background image

20

7 - WATER CONNECTIONS

ATTENTION:  Before  carrying  out  any  water  connections 

install the water box purge plugs (one plug per water box in 

the lower section supplied in the control box).

For size and position of the heat exchanger water inlet and outlet 

connections refer to the certified dimensional drawings supplied 

with the unit.
The water pipes must not transmit any radial or axial force to the 

heat exchangers nor any vibration.

The  water  supply  must  be  analysed  and  appropriate  filtering, 

treatment, control devices, isolation and bleed valves and circuits 

built in, to prevent corrosion, fouling and deterioration of the pump 

fittings. Consult either a water treatment specialist or appropriate 

literature on the subject.

7.1 - 

Operating precautions

The water circuit should be designed to have the least number of 

elbows and horizontal pipe runs at different levels. Below the main 

points to be checked for the connection:

• Comply with the water inlet and outlet connections shown 

on the unit.

• Install manual or automatic air purge valves at all high points 

in the circuit(s).

• Use a pressure reducer to maintain pressure in the circuit(s) 

and install a relief valve as well as an expansion tank.

• Install thermometers in both the entering and leaving water 

connections.

• Install drain connections at all low points to allow the whole 

circuit to be drained.

• Install stop valves, close to the entering and leaving water 

connections.

• Use flexible connections to reduce the transmission  

of vibrations.

• Insulate all pipework, after testing for leaks, both to reduce 

heat gains and to prevent condensation.

• Cover the insulation with a vapour barrier.

Where  there  are  particles  in  the  fluid  that  could  foul  the  heat 

exchanger, a screen filter should be installed ahead of the pump, 

or directly at the exchanger inlet in case the pump is more than 

20m away. The mesh size of the filter must be 1.2 mm.

Before the system start-up verify that the water circuits are 

connected to the appropriate heat exchangers (e.g. no reversal 

between evaporator and condenser). Do not introduce any 

significant static or dynamic pressure into the heat exchange circuit 

(with regard to the design operating pressures). Before any start-

up  verify  that  the  heat  exchange  fluid  is  compatible  with  the 

materials and the water circuit coating. The use of different metals 

on hydraulic piping could generate eletrolytic pairs and 

consequently  corrosion.  It  could  be  needed  to  add  sacrificial 

anodes. In case additives or other fluids than those recommended 

by Carrier are used, ensure that the fluids are not considered as 

a  gas,  and  that  they  belong  to  class  2,  as  defined  in  directive 

2014/68/EU.

Carrier recommendations on heat exchange fluids:

• No NH

4+

 ammonium ions in the water, they are very 

detrimental for copper. This is one of the most important 

factors for the operating life of copper piping. A content of 

several tenths of mg/l will badly corrode the copper over 

time.

• Cl- Chloride ions are detrimental for copper with a risk of 

perforations by corrosion by puncture. If possible keep 

below 125 mg/l.

• SO

4

2-

 sulphate ions can cause perforating corrosion, if their 

content is above 30 mg/l.

• 

No fluoride ions (<0,1 mg/l).

• No Fe

2+

 and Fe

3+

 ions with non negligible levels of dissolved 

oxygen must be present. Dissolved iron < 5 mg/l with 

dissolved oxygen < 5 mg/l.

• Dissolved silica: silica is an acid element of water and can 

also lead to corrosion risks. Content < 1 mg/l.

• Water hardness: > 0,5 mmol/l. Values between 1 and 2,5 

can be recommended. This will facilitate scale deposit that 

can limit corrosion of copper. Values that are too high can 

cause piping blockage over time. A total alkalimetric titre 

(TAC) below 100 mg/l is desirable.

• Dissolved oxygen: Any sudden change in water oxygenation 

conditions must be avoided. It is as detrimental to 

deoxygenate the water by mixing it with inert gas as it is to 

over-oxygenate it by mixing it with pure oxygen. The 

disturbance of the oxygenation conditions encourages 

destabilisation of copper hydroxides and enlargement of 

particles.

• Electric conductivity 10-600µS/cm.

• pH: Ideal case pH neutral at 20-25°C 7 < pH < 8

When the water circuit must be emptied for longer than one month 

or immediately if the water does not comply with the above 

description, the circuit must be either totally dried or placed under 

0.5 bar maximum nitrogen charge. This is done to avoid any 

damage of the exchanger copper tubes with corrosion by 

differential aeration. In case of nitrogen charge, the circuit must 

be equipped with relief valves to avoid overpressure due to 

refrigerant leakage. Charging and removing heat exchange fluids 

should be done with devices that must be included on the water 

circuit by the installer. Never use the unit heat exchangers to add 

heat exchange fluid.

CAUTION: Filling, completing and draining the water circuit 

charge must be done by qualified personnel, using the air 

purges and materials that are suitable for the products.
Charging and removing heat exchange fluids should be done 

with devices that must be included on the water circuit by the 

installer.  Never  use  the  unit  heat  exchangers  to  add  heat 

exchange fluid. 

Summary of Contents for AquaForce PUREtec 30XW-PZE 1001

Page 1: ...RATION AND M A I N T E N A N C E I N S T R U C T I O N S Original document Water Cooled Liquid Chillers and heat pump AquaForce PUREtec with R 1234ze E or optionally with R 515B refrigerant 30XW PZE 3...

Page 2: ...2...

Page 3: ...perating limits 18 6 2 Minimum chilled water flow 18 6 3 Maximum chilled water flow 18 6 4 Condenser water flow rate 18 6 5 Standard and optional number of water passes 18 6 6 Evaporator and condenser...

Page 4: ...op periodic test 34 13 FINAL SHUTDOWN 35 13 1 Shutting down 35 13 2 Recommendations for disassembly 35 13 3 Fluids to be recovered for treatment 35 13 4 Materials to be recovered for recycling 35 13 5...

Page 5: ...smoking area around the machine 1 1 Installation safety considerations The 30XW PZE 30XWHPZE liquid chillers are classified as indirect heat exchange system and are designated to be installed in a spe...

Page 6: ...ecking that this is allowed by local regulations and authorities This is the responsibility of the operator When the unit is subjected to fire safety devices prevent rupture due to over pressure by re...

Page 7: ...ied and authorised engineer These procedures must be carried out with the unit shut down NOTE The unit must never be left shut down with the liquid line valve closed as liquid refrigerant can be trapp...

Page 8: ...bjective is to prevent penetration of atmospheric humidity and the resulting corrosion on the internal walls and on non protected steel surfaces 1 4 Repair safety considerations Equip the engineers th...

Page 9: ...gerant may expose users and operators to unexpected risks Do not attempt to remove refrigerant circuit components or fittings while the machine is under pressure or while it is running Be sure pressur...

Page 10: ...ave been taken The unit is installed level on an even surface maximum tolerance is 5 mm in both axes There is adequate space above the unit for air flow and to ensure access to the components The numb...

Page 11: ...ons in mm A B C D E F G H 30XW PZE 30XWHPZE 301 1612 800 982 2724 983 141 3 141 3 2600 401 1743 968 980 3059 982 168 3 168 3 2800 451 1743 968 980 3059 982 168 3 168 3 2800 551 1950 1083 1080 3290 118...

Page 12: ...er to the unit name plate to find out the machine weight 3 DIMENSIONS CLEARANCES Dimensions in mm A B C D E F G H 30XW PZE 30XWHPZE 801 1998 1512 1121 4730 1124 219 1 219 1 4500 901 1998 1512 1125 473...

Page 13: ...22 122 152 132 teq CO2 35 7 35 7 44 5 38 7 Oil standard unit Circuit A l 20 20 20 25 25 25 20 20 25 25 Circuit B l 20 20 20 25 Capacity control SmartVuTM electronic expansion valves EXV Minimum capcit...

Page 14: ...9 146 153 97 110 129 129 Circuit B kW 97 110 110 129 Option 81 kW 195 220 239 258 Maximum current drawn Un with option 150B Circuit A A 123 158 179 209 237 249 158 179 209 209 Circuit B A 158 179 179...

Page 15: ...ing the electrical equipment Compliance of the installation to 1999 92 CE directive on minimum requirements for improving the safety and health protection of workers potentially at risk from explosive...

Page 16: ...ssible 2 and is therefore acceptable AB 406 400 6 BC 400 399 1 A 400 394 6 5 3 Power connection disconnect switch Units connection points 30XWPZE 301 651 1 per unit 30XWPZE 801 1101 1 for circuit A 1...

Page 17: ...exceed the connection capacity actually available Special attention must be given to the selection Note The currents considered are given for a machine equipped with a hydraulic module operating at m...

Page 18: ...system flow is less than the minimum unit flow rate the evaporator flow can be recirculated as shown in the diagram For minimum chiller flow rate 1 2 Legend 1 Evaporator 2 Recirculation 6 3 Maximum ch...

Page 19: ...the liquid water or brine Refer to the examples below Conection to buffer tank Bad Good Bad Good 6 9 Evaporator pressure drop curves Units with two evaporator passes standard 30XW PZE 30XWHPZE 10 20 3...

Page 20: ...ase additives or other fluids than those recommended by Carrier are used ensure that the fluids are not considered as a gas and that they belong to class 2 as defined in directive 2014 68 EU Carrier r...

Page 21: ...Re tightening or tightening must be done in accordance with the illustration in the example below NOTE Before this operation we recommend draining the circuit and disconnecting the pipes to be sure t...

Page 22: ...ontrols on the cooling setpoint 8 2 Heating mode Unlike in the cooling mode the unit uses the heating setpoint in this configuration The evaporator leaving water control lowest setpoint taken into con...

Page 23: ...35 7 35 7 38 7 38 7 Circuit B kg 122 122 152 132 teq CO2 35 7 35 7 44 5 38 7 Oil unit with option 150 Circuit A l 20 20 20 25 25 25 20 20 25 25 Circuit B l 20 20 20 25 Capacity control SmartVuTM elect...

Page 24: ...largest compressor Values based on standard Eurovent unit operating conditions evaporator entering leaving water temp 12 C 7 C condenser entering leaving water temp 30 C 35 C 2 Instantaneous start up...

Page 25: ...ator must be included in the supervision and maintenance file Repair Any repair or modification including the replacement of moving parts Must follow local regulations and be made by qualified operato...

Page 26: ...or preventing it from starting if the pressure differential between the inside and the outside of the cabinet is lower than the threshold value This can happen If the cooling fan of the electrical bo...

Page 27: ...3 Restart after high pressure detection After detecting the overpressure it is necessary to manually reset the switched HPS s Using a dull tool with a diameter of less than 6 mm if the PZHH HPS is dea...

Page 28: ...ntactor feedback circuit prevents from restart due to malfunction of contactor Restart allowed after auto check of contactor feedback circuit and HPS sensors inputs Restart not allowed due to discorda...

Page 29: ...ssure drops 301 1101 21 bar evaporator 104 Reinforced evaporator for extension of the maximum water side service pressure to 21 bar standard 10 bar Covers applications with a high water column evapora...

Page 30: ...cation Conformance with Russian regulations 0301 1101 Compliance with Australian regulations 200 Unit approved to Australian code Conformance with Australian regulations 301 1101 Low noise level 257 E...

Page 31: ...nnections see tightening torques table Check and re tighten all control command connections if required see tightening torques table Check the differential switches for correct operation every 6 month...

Page 32: ...wer terminals These precautions must be applied during an intervention that requires the removal of the power conductors connected to the compressor supply terminals The tightening nut of terminal 6 s...

Page 33: ...he compressor The difference in these two pressures will be the pressure drop across the filter check valve and solenoid valve The pressure drop across the check valve and solenoid valve is approximat...

Page 34: ...re part of the circuit compressor discharge 2 Reset all activated alarms 3 Activate the HP test mode for the corresponding circuit via the control interface Enable Quick Test Mode Quick Test Menu QCK_...

Page 35: ...the unit can be recycled for another purpose 13 3 Fluids to be recovered for treatment Refrigerant Heat transfer fluid depending on the installation water brine solution etc Compressor oil 13 4 Mater...

Page 36: ...Electrical circuit wiring has been sized and installed properly Unit ground wire has been connected Electrical circuit protection has been sized and installed properly All terminals are tight All chi...

Page 37: ...chiller is not switched on until corrective measures have been taken Check cooler water loop Water loop volume litres Calculated volume litres 3 25 litres nominal kW capacity for air conditioning 6 5...

Page 38: ...PPENDICES PROVIDED IN THE DOCUMENT WALLET WITH THE INSTRUCTION MANUAL 15 1 Appendix 1 Declaration of conformity 15 2 Appendix 2 Wiring diagram 15 3 Appendix 3 Machine PID 15 4 Appendix 4 Dimensional d...

Page 39: ...39...

Page 40: ...No 10132 10 2021 Supersedes order No 10132 09 2020 Manufacturedby CarrierSCS Montluel France Manufacturer reserves the right to change any product specifications without notice Printed in the European...

Reviews: