure switch 3 Low pressure transducer 4 Pressure service port 5 Accurater expansion device 6 Crankcase heater 7 Suction accumulator 8 Water inlet 9 Chilled water outlet 10 Hot water outlet 11 Reversin...

Page 15: ...ooling control setpoint This parameter is regulated by the control and factory set to an entering water temperature of 12 C The second set point default value is 14 C and it can be selected via the Se...

Page 16: ...utomatic Sensor out of range probe wire interruption or sensor fault 5 Air temperature probe fault Unit stopped Automatic Sensor out of range probe wire interruption or sensor fault 6 High pressure tr...

Page 17: ...essure too high Coil dirty or obstructed clean or remove obstructions Water flow rate is insufficient or the pump is faulty during heating replace Refrigerant charge too high drain some refrigerant se...

Page 18: ...L010126H39 0404 Via R Sanzio 9 20058 Villasanta MI Italy Tel 039 3636 1 The manufacturer reserves the right to change any product specifications without notice April 2004 Printed in Italy...

Reviews: