3. Power entry is at the right-hand side of the unit when fac-
ing the control box.
4. Maximum field wire sizes allowed by lugs on terminal
block/non-fused disconnect are listed in Table 12.
5. Terminals for field power supply are suitable for
copper conductors. Insulation must be rated 167 F (75 C)
minimum.
6. Units with high short circuit ratings and terminal block
option require that specific fuses be applied to achieve
this rating. Refer to Table 12.
Table 12 — Field Wiring Sizes
LEGEND
NOTES:
1. Wiring for main field supply must
b
e rated 75 C. Use copper
conductors only.
2. Units with high SCCR option and terminal
b
lock must use
approved fuses to meet high SCCR rating.
3. High SCCR option not availa
b
le on dual point unit.
CONNECTION TYPE
30RAP
UNIT SIZES
MCA RANGE
WIRE SIZE RANGE
MAXIMUM NUMBER
OF WIRES PER PHASE
HIGH SCCR FUSE
TYPE
TERMINAL BLOCK
010-060
MCA up to 175
14 AWG to 2/0 AWG
1
J, , T, RK1, RK5, G, CC
060-060
MCA 175.1 to 335
6 AWG to 400 kcmil
1
J, , T, RK1, RK5, G, CC
070-150
MCA up to 420
2 AWG to 600 kcmil
1
J, , T, RK1, RK5, G, CC
070-150
MCA 420.1 to 760
6 AWG to 500 kcmil
2
J, , T, RK1, RK5, G, CC
NON-FUSED
DISCONNECT
All
MCA up to 100
14 AWG to 3/0 AWG
1
—
All
MCA 100.1 to 250
6 AWG to 350 kcmil
1
—
All
MCA 250.1 to 600
3/0 AWG to 500 kcmil
2
—
AWG
—
American Wire Gage
MCA
—
Minimum Circuit Amps
SCCR —
Short Circuit Current Rating
Summary of Contents for AQUASNAP 30RAP010-150
Page 12: ...12 Fig 9A Unit Rigging Label Detail 010 060 Sizes a30 4916 ...
Page 14: ...14 a30 5733 Fig 10 Dimensions 30RAP010 and 015 Units ...
Page 15: ...15 a30 5734 Fig 11 Dimensions 30RAP018 030 Units ...
Page 16: ...16 a30 5735 Fig 12 Dimensions 30RAP035 060 Units ...
Page 17: ...17 Fig 13 Dimensions 30RAP070 090 Units a30 5731 ...
Page 18: ...18 Fig 14 Dimensions 30RAP100 115 Units a30 5730 ...
Page 19: ...19 a30 5732 Fig 15 Dimensions 30RAP130 150 Units ...
Page 54: ...54 Fig 33 Typical Main Power and Control Connections a30 5514 ...
Page 71: ......