background image

5

1 - INTRODUCTION

The 30XW-PZE / 30XWHPZE units are designed to cool water 

(or brine) for the air conditioning of buildings and industrial 

processes.
Prior to the initial start-up of the 30XW-PZE / 30XWHPZE units, 

the people involved in the on-site installation, start-up, operation, 

and maintenance of this unit must be thoroughly familiar with these 

instructions and the specific project data for the installation site 

(Machine room, etc).
They are designed for an operating life of 15 years by assuming a 

75% utilisation factor; that is approximately 100,000 operating hours.
This manual provides the necessary information to familiarize 

yourself with the control system before performing start-up 

procedures. The procedures in this manual are arranged in the 

sequence required for machine installation, start-up, operation 

and maintenance.
Always ensure that all required safety measures are followed, 

including those in this document, such as: wearing protective 

clothing (gloves, safety glasses and shoes) using appropriate tools, 

employing qualified and skilled technicians (electricians, refrigeration 

engineers) fully trained in the use of flammable refrigerants and 

following local regulations (see annexe E in EN 378 -4 - Guidelines 

for repairs of equipment using flammable refrigerants).
To  find  out,  if  these  products  comply  with  European  directives 

(machine safety, low voltage, electromagnetic compatibility, 

equipment under pressure etc.) check the declarations of 

conformity for these products. 

According  to  ISO-817,  R-1234ze(E)  is  classified  in  safety 

group A2L: lower flammability. One of the characteristic of 

this refrigerant is the absence of flammable mixture with air 

under 21°C of ambiance and controlled humidity conditions. 

However  when  humidity  or  temperature  goes  up,  this 

refrigerant  can  become  flammable  and  can  represent  a 

potential  danger  if  flammability  risks  are  not  properly 

mitigated within the machine room installation.
Local building codes and safety standards shall be followed. 

In absence of local codes and standards, please refer to EN-

378 (2012) (Safety requirements for substances classified A2) 

or to ISO-5149 (2014)  (for substances classified A2L) as a 

guide. Customer shall obtain approval from the local building 

authorities.

For  further  details  on  physical  properties,  flammability  & 

toxicity  characteristics,  hazards  Identification,  installation 

safety requirements, etc, refer to standards such as: 

• 

ASHRAE 34, EN 378, ISO-817 and ISO-5149.

• 

Safety  Data  Sheet  (SDS)  supplied  by  the  refrigerant 

manufacturer.

• 

European  union’s  REACH  database  (Registration, 

Evaluation, Authorisation and Restriction of Chemicals).

As R-1234ze(E) refrigerant is mildly flammable, an ATEX perimeter 

of 0,6 m must be put in place around the machine (see § 3 - 

Dimensions, Clearances). No source of ignition must be present 

within this zone (see standard EN 378-2, Appendix K).

If an ignition  source is identified  in the hazard area, additional 

ventilation is compulsory. Implement a no smoking area around 

the machine.

1.1 - 

Installation safety considerations

The  30XW-PZE  /  30XWHPZE  liquid  chillers  are  classified  as 

“indirect heat exchange system” and are designated to be installed 

in a special machinery room (Class C as per ISO-5149 and EN-

378) where only authorized personnel have access, who are 

acquainted with general and special safety precautions of the 

establishment  and  are  qualified  and  trained  in  monitoring  and 

maintenance. The access limitation device must be installed by 

the customer (e.g. cut-off, enclosure). This machine is not intended 

to operate in an ATEX area.
The refrigerant R-1234ze(E) falls into refrigerant safety group A2L 

in accordance to ISO-5149 and A2 in accordance to EN-378. No 

Charge limitations apply for the level of occupancy is ‘C’. Please 

refer to these standards for further details. This level needs to be 

confirmed by the customer.

After the unit has been received, when it is ready to be installed 

or reinstalled, and before it is started up, it must be inspected for 

damage. Check that the refrigerant circuit(s) is (are) intact, 

especially that no components or pipes have shifted (e.g. following 

a shock). If in doubt, carry out a leak tightness check and verify 

with the manufacturer that the circuit integrity has not been 

impaired. If damage is detected upon receipt, immediately fill a 

claim with the shipping company.
Carrier strongly recommends employing a specialised company 

to unload the machine.
It is compulsory to wear personal protection equipment.

Do not remove the skid or the packaging until the unit is in its final 

position. These units can be moved with a fork lift truck, as long 

as the forks are positioned in the right place 
and direction on the unit. 
The units can also be lifted with slings, using only the designated 

lifting points marked on the unit.
Use slings or lifting beams with the correct capacity, and always 

follow the lifting instructions on the certified drawings supplied with 

the unit. Do not tilt the unit more than 15°.
Safety is only guaranteed, if these instructions are carefully 

followed. If this is not the case, there is a risk of material 

deterioration and injuries to personnel.

Never cover any protection devices.
This applies to the relief valves in the refrigerant or heat transfer 

medium circuits, and the pressure switches.
Ensure that the valves are correctly installed, before operating the 

unit.
DO NOT OBSTRUCT ANY PROTECTIVE DEVICES:

This applies to any fusible plugs, rupture disks and valves fitted 

on the refrigerant or heat transfer fluid circuits. Check whether the 

original protection plugs are still present at the valve outlets. These 

plugs are generally made of plastic and should not be used. If they 

are still present, please remove them. Fit devices at the valve or 

discharge piping outlets to prevent the penetration of foreign 

bodies (dust, building debris, etc.) and atmospheric agents (water 

can form rust or ice). These devices, as well as the discharge 

piping, must not impair operation or lead to a pressure drop that 

is higher than 10% of the set pressure.

Greyed text does not apply to units equipped with option 330 (Low GWP A1 R-515B refrigerant)

Summary of Contents for AquaForce PUREtec 30XW-PZE 1001

Page 1: ...RATION AND M A I N T E N A N C E I N S T R U C T I O N S Original document Water Cooled Liquid Chillers and heat pump AquaForce PUREtec with R 1234ze E or optionally with R 515B refrigerant 30XW PZE 3...

Page 2: ...2...

Page 3: ...perating limits 18 6 2 Minimum chilled water flow 18 6 3 Maximum chilled water flow 18 6 4 Condenser water flow rate 18 6 5 Standard and optional number of water passes 18 6 6 Evaporator and condenser...

Page 4: ...op periodic test 34 13 FINAL SHUTDOWN 35 13 1 Shutting down 35 13 2 Recommendations for disassembly 35 13 3 Fluids to be recovered for treatment 35 13 4 Materials to be recovered for recycling 35 13 5...

Page 5: ...smoking area around the machine 1 1 Installation safety considerations The 30XW PZE 30XWHPZE liquid chillers are classified as indirect heat exchange system and are designated to be installed in a spe...

Page 6: ...ecking that this is allowed by local regulations and authorities This is the responsibility of the operator When the unit is subjected to fire safety devices prevent rupture due to over pressure by re...

Page 7: ...ied and authorised engineer These procedures must be carried out with the unit shut down NOTE The unit must never be left shut down with the liquid line valve closed as liquid refrigerant can be trapp...

Page 8: ...bjective is to prevent penetration of atmospheric humidity and the resulting corrosion on the internal walls and on non protected steel surfaces 1 4 Repair safety considerations Equip the engineers th...

Page 9: ...gerant may expose users and operators to unexpected risks Do not attempt to remove refrigerant circuit components or fittings while the machine is under pressure or while it is running Be sure pressur...

Page 10: ...ave been taken The unit is installed level on an even surface maximum tolerance is 5 mm in both axes There is adequate space above the unit for air flow and to ensure access to the components The numb...

Page 11: ...ons in mm A B C D E F G H 30XW PZE 30XWHPZE 301 1612 800 982 2724 983 141 3 141 3 2600 401 1743 968 980 3059 982 168 3 168 3 2800 451 1743 968 980 3059 982 168 3 168 3 2800 551 1950 1083 1080 3290 118...

Page 12: ...er to the unit name plate to find out the machine weight 3 DIMENSIONS CLEARANCES Dimensions in mm A B C D E F G H 30XW PZE 30XWHPZE 801 1998 1512 1121 4730 1124 219 1 219 1 4500 901 1998 1512 1125 473...

Page 13: ...22 122 152 132 teq CO2 35 7 35 7 44 5 38 7 Oil standard unit Circuit A l 20 20 20 25 25 25 20 20 25 25 Circuit B l 20 20 20 25 Capacity control SmartVuTM electronic expansion valves EXV Minimum capcit...

Page 14: ...9 146 153 97 110 129 129 Circuit B kW 97 110 110 129 Option 81 kW 195 220 239 258 Maximum current drawn Un with option 150B Circuit A A 123 158 179 209 237 249 158 179 209 209 Circuit B A 158 179 179...

Page 15: ...ing the electrical equipment Compliance of the installation to 1999 92 CE directive on minimum requirements for improving the safety and health protection of workers potentially at risk from explosive...

Page 16: ...ssible 2 and is therefore acceptable AB 406 400 6 BC 400 399 1 A 400 394 6 5 3 Power connection disconnect switch Units connection points 30XWPZE 301 651 1 per unit 30XWPZE 801 1101 1 for circuit A 1...

Page 17: ...exceed the connection capacity actually available Special attention must be given to the selection Note The currents considered are given for a machine equipped with a hydraulic module operating at m...

Page 18: ...system flow is less than the minimum unit flow rate the evaporator flow can be recirculated as shown in the diagram For minimum chiller flow rate 1 2 Legend 1 Evaporator 2 Recirculation 6 3 Maximum ch...

Page 19: ...the liquid water or brine Refer to the examples below Conection to buffer tank Bad Good Bad Good 6 9 Evaporator pressure drop curves Units with two evaporator passes standard 30XW PZE 30XWHPZE 10 20 3...

Page 20: ...ase additives or other fluids than those recommended by Carrier are used ensure that the fluids are not considered as a gas and that they belong to class 2 as defined in directive 2014 68 EU Carrier r...

Page 21: ...Re tightening or tightening must be done in accordance with the illustration in the example below NOTE Before this operation we recommend draining the circuit and disconnecting the pipes to be sure t...

Page 22: ...ontrols on the cooling setpoint 8 2 Heating mode Unlike in the cooling mode the unit uses the heating setpoint in this configuration The evaporator leaving water control lowest setpoint taken into con...

Page 23: ...35 7 35 7 38 7 38 7 Circuit B kg 122 122 152 132 teq CO2 35 7 35 7 44 5 38 7 Oil unit with option 150 Circuit A l 20 20 20 25 25 25 20 20 25 25 Circuit B l 20 20 20 25 Capacity control SmartVuTM elect...

Page 24: ...largest compressor Values based on standard Eurovent unit operating conditions evaporator entering leaving water temp 12 C 7 C condenser entering leaving water temp 30 C 35 C 2 Instantaneous start up...

Page 25: ...ator must be included in the supervision and maintenance file Repair Any repair or modification including the replacement of moving parts Must follow local regulations and be made by qualified operato...

Page 26: ...or preventing it from starting if the pressure differential between the inside and the outside of the cabinet is lower than the threshold value This can happen If the cooling fan of the electrical bo...

Page 27: ...3 Restart after high pressure detection After detecting the overpressure it is necessary to manually reset the switched HPS s Using a dull tool with a diameter of less than 6 mm if the PZHH HPS is dea...

Page 28: ...ntactor feedback circuit prevents from restart due to malfunction of contactor Restart allowed after auto check of contactor feedback circuit and HPS sensors inputs Restart not allowed due to discorda...

Page 29: ...ssure drops 301 1101 21 bar evaporator 104 Reinforced evaporator for extension of the maximum water side service pressure to 21 bar standard 10 bar Covers applications with a high water column evapora...

Page 30: ...cation Conformance with Russian regulations 0301 1101 Compliance with Australian regulations 200 Unit approved to Australian code Conformance with Australian regulations 301 1101 Low noise level 257 E...

Page 31: ...nnections see tightening torques table Check and re tighten all control command connections if required see tightening torques table Check the differential switches for correct operation every 6 month...

Page 32: ...wer terminals These precautions must be applied during an intervention that requires the removal of the power conductors connected to the compressor supply terminals The tightening nut of terminal 6 s...

Page 33: ...he compressor The difference in these two pressures will be the pressure drop across the filter check valve and solenoid valve The pressure drop across the check valve and solenoid valve is approximat...

Page 34: ...re part of the circuit compressor discharge 2 Reset all activated alarms 3 Activate the HP test mode for the corresponding circuit via the control interface Enable Quick Test Mode Quick Test Menu QCK_...

Page 35: ...the unit can be recycled for another purpose 13 3 Fluids to be recovered for treatment Refrigerant Heat transfer fluid depending on the installation water brine solution etc Compressor oil 13 4 Mater...

Page 36: ...Electrical circuit wiring has been sized and installed properly Unit ground wire has been connected Electrical circuit protection has been sized and installed properly All terminals are tight All chi...

Page 37: ...chiller is not switched on until corrective measures have been taken Check cooler water loop Water loop volume litres Calculated volume litres 3 25 litres nominal kW capacity for air conditioning 6 5...

Page 38: ...PPENDICES PROVIDED IN THE DOCUMENT WALLET WITH THE INSTRUCTION MANUAL 15 1 Appendix 1 Declaration of conformity 15 2 Appendix 2 Wiring diagram 15 3 Appendix 3 Machine PID 15 4 Appendix 4 Dimensional d...

Page 39: ...39...

Page 40: ...No 10132 10 2021 Supersedes order No 10132 09 2020 Manufacturedby CarrierSCS Montluel France Manufacturer reserves the right to change any product specifications without notice Printed in the European...

Reviews: